Table of Contents

Program Version:EnergyPlus, Version 8.5.0-c87e61b44b, YMD=2017.11.30 14:32

Tabular Output Report in Format: HTML

Building: Building 1

Environment: RUN PERIOD 1 ** 3600175 - UK WG data WMO#=03853

Simulation Timestamp: 2017-11-30 14:32:12


Table of Contents

Top
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
Outdoor Air Summary

Zone Component Load Summary

| L001_P01 | L001_P02 | L001_P03 | L001_P04 | L001_P05 | L001_P06 | L001_P07 | L001_P08 | L001_P09 | L001_P10 | L001_P11 | L001_P12 | L001_P13 | L001_P14 | L001_P15 | L002_P01 | L002_P02 | L002_P03 | L002_P04 | L002_P05 | L002_P06 | L002_P07 | L002_P08 | L002_P09 | L002_P10 | L002_P11 | L002_P12 | L002_P13 | L002_P14 | L002_P15 | L003_P01 | L003_P02 | L003_P03 | L003_P04 | L003_P05 | L003_P06 | L003_P07 | L003_P08 | L003_P09 | L003_P10 | L003_P11 | L003_P12 | L003_P13 | L003_P14 | L003_P15 |

Tariff Report

| ELECTRICSERVICETARIFF | GASSERVICETARIFF |

Economics Results Summary Report

| Entire Facility |

Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2017-11-30 14:32:12

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
3600175 ANN HTG 99.6% CONDNS DB -0.90 0.00 -2.70 Dewpoint [C] 6.70 20.00
3600175 ANN CLG .4% CONDNS ENTH=>MDB 32.30 8.40 22.10 Dewpoint [C] 4.30 210.00
3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 6) 29.00 8.40 19.50 Dewpoint [C] 5.70 290.00
3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 7) 29.00 8.40 19.50 Dewpoint [C] 5.70 290.00
3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 8) 29.00 8.40 19.50 Dewpoint [C] 5.70 290.00
3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 9) 29.00 8.40 19.50 Dewpoint [C] 5.70 290.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2017-11-30 14:32:12

