UAE Baseline - Estidama

Target Energy Consumption (kWh/m2.year)

 

Plugin Values

  Residential General
Wall Insulation (W/m2.K) 0.3 0.3
Floor Insulation (W/m2.K) 1.65 1.65
Roof Insulation (W/m2.K) 0.2 0.2
Glazing U-Factor (W/m2.K) 1.9 1.9
Visible Light Transmittance** 0.42 0.42
Solar Heat Gain Coefficient 0.3 0.3
Heating Efficiency**  0.85 0.85
Cooling Efficiency** 3 3
Infiltration Rate (m3/m2.h) 10 10
Ventilation Rate (L/m3.s) 0.2 0.2
Appliance (W/m2)** 2.7 8.1
Lighting (W/m2) 6.8 8.7
Daylight Response Efficiency** 0 0

 

Web App Values

Envelope Parameters

Wall Insulation (W/m2.K) 0.3
Floor Insulation (W/m2.K) 1.65
Roof Insulation (W/m2.K) 0.2
Glazing U-Factor (W/m2.K) 1.9
Solar Heat Gain Coefficient 0.3

 

HVAC Parameters

  Residential Other
Design Fan Power (kW.s/m3) - Central Mechanical 1.8

1.8

Heating COP** 0.85 0.85
Cooling COP (Averaged) 3
Ventilation Rate (L/m3.s) 0.2 0.2

 

Space Uses Parameters

  Residential Other
Lighting Power Density (W/m2)** 6.8 8.7
Plug Load Power Density (W/m2) 2.7 8.1
Heating Setpoint (°C)** 19 19
Cooling Setpoint (°C)** 22 22
Occupant Density** 1 person / 37m2 1 person / 14m2

 

** Typical value inputted as no value provided

References

Estidama Pearl Building Rating System 

Estidama Consultants Guide

Estidama Prescriptive Pathway (Buildings <5000m2

Was this article helpful?
1 out of 1 found this helpful

Comments

  • Avatar
    Didier Curet

    ventilation rate should not be l/m2.s instead of m3?