Target Energy Consumption (kWh/m2.year)
Building Type | Energy Target (kWh/m2.year) | |
Residential | Normal | 52.5 (+1650kWh/year for the heated floor area) |
Low Energy | 30 (+1600kWh/year for the heated floor area) | |
Other | Normal | 71.3 (+1650kWh/year for the heated floor area) |
Low Energy | 41 (+1100kWh/year for the heated floor area) |
Plugin Values
Wall Insulation (W/m2.K) | 0.15 |
Floor Insulation (W/m2.K) | 0.40 |
Roof Insulation (W/m2.K) | 0.10 |
Glazing U-Factor (W/m2.K) | 1.40 |
Visible Light Transmittance** | 0.75 |
Solar Heat Gain Coefficient** | 0.75 |
Heating Efficiency | 3.1 (Heat Pump) |
Cooling Efficiency** | 3 |
Infiltration Rate (m3/m2.h) | 3.6 |
Ventilation Rate (L/s.person) | 3 |
Appliance** | 4 |
Lighting** | 4 |
Daylight Response Efficiency** | 0 |
Web App Values
Envelope Parameters
Wall Insulation (W/m2.K) | 0.15 | |
Floor Insulation (W/m2.K) | 0.40 | |
Roof Insulation (W/m2.K) | 0.10 | |
Glazing U-Factor (W/m2.K) | 1.40 | |
Solar Heat Gain Coefficient | 0.75 | |
Leakage | Standard Ceilings | 5.4 |
Standard Ceilings, Low Energy | 3.6 | |
High Ceilings | 1.8 | |
High Ceilings, Low Energy | 1.08 |
HVAC Parameters
Design Fan Power (kW.s/m3) |
CAV: 1.8 |
VAV: 1.5 |
||
Heating COP |
Domestic Heat Pump: 3.1 |
Heat Recovery & Heat Pump: 3.6 |
||
Cooling COP** | 3 | |||
Ventilation Rate (L/m3.s) | 0.35 |
** Typical value inputted as no value provided