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
L001_P01:0:EXTWALL_3_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 14.00 11.48 0.00 90.00 N
L001_P01:0:SLABFLOOR_1 SLAB_FLOOR 0.30 0.208 0.216 44.00 44.00 0.00 180.00  
L001_P02:0:EXTWALL_3_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 14.00 9.71 90.00 90.00 E
L001_P02:0:EXTWALL_4_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 24.50 20.09 0.00 90.00 N
L001_P02:0:SLABFLOOR_1 SLAB_FLOOR 0.30 0.208 0.216 84.00 84.00 0.00 180.00  
L001_P03:0:EXTWALL_3_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 3.50 2.87 0.00 90.00 N
L001_P03:0:EXTWALL_4_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 3.50 2.28 270.00 90.00 W
L001_P03:0:EXTWALL_5_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 10.50 8.61 0.00 90.00 N
L001_P03:0:EXTWALL_6_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L001_P03:0:EXTWALL_7_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 16.59 13.61 0.00 90.00 N
L001_P03:0:SLABFLOOR_1 SLAB_FLOOR 0.30 0.208 0.216 72.93 72.93 0.00 180.00  
L001_P04:0:EXTWALL_3_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 14.00 11.48 0.00 90.00 N
L001_P04:0:EXTWALL_4_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 28.00 19.42 90.00 90.00 E
L001_P04:0:EXTWALL_5_SOUTH_179 SOUTH WALL BRICK 0.60 0.250 0.260 21.00 16.17 180.00 90.00 S
L001_P04:0:EXTWALL_6_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 14.91 12.22 0.00 90.00 N
L001_P04:0:EXTWALL_7_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 3.50 2.28 270.00 90.00 W
L001_P04:0:EXTWALL_8_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 10.50 8.61 0.00 90.00 N
L001_P04:0:EXTWALL_9_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L001_P04:0:SLABFLOOR_1 SLAB_FLOOR 0.30 0.208 0.216 93.07 93.07 270.00 180.00  
L001_P05:0:EXTWALL_3_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 10.50 7.28 90.00 90.00 E
L001_P05:0:EXTWALL_4_SOUTH_181 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L001_P05:0:EXTWALL_5_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 5.25 3.64 90.00 90.00 E
L001_P05:0:EXTWALL_6_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 16.50 11.45 90.00 90.00 E
L001_P05:0:EXTWALL_7_NORTH_359 NORTH WALL BRICK 0.60 0.250 0.260 3.50 2.87 0.00 90.00 N
L001_P05:0:SLABFLOOR_1 SLAB_FLOOR 0.30 0.208 0.216 58.29 58.29 0.00 180.00  
L001_P06:0:EXTWALL_3_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 10.50 7.28 90.00 90.00 E
L001_P06:0:EXTWALL_4_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L001_P06:0:EXTWALL_5_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 10.50 7.28 90.00 90.00 E
L001_P06:0:EXTWALL_6_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 5.25 3.64 90.00 90.00 E
L001_P06:0:EXTWALL_7_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 3.50 2.87 0.00 90.00 N
L001_P06:0:SLABFLOOR_1 SLAB_FLOOR 0.30 0.208 0.216 48.00 48.00 0.00 180.00  
L001_P07:0:EXTWALL_3_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 14.00 9.71 90.00 90.00 E
L001_P07:0:EXTWALL_4_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 14.00 10.78 180.00 90.00 S
L001_P07:0:EXTWALL_5_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L001_P07:0:EXTWALL_6_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 10.50 8.09 180.00 90.00 S
L001_P07:0:EXTWALL_7_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 3.50 2.28 270.00 90.00 W
L001_P07:0:EXTWALL_8_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 5.25 4.04 180.00 90.00 S
L001_P07:0:SLABFLOOR_1 SLAB_FLOOR 0.30 0.208 0.216 54.00 54.00 180.00 180.00  
L001_P08:0:EXTWALL_3_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 3.50 2.28 270.00 90.00 W
L001_P08:0:EXTWALL_4_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 14.00 10.78 180.00 90.00 S
L001_P08:0:EXTWALL_5_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 5.25 4.04 180.00 90.00 S
L001_P08:0:EXTWALL_6_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L001_P08:0:EXTWALL_7_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 10.50 8.09 180.00 90.00 S
L001_P08:0:SLABFLOOR_1 SLAB_FLOOR 0.30 0.208 0.216 54.00 54.00 0.00 180.00  
L001_P09:0:EXTWALL_3_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 14.00 10.78 180.00 90.00 S
L001_P09:0:EXTWALL_4_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L001_P09:0:EXTWALL_5_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 15.75 12.13 180.00 90.00 S
L001_P09:0:SLABFLOOR_1 SLAB_FLOOR 0.30 0.208 0.216 55.50 55.50 0.00 180.00  
L001_P10:0:EXTWALL_3_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 5.25 4.04 180.00 90.00 S
L001_P10:0:EXTWALL_4_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L001_P10:0:EXTWALL_5_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 10.50 8.09 180.00 90.00 S
L001_P10:0:EXTWALL_6_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 3.50 2.28 270.00 90.00 W
L001_P10:0:EXTWALL_7_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 14.00 10.78 180.00 90.00 S
L001_P10:0:SLABFLOOR_1 SLAB_FLOOR 0.30 0.208 0.216 62.50 62.50 0.00 180.00  
L001_P11:0:EXTWALL_3_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 5.25 3.43 270.00 90.00 W
L001_P11:0:EXTWALL_4_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 14.00 9.13 270.00 90.00 W
L001_P11:0:EXTWALL_5_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L001_P11:0:EXTWALL_6_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 10.50 6.85 270.00 90.00 W
L001_P11:0:EXTWALL_7_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 3.50 2.87 0.00 90.00 N
L001_P11:0:SLABFLOOR_1 SLAB_FLOOR 0.30 0.208 0.216 45.50 45.50 180.00 180.00  
L001_P12:0:EXTWALL_3_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 5.25 3.43 270.00 90.00 W
L001_P12:0:EXTWALL_4_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L001_P12:0:EXTWALL_5_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 10.50 6.85 270.00 90.00 W
L001_P12:0:EXTWALL_6_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 3.50 2.87 0.00 90.00 N
L001_P12:0:EXTWALL_7_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 7.00 4.57 270.00 90.00 W
L001_P12:0:SLABFLOOR_1 SLAB_FLOOR 0.30 0.208 0.216 35.50 35.50 0.00 180.00  
L001_P13:0:EXTWALL_3_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 7.00 4.57 270.00 90.00 W
L001_P13:0:EXTWALL_4_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L001_P13:0:EXTWALL_5_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 14.00 9.13 270.00 90.00 W
L001_P13:0:SLABFLOOR_1 SLAB_FLOOR 0.30 0.208 0.216 34.00 34.00 270.00 180.00  
L001_P14:0:EXTWALL_3_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 24.50 17.00 270.00 90.00 W
L001_P14:0:EXTWALL_4_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 21.00 16.17 0.00 90.00 N
L001_P14:0:EXTWALL_5_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 21.00 17.22 0.00 90.00 N
L001_P14:0:EXTWALL_6_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 49.00 31.97 90.00 90.00 E
L001_P14:0:EXTWALL_7_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 21.00 16.17 0.00 90.00 N
L001_P14:0:EXTWALL_8_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 49.00 33.99 270.00 90.00 W
L001_P14:0:EXTWALL_9_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 14.00 10.78 0.00 90.00 N
L001_P14:0:EXTWALL_10_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 35.00 22.84 90.00 90.00 E
L001_P14:0:EXTWALL_11_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 7.00 5.74 180.00 90.00 S
L001_P14:0:EXTWALL_12_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 4.50 3.12 270.00 90.00 W
L001_P14:0:EXTWALL_13_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 42.00 34.44 180.00 90.00 S
L001_P14:0:SLABFLOOR_1 SLAB_FLOOR 0.30 0.208 0.216 515.71 515.71 0.00 180.00  
L001_P15:0:EXTWALL_3_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 7.00 5.74 0.00 90.00 N
L001_P15:0:EXTWALL_4_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L001_P15:0:EXTWALL_5_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 28.00 18.27 270.00 90.00 W
L001_P15:0:EXTWALL_6_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 17.50 14.35 0.00 90.00 N
L001_P15:0:EXTWALL_7_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 10.50 6.85 270.00 90.00 W
L001_P15:0:SLABFLOOR_1 SLAB_FLOOR 0.30 0.208 0.216 62.00 62.00 270.00 180.00  
L002_P01:0:EXTWALL_3_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 14.00 11.48 0.00 90.00 N
L002_P02:0:EXTWALL_3_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 14.00 9.71 90.00 90.00 E
L002_P02:0:EXTWALL_4_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 24.50 20.09 0.00 90.00 N
L002_P03:0:EXTWALL_3_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 3.50 2.28 270.00 90.00 W
L002_P03:0:EXTWALL_4_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 10.50 8.61 0.00 90.00 N
L002_P03:0:EXTWALL_5_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L002_P03:0:EXTWALL_6_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 16.59 13.61 0.00 90.00 N
L002_P03:0:EXTWALL_7_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 3.50 2.87 0.00 90.00 N
L002_P04:0:EXTWALL_3_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 3.50 2.28 270.00 90.00 W
L002_P04:0:EXTWALL_4_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 10.50 8.61 0.00 90.00 N
L002_P04:0:EXTWALL_5_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L002_P04:0:EXTWALL_6_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 14.00 11.48 0.00 90.00 N
L002_P04:0:EXTWALL_7_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 28.00 19.42 90.00 90.00 E
L002_P04:0:EXTWALL_8_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 21.00 16.17 180.00 90.00 S
L002_P04:0:EXTWALL_9_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 14.91 12.22 0.00 90.00 N
L002_P05:0:EXTWALL_3_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 10.50 7.28 90.00 90.00 E
L002_P05:0:EXTWALL_4_SOUTH_181 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L002_P05:0:EXTWALL_5_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 5.25 3.64 90.00 90.00 E
L002_P05:0:EXTWALL_6_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 16.50 11.45 90.00 90.00 E
L002_P05:0:EXTWALL_7_NORTH_359 NORTH WALL BRICK 0.60 0.250 0.260 3.50 2.87 0.00 90.00 N
L002_P06:0:EXTWALL_3_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 10.50 7.28 90.00 90.00 E
L002_P06:0:EXTWALL_4_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L002_P06:0:EXTWALL_5_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 10.50 7.28 90.00 90.00 E
L002_P06:0:EXTWALL_6_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 5.25 3.64 90.00 90.00 E
L002_P06:0:EXTWALL_7_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 3.50 2.87 0.00 90.00 N
L002_P07:0:EXTWALL_3_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 5.25 4.04 180.00 90.00 S
L002_P07:0:EXTWALL_4_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 14.00 9.71 90.00 90.00 E
L002_P07:0:EXTWALL_5_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 14.00 10.78 180.00 90.00 S
L002_P07:0:EXTWALL_6_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L002_P07:0:EXTWALL_7_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 10.50 8.09 180.00 90.00 S
L002_P07:0:EXTWALL_8_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 3.50 2.28 270.00 90.00 W
L002_P08:0:EXTWALL_3_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 5.25 4.04 180.00 90.00 S
L002_P08:0:EXTWALL_4_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L002_P08:0:EXTWALL_5_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 10.50 8.09 180.00 90.00 S
L002_P08:0:EXTWALL_6_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 3.50 2.28 270.00 90.00 W
L002_P08:0:EXTWALL_7_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 14.00 10.78 180.00 90.00 S
L002_P09:0:EXTWALL_3_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 14.00 10.78 180.00 90.00 S
L002_P09:0:EXTWALL_4_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L002_P09:0:EXTWALL_5_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 15.75 12.13 180.00 90.00 S
L002_P10:0:EXTWALL_3_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 3.50 2.28 270.00 90.00 W
L002_P10:0:EXTWALL_4_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 14.00 10.78 180.00 90.00 S
L002_P10:0:EXTWALL_5_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 5.25 4.04 180.00 90.00 S
L002_P10:0:EXTWALL_6_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L002_P10:0:EXTWALL_7_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 10.50 8.09 180.00 90.00 S
L002_P11:0:EXTWALL_3_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 14.00 9.13 270.00 90.00 W
