Space Use Parameters:

Parameter

Office

Residential

Lighting Power Density (W/m2)

12

6

Plug Load Density (W/m2)

15

3

Heating setpoint (C)

19

19

Cooling setpoint (C)

22

22

Occupant Density

1 person/14 m2

1 person/37 m2

 

Envelope parameters: 

Parameter\Building Type

Office and Residential

Wall U-value (W/m2-K)

0.36

Roof U-value (W/m2-K)

0.36

Ground floor U-value (W/m2-K)

0.36

Glazing U-value (W/m2-K)

2.4

Glazing SHGC

0.6

 

HVAC system efficiencies: 

Parameter\Building Type

Office and Residential

Heating efficiency

0.85

Cooling efficiency

3.0