ASHRAE 90.1 - 2010 - US Units

Office

Space Uses Parameters:

Parameter

Value (For all climate locations)

Lighting power density (W/ft2)

0.9

Plug Load power density (W/ft2)

0.7

Heating Setpoint (F)

66.2

Cooling Setpoint (F)

71.6

Occupant Density

1 person / 150 ft2

 

Envelope parameters: 

Parameter\Climate zone

1

2

3

4

5

6

 

Roof R-Value (ft2.h.F/BTU)

15.96

20.88

20.88

20.88

20.88

20.88

Wall R-Value (ft2.h.F/BTU)

1.73

6.63

8.14

9.63

11.12

12.51

Floor R-Value (ft2.h.F/BTU)

3.11

9.36

9.36

9.36

11.12

12.51

Glazing U-Value (BTU/ft2.h.F)

1.23

0.77

0.66

0.41

0.36

0.36

Glazing SHGC

0.25

0.25

0.25

0.4

0.4

0.4

Infiltration rate (cfm/ft2)

0.394

0.394

0.394

0.394

0.394

0.394

 

HVAC Parameters:

Parameter

Value (For all climate locations)

Heating Efficiency

0.85

Cooling Efficiency

3

Ventilation Rate (cfm/ft2)

0.06

 

Residential 

Space Uses Parameters:

Parameter

Value (For all climate locations)

Lighting power density (W/ft2)

0.6

Plug Load power density (W/ft2)

0.3

Heating Setpoint (F)

66.2

Cooling Setpoint (F)

71.6

Occupant Density

1 person / 398 ft2

 

Envelope parameters: 

Parameter\Climate zone

1

2

3

4

5

6

 

Roof R-Value (ft2.h.F/BTU)

20.88

20.88

20.88

20.88

20.88

20.88

Wall R-Value (ft2.h.F/BTU)

6.63

8.14

9.63

11.12

12.51

14.09

Floor R-Value (ft2.h.F/BTU)

3.11

11.50

9.36

13.52

15.65

17.63

Glazing U-Value (BTU/ft2.h.F)

1.23

0.77

0.66

0.41

0.36

0.36

Glazing SHGC

0.25

0.25

0.25

0.4

0.4

0.4

Infiltration rate (cfm/ft2)

0.394

0.394

0.394

0.394

0.394

0.394

 

 

HVAC Parameters:

Parameter

Value (For all climate locations)

Heating Efficiency

0.85

Cooling Efficiency

3

Ventilation Rate (cfm/ft2)

0.04

 

The sources for the EUI benchmarks are:

  1. US Residential: 2003 Residential Energy Consumption Survey (RECS)
  2. US Office: 2003 Commercial Buildings Energy Consumption Survey (CBECS)

 

 

Was this article helpful?
5 out of 5 found this helpful

Comments

  • Avatar
    John Nichols

    It would be helpful to have these same tables updated for the new "School" usage occupancy that has been added to the plugin since these were first authored.  Thank you!

  • Avatar
    Katrina Schoen

    Hi John,

    Thanks for the comment - good point!  The envelope properties for "School" and "Office" are actually the same, since they are both nonresidential under ASHRAE 90.1.  The two spaces do differ for lighting loads, plug loads, and occupancy schedule.

    Best,

    Katrina

  • Avatar
    Sean Quinn

    As we have several projects targeting LEED v3, it would be great to have a breakdown of both ASHRAE 90.1-2007, US & Metric.

  • Avatar
    Greg McDowell

    Should I assume that these values are an average, or weighted average, of the values in 90.1? For example, I understand that mass walls should be 5.7 in zone 2 but the value here is 8.14.

  • Avatar
    Qinheng Zhang

    Hello, Greg

    As far as I know, The mass wall in zone 2 should be 0.123 (U factor), so 8.14 is the right value.