L002_P11:0:EXTWALL_4_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L002_P11:0:EXTWALL_5_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 10.50 6.85 270.00 90.00 W
L002_P11:0:EXTWALL_6_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 3.50 2.87 0.00 90.00 N
L002_P11:0:EXTWALL_7_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 5.25 3.43 270.00 90.00 W
L002_P12:0:EXTWALL_3_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L002_P12:0:EXTWALL_4_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 10.50 6.85 270.00 90.00 W
L002_P12:0:EXTWALL_5_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 3.50 2.87 0.00 90.00 N
L002_P12:0:EXTWALL_6_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 7.00 4.57 270.00 90.00 W
L002_P12:0:EXTWALL_7_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 5.25 3.43 270.00 90.00 W
L002_P13:0:EXTWALL_3_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 24.50 17.00 270.00 90.00 W
L002_P13:0:EXTWALL_4_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 21.00 16.17 0.00 90.00 N
L002_P13:0:EXTWALL_5_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 21.00 17.22 0.00 90.00 N
L002_P13:0:EXTWALL_6_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 49.00 31.97 90.00 90.00 E
L002_P13:0:EXTWALL_7_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 21.00 16.17 0.00 90.00 N
L002_P13:0:EXTWALL_8_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 49.00 33.99 270.00 90.00 W
L002_P13:0:EXTWALL_9_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 14.00 10.78 0.00 90.00 N
L002_P13:0:EXTWALL_10_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 35.00 22.84 90.00 90.00 E
L002_P13:0:EXTWALL_11_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 7.00 5.74 180.00 90.00 S
L002_P13:0:EXTWALL_12_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 4.50 3.12 270.00 90.00 W
L002_P13:0:EXTWALL_13_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 42.00 34.44 180.00 90.00 S
L002_P14:0:EXTWALL_3_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 7.00 4.57 270.00 90.00 W
L002_P14:0:EXTWALL_4_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L002_P14:0:EXTWALL_5_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 14.00 9.13 270.00 90.00 W
L002_P15:0:EXTWALL_3_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L002_P15:0:EXTWALL_4_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 28.00 18.27 270.00 90.00 W
L002_P15:0:EXTWALL_5_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 17.50 14.35 0.00 90.00 N
L002_P15:0:EXTWALL_6_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 10.50 6.85 270.00 90.00 W
L002_P15:0:EXTWALL_7_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 7.00 5.74 0.00 90.00 N
L003_P01:0:EXTWALL_3_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 14.00 11.48 0.00 90.00 N
L003_P01:0:ROOF_2 UP ROOF METALDECK 0.60 0.176 0.180 44.00 44.00 180.00 0.00  
L003_P02:0:EXTWALL_3_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 14.00 9.71 90.00 90.00 E
L003_P02:0:EXTWALL_4_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 24.50 20.09 0.00 90.00 N
L003_P02:0:ROOF_2 UP ROOF METALDECK 0.60 0.176 0.180 84.00 84.00 180.00 0.00  
L003_P03:0:EXTWALL_3_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 3.50 2.87 0.00 90.00 N
L003_P03:0:EXTWALL_4_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 3.50 2.28 270.00 90.00 W
L003_P03:0:EXTWALL_5_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 10.50 8.61 0.00 90.00 N
L003_P03:0:EXTWALL_6_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L003_P03:0:EXTWALL_7_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 16.59 13.61 0.00 90.00 N
L003_P03:0:ROOF_2 UP ROOF METALDECK 0.60 0.176 0.180 72.93 72.93 0.00 0.00  
L003_P04:0:EXTWALL_3_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 21.00 16.17 180.00 90.00 S
L003_P04:0:EXTWALL_4_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 14.91 12.22 0.00 90.00 N
L003_P04:0:EXTWALL_5_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 3.50 2.28 270.00 90.00 W
L003_P04:0:EXTWALL_6_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 10.50 8.61 0.00 90.00 N
L003_P04:0:EXTWALL_7_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L003_P04:0:EXTWALL_8_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 14.00 11.48 0.00 90.00 N
L003_P04:0:EXTWALL_9_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 28.00 19.42 90.00 90.00 E
L003_P04:0:ROOF_2 UP ROOF METALDECK 0.60 0.176 0.180 93.07 93.07 90.00 0.00  
L003_P05:0:EXTWALL_3_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 10.50 7.28 90.00 90.00 E
L003_P05:0:EXTWALL_4_SOUTH_181 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L003_P05:0:EXTWALL_5_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 5.25 3.64 90.00 90.00 E
L003_P05:0:EXTWALL_6_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 16.50 11.45 90.00 90.00 E
L003_P05:0:EXTWALL_7_NORTH_360 NORTH WALL BRICK 0.60 0.250 0.260 3.50 2.87 0.00 90.00 N
L003_P05:0:ROOF_2 UP ROOF METALDECK 0.60 0.176 0.180 58.29 58.29 0.00 0.00  
L003_P06:0:EXTWALL_3_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 10.50 7.28 90.00 90.00 E
L003_P06:0:EXTWALL_4_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L003_P06:0:EXTWALL_5_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 10.50 7.28 90.00 90.00 E
L003_P06:0:EXTWALL_6_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 5.25 3.64 90.00 90.00 E
L003_P06:0:EXTWALL_7_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 3.50 2.87 0.00 90.00 N
L003_P06:0:ROOF_2 UP ROOF METALDECK 0.60 0.176 0.180 48.00 48.00 0.00 0.00  
L003_P07:0:EXTWALL_3_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 14.00 9.71 90.00 90.00 E
L003_P07:0:EXTWALL_4_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 14.00 10.78 180.00 90.00 S
L003_P07:0:EXTWALL_5_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L003_P07:0:EXTWALL_6_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 10.50 8.09 180.00 90.00 S
L003_P07:0:EXTWALL_7_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 3.50 2.28 270.00 90.00 W
L003_P07:0:EXTWALL_8_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 5.25 4.04 180.00 90.00 S
L003_P07:0:ROOF_2 UP ROOF METALDECK 0.60 0.176 0.180 54.00 54.00 180.00 0.00  
L003_P08:0:EXTWALL_3_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 5.25 4.04 180.00 90.00 S
L003_P08:0:EXTWALL_4_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L003_P08:0:EXTWALL_5_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 10.50 8.09 180.00 90.00 S
L003_P08:0:EXTWALL_6_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 3.50 2.28 270.00 90.00 W
L003_P08:0:EXTWALL_7_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 14.00 10.78 180.00 90.00 S
L003_P08:0:ROOF_2 UP ROOF METALDECK 0.60 0.176 0.180 54.00 54.00 180.00 0.00  
L003_P09:0:EXTWALL_3_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 14.00 10.78 180.00 90.00 S
L003_P09:0:EXTWALL_4_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L003_P09:0:EXTWALL_5_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 15.75 12.13 180.00 90.00 S
L003_P09:0:ROOF_2 UP ROOF METALDECK 0.60 0.176 0.180 55.50 55.50 180.00 0.00  
L003_P10:0:EXTWALL_3_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 3.50 2.28 270.00 90.00 W
L003_P10:0:EXTWALL_4_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 14.00 10.78 180.00 90.00 S
L003_P10:0:EXTWALL_5_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 5.25 4.04 180.00 90.00 S
L003_P10:0:EXTWALL_6_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 3.50 2.43 90.00 90.00 E
L003_P10:0:EXTWALL_7_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 10.50 8.09 180.00 90.00 S
L003_P10:0:ROOF_2 UP ROOF METALDECK 0.60 0.176 0.180 62.50 62.50 180.00 0.00  
L003_P11:0:EXTWALL_3_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 14.00 9.13 270.00 90.00 W
L003_P11:0:EXTWALL_4_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L003_P11:0:EXTWALL_5_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 10.50 6.85 270.00 90.00 W
L003_P11:0:EXTWALL_6_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 3.50 2.87 0.00 90.00 N
L003_P11:0:EXTWALL_7_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 5.25 3.43 270.00 90.00 W
L003_P11:0:ROOF_2 UP ROOF METALDECK 0.60 0.176 0.180 45.50 45.50 270.00 0.00  
L003_P12:0:EXTWALL_3_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 3.50 2.87 0.00 90.00 N
L003_P12:0:EXTWALL_4_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 7.00 4.57 270.00 90.00 W
L003_P12:0:EXTWALL_5_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 5.25 3.43 270.00 90.00 W
L003_P12:0:EXTWALL_6_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L003_P12:0:EXTWALL_7_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 10.50 6.85 270.00 90.00 W
L003_P12:0:ROOF_2 UP ROOF METALDECK 0.60 0.176 0.180 35.50 35.50 270.00 0.00  
L003_P13:0:EXTWALL_3_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 24.50 17.00 270.00 90.00 W
L003_P13:0:EXTWALL_4_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 21.00 16.17 0.00 90.00 N
L003_P13:0:EXTWALL_5_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 21.00 17.22 0.00 90.00 N
L003_P13:0:EXTWALL_6_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 49.00 31.97 90.00 90.00 E
L003_P13:0:EXTWALL_7_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 21.00 16.17 0.00 90.00 N
L003_P13:0:EXTWALL_8_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 49.00 33.99 270.00 90.00 W
L003_P13:0:EXTWALL_9_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 14.00 10.78 0.00 90.00 N
L003_P13:0:EXTWALL_10_EAST_090 EAST WALL BRICK 0.60 0.250 0.260 35.00 22.84 90.00 90.00 E
L003_P13:0:EXTWALL_11_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 7.00 5.74 180.00 90.00 S
L003_P13:0:EXTWALL_12_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 4.50 3.12 270.00 90.00 W
L003_P13:0:EXTWALL_13_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 42.00 34.44 0.00 90.00 N
L003_P13:0:ROOF_2 UP ROOF METALDECK 0.60 0.176 0.180 515.71 515.71 180.00 0.00  
L003_P14:0:EXTWALL_3_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 7.00 4.57 270.00 90.00 W
L003_P14:0:EXTWALL_4_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L003_P14:0:EXTWALL_5_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 14.00 9.13 270.00 90.00 W
L003_P14:0:ROOF_2 UP ROOF METALDECK 0.60 0.176 0.180 34.00 34.00 180.00 0.00  
L003_P15:0:EXTWALL_3_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 7.00 5.74 0.00 90.00 N
L003_P15:0:EXTWALL_4_SOUTH_180 SOUTH WALL BRICK 0.60 0.250 0.260 3.50 2.70 180.00 90.00 S
L003_P15:0:EXTWALL_5_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 28.00 18.27 270.00 90.00 W
L003_P15:0:EXTWALL_6_NORTH_000 NORTH WALL BRICK 0.60 0.250 0.260 17.50 14.35 0.00 90.00 N
L003_P15:0:EXTWALL_7_WEST_270 WEST WALL BRICK 0.60 0.250 0.260 10.50 6.85 270.00 90.00 W
L003_P15:0:ROOF_2 UP ROOF METALDECK 0.60 0.176 0.180 62.00 62.00 270.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
L001_P01:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_NORTH_000 NORTH WALL GLAZING 2.52 0.00 0.00 2.52 2.52 1.600 0.599 0.100     No L001_P01:0:EXTWALL_3_NORTH_000 0.00 90.00 N
L001_P02:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_EAST_090 EAST WALL GLAZING 4.29 0.00 0.00 4.29 4.29 1.600 0.599 0.100     No L001_P02:0:EXTWALL_3_EAST_090 90.00 90.00 E
L001_P02:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_NORTH_000 NORTH WALL GLAZING 4.41 0.00 0.00 4.41 4.41 1.600 0.599 0.100     No L001_P02:0:EXTWALL_4_NORTH_000 0.00 90.00 N
L001_P03:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_NORTH_000 NORTH WALL GLAZING 0.63 0.00 0.00 0.63 0.63 1.600 0.599 0.100     No L001_P03:0:EXTWALL_3_NORTH_000 0.00 90.00 N
L001_P03:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_WEST_270 WEST WALL GLAZING 1.22 0.00 0.00 1.22 1.22 1.600 0.599 0.100     No L001_P03:0:EXTWALL_4_WEST_270 270.00 90.00 W
L001_P03:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_NORTH_000 NORTH WALL GLAZING 1.89 0.00 0.00 1.89 1.89 1.600 0.599 0.100     No L001_P03:0:EXTWALL_5_NORTH_000 0.00 90.00 N
L001_P03:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L001_P03:0:EXTWALL_6_EAST_090 90.00 90.00 E
L001_P03:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_NORTH_000 NORTH WALL GLAZING 2.99 0.00 0.00 2.99 2.99 1.600 0.599 0.100     No L001_P03:0:EXTWALL_7_NORTH_000 0.00 90.00 N
L001_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_NORTH_000 NORTH WALL GLAZING 2.52 0.00 0.00 2.52 2.52 1.600 0.599 0.100     No L001_P04:0:EXTWALL_3_NORTH_000 0.00 90.00 N
