Norway Baseline - TEK10

Target Energy Consumption (kWh/m2.year)

SEE TEK10 - Section 14-4 Table.

Note: this has been updated to 01/01/2016 amendment. 

 

Plugin Values

  Residential Other
Wall Insulation (W/m2.K) 0.18 0.18
Floor Insulation (W/m2.K) 0.15 0.15
Roof Insulation (W/m2.K) 0.13 0.13
Glazing U-Factor (W/m2.K) 1.2 1.2
Visible Light Transmittance** 0.42 0.42
Solar Heat Gain Coefficient** 0.5 0.5
Heating Efficiency 0.7 0.8
Cooling Efficiency** 3 3
Infiltration Rate (m3/m2.h)* 2.8 4
Ventilation Rate (L/m3.s) 5 10
Appliance (W/m2)** 2.7 8.1
Lighting (W/m2)** 5.5 8.8
Daylight Response Efficiency** 0 0

* Systems Webapp infiltration: 0.075 Air Changes

 

HVAC Parameters

  Residential Other
Design Fan Power (kW.s/m3) 2.5

2

Heating COP 0.7 0.8
Cooling COP** 3
Ventilation Rate (L/m3.s) 0.33 0.69

 

Space Uses Parameters

  Residential Other
Lighting Power Density (W/m2) 5.5 8.8
Plug Load Power Density (W/m2) 2.7 8.1
Heating Setpoint (°C) 19 19
Cooling Setpoint (°C) 22 22
Occupant Density 1 person / 37m2 1 person / 14m2

 

** Typical value inputted as no value provided

References

TEK 10 - Norwegian (2016 update)

TEK 10 - Norwegian

TEK 10 - English

 

 