Swedish Baseline - BBR 19 BFS 2011:26

Target Energy Consumption (kWh/m2.year)

Climate Zone I II III
Non-Electrically Heated Building (kWh/m2.year) 130 110 90
Electrically Heated Building (kWh/m2.year) 95 75 55

 

Plugin Values

Wall Insulation (W/m2.K) 0.18
Floor Insulation (W/m2.K) 0.15
Roof Insulation (W/m2.K) 0.13
Glazing U-Factor (W/m2.K)* 1.15
Visible Light Transmittance** 0.72
Solar Heat Gain Coefficient 0.75
Heating Efficiency** 0.85
Cooling Efficiency** 3
Infiltration Rate (m3/m2.h) 2.88
Ventilation Rate (L/m3.s) 0.35
Appliance**
Lighting**
Daylight Response Efficiency**

 

Web App Values

Envelope Parameters

Wall Insulation (W/m2.K) 0.18
Floor Insulation (W/m2.K) 0.15
Roof Insulation (W/m2.K) 0.13
Glazing U-Factor (W/m2.K) 1.15
Solar Heat Gain Coefficient 0.75

 

HVAC Parameters

Design Fan Power (kW.s/m3)

Extract and supply air with heat recovery:

2.0

Extract and supply air without heat recovery:

1.5

Extract air with recovery:

1.0

Extract air:

0.6

Heating COP** 0.85
Cooling COP**
Ventilation Rate (L/m3.s) 0.35

 

* Assumed based on a target overall building thermal transmittance of 0.4 (W/m2.K).

** Typical value inputted as no value provided

 

References

http://www.boverket.se/en/start-in-english/publications/2012/building-regulations-bbr/

http://www.ecofys.com/files/files/ecofys_2007_uvaluesenergyperformancebuildings.pdf

 