L001_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_EAST_090 EAST WALL GLAZING 8.58 0.00 0.00 8.58 8.58 1.600 0.599 0.100     No L001_P04:0:EXTWALL_4_EAST_090 90.00 90.00 E
L001_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_SOUTH_179 SOUTH WALL GLAZING 4.83 0.00 0.00 4.83 4.83 1.600 0.599 0.100     No L001_P04:0:EXTWALL_5_SOUTH_179 180.00 90.00 S
L001_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_NORTH_000 NORTH WALL GLAZING 2.68 0.00 0.00 2.68 2.68 1.600 0.599 0.100     No L001_P04:0:EXTWALL_6_NORTH_000 0.00 90.00 N
L001_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_WEST_270 WEST WALL GLAZING 1.22 0.00 0.00 1.22 1.22 1.600 0.599 0.100     No L001_P04:0:EXTWALL_7_WEST_270 270.00 90.00 W
L001_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_8_NORTH_000 NORTH WALL GLAZING 1.89 0.00 0.00 1.89 1.89 1.600 0.599 0.100     No L001_P04:0:EXTWALL_8_NORTH_000 0.00 90.00 N
L001_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_9_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L001_P04:0:EXTWALL_9_EAST_090 90.00 90.00 E
L001_P05:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_EAST_090 EAST WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L001_P05:0:EXTWALL_3_EAST_090 90.00 90.00 E
L001_P05:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_181 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L001_P05:0:EXTWALL_4_SOUTH_181 180.00 90.00 S
L001_P05:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_EAST_090 EAST WALL GLAZING 1.61 0.00 0.00 1.61 1.61 1.600 0.599 0.100     No L001_P05:0:EXTWALL_5_EAST_090 90.00 90.00 E
L001_P05:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_EAST_090 EAST WALL GLAZING 5.06 0.00 0.00 5.06 5.06 1.600 0.599 0.100     No L001_P05:0:EXTWALL_6_EAST_090 90.00 90.00 E
L001_P05:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_NORTH_359 NORTH WALL GLAZING 0.63 0.00 0.00 0.63 0.63 1.600 0.599 0.100     No L001_P05:0:EXTWALL_7_NORTH_359 0.00 90.00 N
L001_P06:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_EAST_090 EAST WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L001_P06:0:EXTWALL_3_EAST_090 90.00 90.00 E
L001_P06:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_180 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L001_P06:0:EXTWALL_4_SOUTH_180 180.00 90.00 S
L001_P06:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_EAST_090 EAST WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L001_P06:0:EXTWALL_5_EAST_090 90.00 90.00 E
L001_P06:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_EAST_090 EAST WALL GLAZING 1.61 0.00 0.00 1.61 1.61 1.600 0.599 0.100     No L001_P06:0:EXTWALL_6_EAST_090 90.00 90.00 E
L001_P06:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_NORTH_000 NORTH WALL GLAZING 0.63 0.00 0.00 0.63 0.63 1.600 0.599 0.100     No L001_P06:0:EXTWALL_7_NORTH_000 0.00 90.00 N
L001_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_EAST_090 EAST WALL GLAZING 4.29 0.00 0.00 4.29 4.29 1.600 0.599 0.100     No L001_P07:0:EXTWALL_3_EAST_090 90.00 90.00 E
L001_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_180 SOUTH WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L001_P07:0:EXTWALL_4_SOUTH_180 180.00 90.00 S
L001_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L001_P07:0:EXTWALL_5_EAST_090 90.00 90.00 E
L001_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_SOUTH_180 SOUTH WALL GLAZING 2.41 0.00 0.00 2.41 2.41 1.600 0.599 0.100     No L001_P07:0:EXTWALL_6_SOUTH_180 180.00 90.00 S
L001_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_WEST_270 WEST WALL GLAZING 1.22 0.00 0.00 1.22 1.22 1.600 0.599 0.100     No L001_P07:0:EXTWALL_7_WEST_270 270.00 90.00 W
L001_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_8_SOUTH_180 SOUTH WALL GLAZING 1.21 0.00 0.00 1.21 1.21 1.600 0.599 0.100     No L001_P07:0:EXTWALL_8_SOUTH_180 180.00 90.00 S
L001_P08:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_WEST_270 WEST WALL GLAZING 1.22 0.00 0.00 1.22 1.22 1.600 0.599 0.100     No L001_P08:0:EXTWALL_3_WEST_270 270.00 90.00 W
L001_P08:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_180 SOUTH WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L001_P08:0:EXTWALL_4_SOUTH_180 180.00 90.00 S
L001_P08:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_SOUTH_180 SOUTH WALL GLAZING 1.21 0.00 0.00 1.21 1.21 1.600 0.599 0.100     No L001_P08:0:EXTWALL_5_SOUTH_180 180.00 90.00 S
L001_P08:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L001_P08:0:EXTWALL_6_EAST_090 90.00 90.00 E
L001_P08:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_SOUTH_180 SOUTH WALL GLAZING 2.41 0.00 0.00 2.41 2.41 1.600 0.599 0.100     No L001_P08:0:EXTWALL_7_SOUTH_180 180.00 90.00 S
L001_P09:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_SOUTH_180 SOUTH WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L001_P09:0:EXTWALL_3_SOUTH_180 180.00 90.00 S
L001_P09:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L001_P09:0:EXTWALL_4_EAST_090 90.00 90.00 E
L001_P09:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_SOUTH_180 SOUTH WALL GLAZING 3.62 0.00 0.00 3.62 3.62 1.600 0.599 0.100     No L001_P09:0:EXTWALL_5_SOUTH_180 180.00 90.00 S
L001_P10:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_SOUTH_180 SOUTH WALL GLAZING 1.21 0.00 0.00 1.21 1.21 1.600 0.599 0.100     No L001_P10:0:EXTWALL_3_SOUTH_180 180.00 90.00 S
L001_P10:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L001_P10:0:EXTWALL_4_EAST_090 90.00 90.00 E
L001_P10:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_SOUTH_180 SOUTH WALL GLAZING 2.41 0.00 0.00 2.41 2.41 1.600 0.599 0.100     No L001_P10:0:EXTWALL_5_SOUTH_180 180.00 90.00 S
L001_P10:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_WEST_270 WEST WALL GLAZING 1.22 0.00 0.00 1.22 1.22 1.600 0.599 0.100     No L001_P10:0:EXTWALL_6_WEST_270 270.00 90.00 W
L001_P10:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_SOUTH_180 SOUTH WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L001_P10:0:EXTWALL_7_SOUTH_180 180.00 90.00 S
L001_P11:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_WEST_270 WEST WALL GLAZING 1.82 0.00 0.00 1.82 1.82 1.600 0.599 0.100     No L001_P11:0:EXTWALL_3_WEST_270 270.00 90.00 W
L001_P11:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_WEST_270 WEST WALL GLAZING 4.87 0.00 0.00 4.87 4.87 1.600 0.599 0.100     No L001_P11:0:EXTWALL_4_WEST_270 270.00 90.00 W
L001_P11:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_SOUTH_180 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L001_P11:0:EXTWALL_5_SOUTH_180 180.00 90.00 S
L001_P11:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_WEST_270 WEST WALL GLAZING 3.65 0.00 0.00 3.65 3.65 1.600 0.599 0.100     No L001_P11:0:EXTWALL_6_WEST_270 270.00 90.00 W
L001_P11:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_NORTH_000 NORTH WALL GLAZING 0.63 0.00 0.00 0.63 0.63 1.600 0.599 0.100     No L001_P11:0:EXTWALL_7_NORTH_000 0.00 90.00 N
L001_P12:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_WEST_270 WEST WALL GLAZING 1.82 0.00 0.00 1.82 1.82 1.600 0.599 0.100     No L001_P12:0:EXTWALL_3_WEST_270 270.00 90.00 W
L001_P12:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_180 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L001_P12:0:EXTWALL_4_SOUTH_180 180.00 90.00 S
L001_P12:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_WEST_270 WEST WALL GLAZING 3.65 0.00 0.00 3.65 3.65 1.600 0.599 0.100     No L001_P12:0:EXTWALL_5_WEST_270 270.00 90.00 W
L001_P12:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_NORTH_000 NORTH WALL GLAZING 0.63 0.00 0.00 0.63 0.63 1.600 0.599 0.100     No L001_P12:0:EXTWALL_6_NORTH_000 0.00 90.00 N
L001_P12:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_WEST_270 WEST WALL GLAZING 2.43 0.00 0.00 2.43 2.43 1.600 0.599 0.100     No L001_P12:0:EXTWALL_7_WEST_270 270.00 90.00 W
L001_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_WEST_270 WEST WALL GLAZING 2.43 0.00 0.00 2.43 2.43 1.600 0.599 0.100     No L001_P13:0:EXTWALL_3_WEST_270 270.00 90.00 W
L001_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_180 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L001_P13:0:EXTWALL_4_SOUTH_180 180.00 90.00 S
L001_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_WEST_270 WEST WALL GLAZING 4.87 0.00 0.00 4.87 4.87 1.600 0.599 0.100     No L001_P13:0:EXTWALL_5_WEST_270 270.00 90.00 W
L001_P14:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_WEST_270 WEST WALL GLAZING 7.50 0.00 0.00 7.50 7.50 1.600 0.599 0.100     No L001_P14:0:EXTWALL_3_WEST_270 270.00 90.00 W
L001_P14:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_NORTH_000 NORTH WALL GLAZING 4.83 0.00 0.00 4.83 4.83 1.600 0.599 0.100     No L001_P14:0:EXTWALL_4_NORTH_000 0.00 90.00 N
L001_P14:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_NORTH_000 NORTH WALL GLAZING 3.78 0.00 0.00 3.78 3.78 1.600 0.599 0.100     No L001_P14:0:EXTWALL_5_NORTH_000 0.00 90.00 N
L001_P14:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_EAST_090 EAST WALL GLAZING 17.03 0.00 0.00 17.03 17.03 1.600 0.599 0.100     No L001_P14:0:EXTWALL_6_EAST_090 90.00 90.00 E
L001_P14:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_NORTH_000 NORTH WALL GLAZING 4.83 0.00 0.00 4.83 4.83 1.600 0.599 0.100     No L001_P14:0:EXTWALL_7_NORTH_000 0.00 90.00 N
L001_P14:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_8_WEST_270 WEST WALL GLAZING 15.01 0.00 0.00 15.01 15.01 1.600 0.599 0.100     No L001_P14:0:EXTWALL_8_WEST_270 270.00 90.00 W
L001_P14:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_9_NORTH_000 NORTH WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L001_P14:0:EXTWALL_9_NORTH_000 0.00 90.00 N
L001_P14:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_10_EAST_090 EAST WALL GLAZING 12.16 0.00 0.00 12.16 12.16 1.600 0.599 0.100     No L001_P14:0:EXTWALL_10_EAST_090 90.00 90.00 E
L001_P14:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_11_SOUTH_180 SOUTH WALL GLAZING 1.26 0.00 0.00 1.26 1.26 1.600 0.599 0.100     No L001_P14:0:EXTWALL_11_SOUTH_180 180.00 90.00 S
L001_P14:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_12_WEST_270 WEST WALL GLAZING 1.38 0.00 0.00 1.38 1.38 1.600 0.599 0.100     No L001_P14:0:EXTWALL_12_WEST_270 270.00 90.00 W
L001_P14:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_13_SOUTH_180 SOUTH WALL GLAZING 7.56 0.00 0.00 7.56 7.56 1.600 0.599 0.100     No L001_P14:0:EXTWALL_13_SOUTH_180 180.00 90.00 S
L001_P15:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_NORTH_000 NORTH WALL GLAZING 1.26 0.00 0.00 1.26 1.26 1.600 0.599 0.100     No L001_P15:0:EXTWALL_3_NORTH_000 0.00 90.00 N
L001_P15:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_180 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L001_P15:0:EXTWALL_4_SOUTH_180 180.00 90.00 S
L001_P15:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_WEST_270 WEST WALL GLAZING 9.73 0.00 0.00 9.73 9.73 1.600 0.599 0.100     No L001_P15:0:EXTWALL_5_WEST_270 270.00 90.00 W
L001_P15:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_NORTH_000 NORTH WALL GLAZING 3.15 0.00 0.00 3.15 3.15 1.600 0.599 0.100     No L001_P15:0:EXTWALL_6_NORTH_000 0.00 90.00 N
L001_P15:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_WEST_270 WEST WALL GLAZING 3.65 0.00 0.00 3.65 3.65 1.600 0.599 0.100     No L001_P15:0:EXTWALL_7_WEST_270 270.00 90.00 W
L002_P01:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_NORTH_000 NORTH WALL GLAZING 2.52 0.00 0.00 2.52 2.52 1.600 0.599 0.100     No L002_P01:0:EXTWALL_3_NORTH_000 0.00 90.00 N
L002_P02:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_EAST_090 EAST WALL GLAZING 4.29 0.00 0.00 4.29 4.29 1.600 0.599 0.100     No L002_P02:0:EXTWALL_3_EAST_090 90.00 90.00 E
L002_P02:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_NORTH_000 NORTH WALL GLAZING 4.41 0.00 0.00 4.41 4.41 1.600 0.599 0.100     No L002_P02:0:EXTWALL_4_NORTH_000 0.00 90.00 N
L002_P03:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_WEST_270 WEST WALL GLAZING 1.22 0.00 0.00 1.22 1.22 1.600 0.599 0.100     No L002_P03:0:EXTWALL_3_WEST_270 270.00 90.00 W
L002_P03:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_NORTH_000 NORTH WALL GLAZING 1.89 0.00 0.00 1.89 1.89 1.600 0.599 0.100     No L002_P03:0:EXTWALL_4_NORTH_000 0.00 90.00 N
L002_P03:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L002_P03:0:EXTWALL_5_EAST_090 90.00 90.00 E
L002_P03:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_NORTH_000 NORTH WALL GLAZING 2.99 0.00 0.00 2.99 2.99 1.600 0.599 0.100     No L002_P03:0:EXTWALL_6_NORTH_000 0.00 90.00 N
L002_P03:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_NORTH_000 NORTH WALL GLAZING 0.63 0.00 0.00 0.63 0.63 1.600 0.599 0.100     No L002_P03:0:EXTWALL_7_NORTH_000 0.00 90.00 N
L002_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_WEST_270 WEST WALL GLAZING 1.22 0.00 0.00 1.22 1.22 1.600 0.599 0.100     No L002_P04:0:EXTWALL_3_WEST_270 270.00 90.00 W
L002_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_NORTH_000 NORTH WALL GLAZING 1.89 0.00 0.00 1.89 1.89 1.600 0.599 0.100     No L002_P04:0:EXTWALL_4_NORTH_000 0.00 90.00 N
L002_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L002_P04:0:EXTWALL_5_EAST_090 90.00 90.00 E
L002_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_NORTH_000 NORTH WALL GLAZING 2.52 0.00 0.00 2.52 2.52 1.600 0.599 0.100     No L002_P04:0:EXTWALL_6_NORTH_000 0.00 90.00 N
L002_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_EAST_090 EAST WALL GLAZING 8.58 0.00 0.00 8.58 8.58 1.600 0.599 0.100     No L002_P04:0:EXTWALL_7_EAST_090 90.00 90.00 E
L002_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_8_SOUTH_180 SOUTH WALL GLAZING 4.83 0.00 0.00 4.83 4.83 1.600 0.599 0.100     No L002_P04:0:EXTWALL_8_SOUTH_180 180.00 90.00 S
L002_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_9_NORTH_000 NORTH WALL GLAZING 2.68 0.00 0.00 2.68 2.68 1.600 0.599 0.100     No L002_P04:0:EXTWALL_9_NORTH_000 0.00 90.00 N
L002_P05:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_EAST_090 EAST WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L002_P05:0:EXTWALL_3_EAST_090 90.00 90.00 E
L002_P05:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_181 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L002_P05:0:EXTWALL_4_SOUTH_181 180.00 90.00 S
L002_P05:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_EAST_090 EAST WALL GLAZING 1.61 0.00 0.00 1.61 1.61 1.600 0.599 0.100     No L002_P05:0:EXTWALL_5_EAST_090 90.00 90.00 E
L002_P05:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_EAST_090 EAST WALL GLAZING 5.06 0.00 0.00 5.06 5.06 1.600 0.599 0.100     No L002_P05:0:EXTWALL_6_EAST_090 90.00 90.00 E
L002_P05:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_NORTH_359 NORTH WALL GLAZING 0.63 0.00 0.00 0.63 0.63 1.600 0.599 0.100     No L002_P05:0:EXTWALL_7_NORTH_359 0.00 90.00 N
L002_P06:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_EAST_090 EAST WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L002_P06:0:EXTWALL_3_EAST_090 90.00 90.00 E
L002_P06:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_180 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L002_P06:0:EXTWALL_4_SOUTH_180 180.00 90.00 S
L002_P06:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_EAST_090 EAST WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L002_P06:0:EXTWALL_5_EAST_090 90.00 90.00 E
L002_P06:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_EAST_090 EAST WALL GLAZING 1.61 0.00 0.00 1.61 1.61 1.600 0.599 0.100     No L002_P06:0:EXTWALL_6_EAST_090 90.00 90.00 E
L002_P06:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_NORTH_000 NORTH WALL GLAZING 0.63 0.00 0.00 0.63 0.63 1.600 0.599 0.100     No L002_P06:0:EXTWALL_7_NORTH_000 0.00 90.00 N
L002_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_SOUTH_180 SOUTH WALL GLAZING 1.21 0.00 0.00 1.21 1.21 1.600 0.599 0.100     No L002_P07:0:EXTWALL_3_SOUTH_180 180.00 90.00 S
L002_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_EAST_090 EAST WALL GLAZING 4.29 0.00 0.00 4.29 4.29 1.600 0.599 0.100     No L002_P07:0:EXTWALL_4_EAST_090 90.00 90.00 E
L002_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_SOUTH_180 SOUTH WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L002_P07:0:EXTWALL_5_SOUTH_180 180.00 90.00 S
L002_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L002_P07:0:EXTWALL_6_EAST_090 90.00 90.00 E
L002_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_SOUTH_180 SOUTH WALL GLAZING 2.41 0.00 0.00 2.41 2.41 1.600 0.599 0.100     No L002_P07:0:EXTWALL_7_SOUTH_180 180.00 90.00 S
L002_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_8_WEST_270 WEST WALL GLAZING 1.22 0.00 0.00 1.22 1.22 1.600 0.599 0.100     No L002_P07:0:EXTWALL_8_WEST_270 270.00 90.00 W
L002_P08:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_SOUTH_180 SOUTH WALL GLAZING 1.21 0.00 0.00 1.21 1.21 1.600 0.599 0.100     No L002_P08:0:EXTWALL_3_SOUTH_180 180.00 90.00 S
L002_P08:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L002_P08:0:EXTWALL_4_EAST_090 90.00 90.00 E
L002_P08:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_SOUTH_180 SOUTH WALL GLAZING 2.41 0.00 0.00 2.41 2.41 1.600 0.599 0.100     No L002_P08:0:EXTWALL_5_SOUTH_180 180.00 90.00 S
L002_P08:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_WEST_270 WEST WALL GLAZING 1.22 0.00 0.00 1.22 1.22 1.600 0.599 0.100     No L002_P08:0:EXTWALL_6_WEST_270 270.00 90.00 W
L002_P08:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_SOUTH_180 SOUTH WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L002_P08:0:EXTWALL_7_SOUTH_180 180.00 90.00 S
L002_P09:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_SOUTH_180 SOUTH WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L002_P09:0:EXTWALL_3_SOUTH_180 180.00 90.00 S
L002_P09:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L002_P09:0:EXTWALL_4_EAST_090 90.00 90.00 E
L002_P09:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_SOUTH_180 SOUTH WALL GLAZING 3.62 0.00 0.00 3.62 3.62 1.600 0.599 0.100     No L002_P09:0:EXTWALL_5_SOUTH_180 180.00 90.00 S
L002_P10:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_WEST_270 WEST WALL GLAZING 1.22 0.00 0.00 1.22 1.22 1.600 0.599 0.100     No L002_P10:0:EXTWALL_3_WEST_270 270.00 90.00 W
L002_P10:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_180 SOUTH WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L002_P10:0:EXTWALL_4_SOUTH_180 180.00 90.00 S
L002_P10:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_SOUTH_180 SOUTH WALL GLAZING 1.21 0.00 0.00 1.21 1.21 1.600 0.599 0.100     No L002_P10:0:EXTWALL_5_SOUTH_180 180.00 90.00 S
L002_P10:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L002_P10:0:EXTWALL_6_EAST_090 90.00 90.00 E
L002_P10:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_SOUTH_180 SOUTH WALL GLAZING 2.41 0.00 0.00 2.41 2.41 1.600 0.599 0.100     No L002_P10:0:EXTWALL_7_SOUTH_180 180.00 90.00 S
L002_P11:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_WEST_270 WEST WALL GLAZING 4.87 0.00 0.00 4.87 4.87 1.600 0.599 0.100     No L002_P11:0:EXTWALL_3_WEST_270 270.00 90.00 W
L002_P11:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_180 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L002_P11:0:EXTWALL_4_SOUTH_180 180.00 90.00 S
L002_P11:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_WEST_270 WEST WALL GLAZING 3.65 0.00 0.00 3.65 3.65 1.600 0.599 0.100     No L002_P11:0:EXTWALL_5_WEST_270 270.00 90.00 W
L002_P11:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_NORTH_000 NORTH WALL GLAZING 0.63 0.00 0.00 0.63 0.63 1.600 0.599 0.100     No L002_P11:0:EXTWALL_6_NORTH_000 0.00 90.00 N
L002_P11:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_WEST_270 WEST WALL GLAZING 1.82 0.00 0.00 1.82 1.82 1.600 0.599 0.100     No L002_P11:0:EXTWALL_7_WEST_270 270.00 90.00 W
L002_P12:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_SOUTH_180 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L002_P12:0:EXTWALL_3_SOUTH_180 180.00 90.00 S
L002_P12:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_WEST_270 WEST WALL GLAZING 3.65 0.00 0.00 3.65 3.65 1.600 0.599 0.100     No L002_P12:0:EXTWALL_4_WEST_270 270.00 90.00 W
L002_P12:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_NORTH_000 NORTH WALL GLAZING 0.63 0.00 0.00 0.63 0.63 1.600 0.599 0.100     No L002_P12:0:EXTWALL_5_NORTH_000 0.00 90.00 N
L002_P12:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_WEST_270 WEST WALL GLAZING 2.43 0.00 0.00 2.43 2.43 1.600 0.599 0.100     No L002_P12:0:EXTWALL_6_WEST_270 270.00 90.00 W
L002_P12:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_WEST_270 WEST WALL GLAZING 1.82 0.00 0.00 1.82 1.82 1.600 0.599 0.100     No L002_P12:0:EXTWALL_7_WEST_270 270.00 90.00 W
L002_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_WEST_270 WEST WALL GLAZING 7.50 0.00 0.00 7.50 7.50 1.600 0.599 0.100     No L002_P13:0:EXTWALL_3_WEST_270 270.00 90.00 W
L002_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_NORTH_000 NORTH WALL GLAZING 4.83 0.00 0.00 4.83 4.83 1.600 0.599 0.100     No L002_P13:0:EXTWALL_4_NORTH_000 0.00 90.00 N
L002_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_NORTH_000 NORTH WALL GLAZING 3.78 0.00 0.00 3.78 3.78 1.600 0.599 0.100     No L002_P13:0:EXTWALL_5_NORTH_000 0.00 90.00 N
L002_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_EAST_090 EAST WALL GLAZING 17.03 0.00 0.00 17.03 17.03 1.600 0.599 0.100     No L002_P13:0:EXTWALL_6_EAST_090 90.00 90.00 E
L002_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_NORTH_000 NORTH WALL GLAZING 4.83 0.00 0.00 4.83 4.83 1.600 0.599 0.100     No L002_P13:0:EXTWALL_7_NORTH_000 0.00 90.00 N
L002_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_8_WEST_270 WEST WALL GLAZING 15.01 0.00 0.00 15.01 15.01 1.600 0.599 0.100     No L002_P13:0:EXTWALL_8_WEST_270 270.00 90.00 W
L002_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_9_NORTH_000 NORTH WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L002_P13:0:EXTWALL_9_NORTH_000 0.00 90.00 N
L002_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_10_EAST_090 EAST WALL GLAZING 12.16 0.00 0.00 12.16 12.16 1.600 0.599 0.100     No L002_P13:0:EXTWALL_10_EAST_090 90.00 90.00 E
L002_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_11_SOUTH_180 SOUTH WALL GLAZING 1.26 0.00 0.00 1.26 1.26 1.600 0.599 0.100     No L002_P13:0:EXTWALL_11_SOUTH_180 180.00 90.00 S
L002_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_12_WEST_270 WEST WALL GLAZING 1.38 0.00 0.00 1.38 1.38 1.600 0.599 0.100     No L002_P13:0:EXTWALL_12_WEST_270 270.00 90.00 W
L002_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_13_SOUTH_180 SOUTH WALL GLAZING 7.56 0.00 0.00 7.56 7.56 1.600 0.599 0.100     No L002_P13:0:EXTWALL_13_SOUTH_180 180.00 90.00 S
L002_P14:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_WEST_270 WEST WALL GLAZING 2.43 0.00 0.00 2.43 2.43 1.600 0.599 0.100     No L002_P14:0:EXTWALL_3_WEST_270 270.00 90.00 W
L002_P14:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_180 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L002_P14:0:EXTWALL_4_SOUTH_180 180.00 90.00 S
L002_P14:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_WEST_270 WEST WALL GLAZING 4.87 0.00 0.00 4.87 4.87 1.600 0.599 0.100     No L002_P14:0:EXTWALL_5_WEST_270 270.00 90.00 W
L002_P15:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_SOUTH_180 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L002_P15:0:EXTWALL_3_SOUTH_180 180.00 90.00 S
L002_P15:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_WEST_270 WEST WALL GLAZING 9.73 0.00 0.00 9.73 9.73 1.600 0.599 0.100     No L002_P15:0:EXTWALL_4_WEST_270 270.00 90.00 W
L002_P15:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_NORTH_000 NORTH WALL GLAZING 3.15 0.00 0.00 3.15 3.15 1.600 0.599 0.100     No L002_P15:0:EXTWALL_5_NORTH_000 0.00 90.00 N
L002_P15:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_WEST_270 WEST WALL GLAZING 3.65 0.00 0.00 3.65 3.65 1.600 0.599 0.100     No L002_P15:0:EXTWALL_6_WEST_270 270.00 90.00 W
L002_P15:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_NORTH_000 NORTH WALL GLAZING 1.26 0.00 0.00 1.26 1.26 1.600 0.599 0.100     No L002_P15:0:EXTWALL_7_NORTH_000 0.00 90.00 N
L003_P01:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_NORTH_000 NORTH WALL GLAZING 2.52 0.00 0.00 2.52 2.52 1.600 0.599 0.100     No L003_P01:0:EXTWALL_3_NORTH_000 0.00 90.00 N
L003_P02:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_EAST_090 EAST WALL GLAZING 4.29 0.00 0.00 4.29 4.29 1.600 0.599 0.100     No L003_P02:0:EXTWALL_3_EAST_090 90.00 90.00 E
L003_P02:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_NORTH_000 NORTH WALL GLAZING 4.41 0.00 0.00 4.41 4.41 1.600 0.599 0.100     No L003_P02:0:EXTWALL_4_NORTH_000 0.00 90.00 N
L003_P03:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_NORTH_000 NORTH WALL GLAZING 0.63 0.00 0.00 0.63 0.63 1.600 0.599 0.100     No L003_P03:0:EXTWALL_3_NORTH_000 0.00 90.00 N
L003_P03:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_WEST_270 WEST WALL GLAZING 1.22 0.00 0.00 1.22 1.22 1.600 0.599 0.100     No L003_P03:0:EXTWALL_4_WEST_270 270.00 90.00 W
L003_P03:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_NORTH_000 NORTH WALL GLAZING 1.89 0.00 0.00 1.89 1.89 1.600 0.599 0.100     No L003_P03:0:EXTWALL_5_NORTH_000 0.00 90.00 N
L003_P03:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L003_P03:0:EXTWALL_6_EAST_090 90.00 90.00 E
L003_P03:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_NORTH_000 NORTH WALL GLAZING 2.99 0.00 0.00 2.99 2.99 1.600 0.599 0.100     No L003_P03:0:EXTWALL_7_NORTH_000 0.00 90.00 N
L003_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_SOUTH_180 SOUTH WALL GLAZING 4.83 0.00 0.00 4.83 4.83 1.600 0.599 0.100     No L003_P04:0:EXTWALL_3_SOUTH_180 180.00 90.00 S
L003_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_NORTH_000 NORTH WALL GLAZING 2.68 0.00 0.00 2.68 2.68 1.600 0.599 0.100     No L003_P04:0:EXTWALL_4_NORTH_000 0.00 90.00 N
L003_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_WEST_270 WEST WALL GLAZING 1.22 0.00 0.00 1.22 1.22 1.600 0.599 0.100     No L003_P04:0:EXTWALL_5_WEST_270 270.00 90.00 W
L003_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_NORTH_000 NORTH WALL GLAZING 1.89 0.00 0.00 1.89 1.89 1.600 0.599 0.100     No L003_P04:0:EXTWALL_6_NORTH_000 0.00 90.00 N
L003_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L003_P04:0:EXTWALL_7_EAST_090 90.00 90.00 E
L003_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_8_NORTH_000 NORTH WALL GLAZING 2.52 0.00 0.00 2.52 2.52 1.600 0.599 0.100     No L003_P04:0:EXTWALL_8_NORTH_000 0.00 90.00 N
L003_P04:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_9_EAST_090 EAST WALL GLAZING 8.58 0.00 0.00 8.58 8.58 1.600 0.599 0.100     No L003_P04:0:EXTWALL_9_EAST_090 90.00 90.00 E
L003_P05:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_EAST_090 EAST WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L003_P05:0:EXTWALL_3_EAST_090 90.00 90.00 E
L003_P05:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_181 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L003_P05:0:EXTWALL_4_SOUTH_181 180.00 90.00 S
L003_P05:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_EAST_090 EAST WALL GLAZING 1.61 0.00 0.00 1.61 1.61 1.600 0.599 0.100     No L003_P05:0:EXTWALL_5_EAST_090 90.00 90.00 E
L003_P05:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_EAST_090 EAST WALL GLAZING 5.06 0.00 0.00 5.06 5.06 1.600 0.599 0.100     No L003_P05:0:EXTWALL_6_EAST_090 90.00 90.00 E
L003_P05:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_NORTH_360 NORTH WALL GLAZING 0.63 0.00 0.00 0.63 0.63 1.600 0.599 0.100     No L003_P05:0:EXTWALL_7_NORTH_360 0.00 90.00 N
L003_P06:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_EAST_090 EAST WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L003_P06:0:EXTWALL_3_EAST_090 90.00 90.00 E
L003_P06:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_180 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L003_P06:0:EXTWALL_4_SOUTH_180 180.00 90.00 S
L003_P06:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_EAST_090 EAST WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L003_P06:0:EXTWALL_5_EAST_090 90.00 90.00 E
L003_P06:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_EAST_090 EAST WALL GLAZING 1.61 0.00 0.00 1.61 1.61 1.600 0.599 0.100     No L003_P06:0:EXTWALL_6_EAST_090 90.00 90.00 E
L003_P06:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_NORTH_000 NORTH WALL GLAZING 0.63 0.00 0.00 0.63 0.63 1.600 0.599 0.100     No L003_P06:0:EXTWALL_7_NORTH_000 0.00 90.00 N
L003_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_EAST_090 EAST WALL GLAZING 4.29 0.00 0.00 4.29 4.29 1.600 0.599 0.100     No L003_P07:0:EXTWALL_3_EAST_090 90.00 90.00 E
L003_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_180 SOUTH WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L003_P07:0:EXTWALL_4_SOUTH_180 180.00 90.00 S
L003_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L003_P07:0:EXTWALL_5_EAST_090 90.00 90.00 E
L003_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_SOUTH_180 SOUTH WALL GLAZING 2.41 0.00 0.00 2.41 2.41 1.600 0.599 0.100     No L003_P07:0:EXTWALL_6_SOUTH_180 180.00 90.00 S
L003_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_WEST_270 WEST WALL GLAZING 1.22 0.00 0.00 1.22 1.22 1.600 0.599 0.100     No L003_P07:0:EXTWALL_7_WEST_270 270.00 90.00 W
L003_P07:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_8_SOUTH_180 SOUTH WALL GLAZING 1.21 0.00 0.00 1.21 1.21 1.600 0.599 0.100     No L003_P07:0:EXTWALL_8_SOUTH_180 180.00 90.00 S
L003_P08:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_SOUTH_180 SOUTH WALL GLAZING 1.21 0.00 0.00 1.21 1.21 1.600 0.599 0.100     No L003_P08:0:EXTWALL_3_SOUTH_180 180.00 90.00 S
L003_P08:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L003_P08:0:EXTWALL_4_EAST_090 90.00 90.00 E
L003_P08:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_SOUTH_180 SOUTH WALL GLAZING 2.41 0.00 0.00 2.41 2.41 1.600 0.599 0.100     No L003_P08:0:EXTWALL_5_SOUTH_180 180.00 90.00 S
L003_P08:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_WEST_270 WEST WALL GLAZING 1.22 0.00 0.00 1.22 1.22 1.600 0.599 0.100     No L003_P08:0:EXTWALL_6_WEST_270 270.00 90.00 W
L003_P08:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_SOUTH_180 SOUTH WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L003_P08:0:EXTWALL_7_SOUTH_180 180.00 90.00 S
L003_P09:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_SOUTH_180 SOUTH WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L003_P09:0:EXTWALL_3_SOUTH_180 180.00 90.00 S
L003_P09:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L003_P09:0:EXTWALL_4_EAST_090 90.00 90.00 E
L003_P09:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_SOUTH_180 SOUTH WALL GLAZING 3.62 0.00 0.00 3.62 3.62 1.600 0.599 0.100     No L003_P09:0:EXTWALL_5_SOUTH_180 180.00 90.00 S
L003_P10:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_WEST_270 WEST WALL GLAZING 1.22 0.00 0.00 1.22 1.22 1.600 0.599 0.100     No L003_P10:0:EXTWALL_3_WEST_270 270.00 90.00 W
L003_P10:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_180 SOUTH WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L003_P10:0:EXTWALL_4_SOUTH_180 180.00 90.00 S
L003_P10:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_SOUTH_180 SOUTH WALL GLAZING 1.21 0.00 0.00 1.21 1.21 1.600 0.599 0.100     No L003_P10:0:EXTWALL_5_SOUTH_180 180.00 90.00 S
L003_P10:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_EAST_090 EAST WALL GLAZING 1.07 0.00 0.00 1.07 1.07 1.600 0.599 0.100     No L003_P10:0:EXTWALL_6_EAST_090 90.00 90.00 E
L003_P10:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_SOUTH_180 SOUTH WALL GLAZING 2.41 0.00 0.00 2.41 2.41 1.600 0.599 0.100     No L003_P10:0:EXTWALL_7_SOUTH_180 180.00 90.00 S
L003_P11:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_WEST_270 WEST WALL GLAZING 4.87 0.00 0.00 4.87 4.87 1.600 0.599 0.100     No L003_P11:0:EXTWALL_3_WEST_270 270.00 90.00 W
L003_P11:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_180 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L003_P11:0:EXTWALL_4_SOUTH_180 180.00 90.00 S
L003_P11:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_WEST_270 WEST WALL GLAZING 3.65 0.00 0.00 3.65 3.65 1.600 0.599 0.100     No L003_P11:0:EXTWALL_5_WEST_270 270.00 90.00 W
L003_P11:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_NORTH_000 NORTH WALL GLAZING 0.63 0.00 0.00 0.63 0.63 1.600 0.599 0.100     No L003_P11:0:EXTWALL_6_NORTH_000 0.00 90.00 N
L003_P11:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_WEST_270 WEST WALL GLAZING 1.82 0.00 0.00 1.82 1.82 1.600 0.599 0.100     No L003_P11:0:EXTWALL_7_WEST_270 270.00 90.00 W
L003_P12:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_NORTH_000 NORTH WALL GLAZING 0.63 0.00 0.00 0.63 0.63 1.600 0.599 0.100     No L003_P12:0:EXTWALL_3_NORTH_000 0.00 90.00 N
L003_P12:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_WEST_270 WEST WALL GLAZING 2.43 0.00 0.00 2.43 2.43 1.600 0.599 0.100     No L003_P12:0:EXTWALL_4_WEST_270 270.00 90.00 W
L003_P12:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_WEST_270 WEST WALL GLAZING 1.82 0.00 0.00 1.82 1.82 1.600 0.599 0.100     No L003_P12:0:EXTWALL_5_WEST_270 270.00 90.00 W
L003_P12:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_SOUTH_180 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L003_P12:0:EXTWALL_6_SOUTH_180 180.00 90.00 S
L003_P12:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_WEST_270 WEST WALL GLAZING 3.65 0.00 0.00 3.65 3.65 1.600 0.599 0.100     No L003_P12:0:EXTWALL_7_WEST_270 270.00 90.00 W
L003_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_WEST_270 WEST WALL GLAZING 7.50 0.00 0.00 7.50 7.50 1.600 0.599 0.100     No L003_P13:0:EXTWALL_3_WEST_270 270.00 90.00 W
L003_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_NORTH_000 NORTH WALL GLAZING 4.83 0.00 0.00 4.83 4.83 1.600 0.599 0.100     No L003_P13:0:EXTWALL_4_NORTH_000 0.00 90.00 N
L003_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_NORTH_000 NORTH WALL GLAZING 3.78 0.00 0.00 3.78 3.78 1.600 0.599 0.100     No L003_P13:0:EXTWALL_5_NORTH_000 0.00 90.00 N
L003_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_EAST_090 EAST WALL GLAZING 17.03 0.00 0.00 17.03 17.03 1.600 0.599 0.100     No L003_P13:0:EXTWALL_6_EAST_090 90.00 90.00 E
L003_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_NORTH_000 NORTH WALL GLAZING 4.83 0.00 0.00 4.83 4.83 1.600 0.599 0.100     No L003_P13:0:EXTWALL_7_NORTH_000 0.00 90.00 N
L003_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_8_WEST_270 WEST WALL GLAZING 15.01 0.00 0.00 15.01 15.01 1.600 0.599 0.100     No L003_P13:0:EXTWALL_8_WEST_270 270.00 90.00 W
L003_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_9_NORTH_000 NORTH WALL GLAZING 3.22 0.00 0.00 3.22 3.22 1.600 0.599 0.100     No L003_P13:0:EXTWALL_9_NORTH_000 0.00 90.00 N
L003_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_10_EAST_090 EAST WALL GLAZING 12.16 0.00 0.00 12.16 12.16 1.600 0.599 0.100     No L003_P13:0:EXTWALL_10_EAST_090 90.00 90.00 E
L003_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_11_SOUTH_180 SOUTH WALL GLAZING 1.26 0.00 0.00 1.26 1.26 1.600 0.599 0.100     No L003_P13:0:EXTWALL_11_SOUTH_180 180.00 90.00 S
L003_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_12_WEST_270 WEST WALL GLAZING 1.38 0.00 0.00 1.38 1.38 1.600 0.599 0.100     No L003_P13:0:EXTWALL_12_WEST_270 270.00 90.00 W
L003_P13:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_13_NORTH_000 NORTH WALL GLAZING 7.56 0.00 0.00 7.56 7.56 1.600 0.599 0.100     No L003_P13:0:EXTWALL_13_NORTH_000 0.00 90.00 N
L003_P14:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_WEST_270 WEST WALL GLAZING 2.43 0.00 0.00 2.43 2.43 1.600 0.599 0.100     No L003_P14:0:EXTWALL_3_WEST_270 270.00 90.00 W
L003_P14:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_180 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L003_P14:0:EXTWALL_4_SOUTH_180 180.00 90.00 S
L003_P14:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_WEST_270 WEST WALL GLAZING 4.87 0.00 0.00 4.87 4.87 1.600 0.599 0.100     No L003_P14:0:EXTWALL_5_WEST_270 270.00 90.00 W
L003_P15:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_3_NORTH_000 NORTH WALL GLAZING 1.26 0.00 0.00 1.26 1.26 1.600 0.599 0.100     No L003_P15:0:EXTWALL_3_NORTH_000 0.00 90.00 N
L003_P15:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_4_SOUTH_180 SOUTH WALL GLAZING 0.80 0.00 0.00 0.80 0.80 1.600 0.599 0.100     No L003_P15:0:EXTWALL_4_SOUTH_180 180.00 90.00 S
L003_P15:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_5_WEST_270 WEST WALL GLAZING 9.73 0.00 0.00 9.73 9.73 1.600 0.599 0.100     No L003_P15:0:EXTWALL_5_WEST_270 270.00 90.00 W
L003_P15:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_6_NORTH_000 NORTH WALL GLAZING 3.15 0.00 0.00 3.15 3.15 1.600 0.599 0.100     No L003_P15:0:EXTWALL_6_NORTH_000 0.00 90.00 N
L003_P15:0:EXTWINDOW_OPERABLE_1_1_ON_EXTWALL_7_WEST_270 WEST WALL GLAZING 3.65 0.00 0.00 3.65 3.65 1.600 0.599 0.100     No L003_P15:0:EXTWALL_7_WEST_270 270.00 90.00 W
Total or Average           685.70 1.600 0.599 0.100              
North Total or Average           136.92 1.600 0.599 0.100              
Non-North Total or Average           548.78 1.600 0.599 0.100              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2017-11-30 14:32:12

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
B-1 Boiler:HotWater 251700.10 0.90    
CH-1 Chiller:Electric:EIR 459421.76 5.00 6.57 22.42
CT-1 CoolingTower:VariableSpeed 587111.42      


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
L001_P01 COOLING COIL Coil:Cooling:Water 2647.52 2929.06 1971.77 957.29 0.67 - 277.81 2.82
L001_P02 COOLING COIL Coil:Cooling:Water 5429.59 6259.80 4259.87 1999.93 0.68 - 585.13 5.93
L001_P03 COOLING COIL Coil:Cooling:Water 3483.59 4390.06 3077.21 1312.85 0.70 - 396.32 4.02
L001_P04 COOLING COIL Coil:Cooling:Water 8305.25 10122.18 7070.07 3052.10 0.70 - 902.16 9.15
L001_P05 COOLING COIL Coil:Cooling:Water 6352.94 7941.15 5660.75 2280.39 0.71 - 680.07 6.90
L001_P06 COOLING COIL Coil:Cooling:Water 4933.90 6175.67 4404.71 1770.96 0.71 - 528.58 5.36
L001_P07 COOLING COIL Coil:Cooling:Water 4917.63 6422.17 4605.08 1817.08 0.72 - 558.12 5.66
L001_P08 COOLING COIL Coil:Cooling:Water 4365.18 5797.31 4188.61 1608.70 0.72 - 500.36 5.07
L001_P09 COOLING COIL Coil:Cooling:Water 4403.47 5849.62 4227.56 1622.06 0.72 - 504.64 5.12
L001_P10 COOLING COIL Coil:Cooling:Water 4634.86 6148.93 4438.34 1710.59 0.72 - 531.56 5.39
L001_P11 COOLING COIL Coil:Cooling:Water 5196.87 6941.79 5036.70 1905.09 0.73 - 594.23 6.03
L001_P12 COOLING COIL Coil:Cooling:Water 4057.28 5421.35 3934.29 1487.06 0.73 - 463.84 4.70
L001_P13 COOLING COIL Coil:Cooling:Water 3762.43 5029.80 3651.17 1378.63 0.73 - 430.02 4.36
L001_P14 COOLING COIL Coil:Cooling:Water 38956.89 46065.65 31667.78 14397.88 0.69 - 4226.96 42.87
L001_P15 COOLING COIL Coil:Cooling:Water 6671.96 8886.06 6436.16 2449.90 0.72 - 763.99 7.75
L002_P01 COOLING COIL Coil:Cooling:Water 2881.99 3329.07 2265.39 1063.68 0.68 - 311.67 3.16
L002_P02 COOLING COIL Coil:Cooling:Water 5840.46 6827.82 4669.53 2158.29 0.68 - 632.87 6.42
L002_P03 COOLING COIL Coil:Cooling:Water 3866.57 4937.10 3487.06 1450.04 0.71 - 439.87 4.46
L002_P04 COOLING COIL Coil:Cooling:Water 7286.03 9515.94 6861.13 2654.81 0.72 - 815.87 8.28
L002_P05 COOLING COIL Coil:Cooling:Water 6223.71 7753.87 5502.46 2251.41 0.71 - 670.55 6.80
L002_P06 COOLING COIL Coil:Cooling:Water 4815.60 6034.82 4302.10 1732.72 0.71 - 517.62 5.25
L002_P07 COOLING COIL Coil:Cooling:Water 4888.09 6492.76 4693.94 1798.83 0.72 - 559.64 5.68
L002_P08 COOLING COIL Coil:Cooling:Water 4363.70 5791.03 4181.75 1609.28 0.72 - 500.23 5.07
L002_P09 COOLING COIL Coil:Cooling:Water 4433.14 5885.58 4251.78 1633.80 0.72 - 508.04 5.15
L002_P10 COOLING COIL Coil:Cooling:Water 4665.51 6185.93 4463.23 1722.70 0.72 - 535.06 5.43
L002_P11 COOLING COIL Coil:Cooling:Water 4932.80 6575.61 4765.59 1810.02 0.72 - 564.57 5.73
L002_P12 COOLING COIL Coil:Cooling:Water 3880.96 5175.89 3752.16 1423.74 0.72 - 444.08 4.50
L002_P13 COOLING COIL Coil:Cooling:Water 38125.85 46254.68 32166.28 14088.41 0.70 - 4164.73 42.24
L002_P14 COOLING COIL Coil:Cooling:Water 3624.05 4836.34 3507.28 1329.07 0.73 - 414.55 4.20
L002_P15 COOLING COIL Coil:Cooling:Water 6397.05 8508.74 6155.05 2353.69 0.72 - 733.07 7.44
L003_P01 COOLING COIL Coil:Cooling:Water 2738.16 3231.87 2216.45 1015.42 0.69 - 298.67 3.03
L003_P02 COOLING COIL Coil:Cooling:Water 6107.90 7297.92 5035.52 2262.41 0.69 - 666.39 6.76
L003_P03 COOLING COIL Coil:Cooling:Water 5014.07 5807.56 3957.29 1850.27 0.68 - 541.98 5.50
L003_P04 COOLING COIL Coil:Cooling:Water 7209.53 9416.71 6786.94 2629.77 0.72 - 808.17 8.20
L003_P05 COOLING COIL Coil:Cooling:Water 6418.93 8015.42 5702.81 2312.62 0.71 - 689.42 6.99
L003_P06 COOLING COIL Coil:Cooling:Water 5279.69 6593.06 4688.82 1904.24 0.71 - 567.74 5.76
L003_P07 COOLING COIL Coil:Cooling:Water 4902.52 6512.03 4707.57 1804.46 0.72 - 561.39 5.69
L003_P08 COOLING COIL Coil:Cooling:Water 4395.37 5842.88 4224.93 1617.95 0.72 - 503.66 5.11
L003_P09 COOLING COIL Coil:Cooling:Water 4419.01 5865.23 4235.77 1629.46 0.72 - 506.56 5.14
L003_P10 COOLING COIL Coil:Cooling:Water 4667.75 6197.80 4476.71 1721.10 0.72 - 535.21 5.43
L003_P11 COOLING COIL Coil:Cooling:Water 5242.39 6999.12 5076.90 1922.22 0.73 - 599.57 6.08
L003_P12 COOLING COIL Coil:Cooling:Water 4059.05 5417.46 3928.92 1488.54 0.73 - 464.30 4.71
L003_P13 COOLING COIL Coil:Cooling:Water 38343.89 46920.19 32788.52 14131.66 0.70 - 4188.82 42.49
L003_P14 COOLING COIL Coil:Cooling:Water 3793.69 5065.86 3674.99 1390.87 0.73 - 433.83 4.40
L003_P15 COOLING COIL Coil:Cooling:Water 6755.55 8996.23 6515.16 2481.07 0.72 - 773.61 7.85
DOAS COOLING COIL Coil:Cooling:Water 135737.72 106779.64 67466.35 39313.29 0.63 - 12561.07 127.40
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
None            


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
L001_P01 HEATING COIL Coil:Heating:Water 1814.50 1959.49 -
L001_P02 HEATING COIL Coil:Heating:Water 3511.29 3495.26 -
L001_P03 HEATING COIL Coil:Heating:Water 3256.58 3217.63 -
L001_P04 HEATING COIL Coil:Heating:Water 5030.29 5349.71 -
L001_P05 HEATING COIL Coil:Heating:Water 3244.10 3171.82 -
L001_P06 HEATING COIL Coil:Heating:Water 2716.68 2659.69 -
L001_P07 HEATING COIL Coil:Heating:Water 3270.58 3157.46 -
L001_P08 HEATING COIL Coil:Heating:Water 2912.40 2860.40 -
L001_P09 HEATING COIL Coil:Heating:Water 2758.09 2724.73 -
L001_P10 HEATING COIL Coil:Heating:Water 3083.72 3043.40 -
L001_P11 HEATING COIL Coil:Heating:Water 2958.10 2861.49 -
L001_P12 HEATING COIL Coil:Heating:Water 2364.20 2291.03 -
L001_P13 HEATING COIL Coil:Heating:Water 2096.75 2046.28 -
L001_P14 HEATING COIL Coil:Heating:Water 25036.93 24582.46 -
L001_P15 HEATING COIL Coil:Heating:Water 4070.94 3930.47 -
L002_P01 HEATING COIL Coil:Heating:Water 1401.87 1442.54 -
L002_P02 HEATING COIL Coil:Heating:Water 2564.51 2637.30 -
L002_P03 HEATING COIL Coil:Heating:Water 2590.49 2632.84 -
L002_P04 HEATING COIL Coil:Heating:Water 5218.77 5123.97 -
L002_P05 HEATING COIL Coil:Heating:Water 2671.19 2681.68 -
L002_P06 HEATING COIL Coil:Heating:Water 2238.40 2249.24 -
L002_P07 HEATING COIL Coil:Heating:Water 3111.69 3067.15 -
L002_P08 HEATING COIL Coil:Heating:Water 2370.08 2390.16 -
L002_P09 HEATING COIL Coil:Heating:Water 2182.43 2216.85 -
L002_P10 HEATING COIL Coil:Heating:Water 2439.27 2475.87 -
L002_P11 HEATING COIL Coil:Heating:Water 2519.07 2498.10 -
L002_P12 HEATING COIL Coil:Heating:Water 2019.39 2004.63 -
L002_P13 HEATING COIL Coil:Heating:Water 19857.27 20071.30 -
L002_P14 HEATING COIL Coil:Heating:Water 1755.82 1757.01 -
L002_P15 HEATING COIL Coil:Heating:Water 3647.72 3599.98 -
L003_P01 HEATING COIL Coil:Heating:Water 2142.63 2310.20 -
L003_P02 HEATING COIL Coil:Heating:Water 3691.14 3646.95 -
L003_P03 HEATING COIL Coil:Heating:Water 3476.36 3727.90 -
L003_P04 HEATING COIL Coil:Heating:Water 5788.10 6150.17 -
L003_P05 HEATING COIL Coil:Heating:Water 3430.28 3331.78 -
L003_P06 HEATING COIL Coil:Heating:Water 2864.23 2786.95 -
L003_P07 HEATING COIL Coil:Heating:Water 3663.20 3894.59 -
L003_P08 HEATING COIL Coil:Heating:Water 3071.60 2998.06 -
L003_P09 HEATING COIL Coil:Heating:Water 2909.96 2855.91 -
L003_P10 HEATING COIL Coil:Heating:Water 3254.65 3190.93 -
L003_P11 HEATING COIL Coil:Heating:Water 3091.07 3288.64 -
L003_P12 HEATING COIL Coil:Heating:Water 2504.72 2665.36 -
L003_P13 HEATING COIL Coil:Heating:Water 26555.25 25885.79 -
L003_P14 HEATING COIL Coil:Heating:Water 2322.74 2473.89 -
L003_P15 HEATING COIL Coil:Heating:Water 4163.17 4428.06 -
DOAS HEATING COIL Coil:Heating:Water 53123.12 43094.46 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
L001_P01 SUPPLY FAN Fan:OnOff 0.25 160.07 0.11 72.05 640.27 1.00 General
L001_P02 SUPPLY FAN Fan:OnOff 0.25 160.07 0.25 160.44 640.27 1.00 General
L001_P03 SUPPLY FAN Fan:OnOff 0.25 160.07 0.20 125.92 640.27 1.00 General
L001_P04 SUPPLY FAN Fan:OnOff 0.25 160.07 0.45 288.39 640.27 1.00 General
L001_P05 SUPPLY FAN Fan:OnOff 0.25 160.07 0.39 247.42 640.27 1.00 General
L001_P06 SUPPLY FAN Fan:OnOff 0.25 160.07 0.30 192.85 640.27 1.00 General
L001_P07 SUPPLY FAN Fan:OnOff 0.25 160.07 0.32 202.71 640.27 1.00 General
L001_P08 SUPPLY FAN Fan:OnOff 0.25 160.07 0.29 188.63 640.27 1.00 General
L001_P09 SUPPLY FAN Fan:OnOff 0.25 160.07 0.30 190.57 640.27 1.00 General
L001_P10 SUPPLY FAN Fan:OnOff 0.25 160.07 0.31 199.21 640.27 1.00 General
L001_P11 SUPPLY FAN Fan:OnOff 0.25 160.07 0.36 230.36 640.27 1.00 General
L001_P12 SUPPLY FAN Fan:OnOff 0.25 160.07 0.28 180.09 640.27 1.00 General
L001_P13 SUPPLY FAN Fan:OnOff 0.25 160.07 0.26 167.32 640.27 1.00 General
L001_P14 SUPPLY FAN Fan:OnOff 0.25 160.07 1.92 1229.45 640.27 1.00 General
L001_P15 SUPPLY FAN Fan:OnOff 0.25 160.07 0.46 292.32 640.27 1.00 General
L002_P01 SUPPLY FAN Fan:OnOff 0.25 160.07 0.13 85.28 640.27 1.00 General
L002_P02 SUPPLY FAN Fan:OnOff 0.25 160.07 0.28 178.45 640.27 1.00 General
L002_P03 SUPPLY FAN Fan:OnOff 0.25 160.07 0.23 146.14 640.27 1.00 General
L002_P04 SUPPLY FAN Fan:OnOff 0.25 160.07 0.48 308.49 640.27 1.00 General
L002_P05 SUPPLY FAN Fan:OnOff 0.25 160.07 0.37 236.61 640.27 1.00 General
L002_P06 SUPPLY FAN Fan:OnOff 0.25 160.07 0.29 187.91 640.27 1.00 General
L002_P07 SUPPLY FAN Fan:OnOff 0.25 160.07 0.33 211.87 640.27 1.00 General
L002_P08 SUPPLY FAN Fan:OnOff 0.25 160.07 0.29 187.97 640.27 1.00 General
L002_P09 SUPPLY FAN Fan:OnOff 0.25 160.07 0.30 191.40 640.27 1.00 General
L002_P10 SUPPLY FAN Fan:OnOff 0.25 160.07 0.31 200.06 640.27 1.00 General
L002_P11 SUPPLY FAN Fan:OnOff 0.25 160.07 0.34 216.95 640.27 1.00 General
L002_P12 SUPPLY FAN Fan:OnOff 0.25 160.07 0.27 171.00 640.27 1.00 General
L002_P13 SUPPLY FAN Fan:OnOff 0.25 160.07 2.02 1292.90 640.27 1.00 General
L002_P14 SUPPLY FAN Fan:OnOff 0.25 160.07 0.25 160.08 640.27 1.00 General
L002_P15 SUPPLY FAN Fan:OnOff 0.25 160.07 0.43 278.32 640.27 1.00 General
L003_P01 SUPPLY FAN Fan:OnOff 0.25 160.07 0.13 85.36 640.27 1.00 General
L003_P02 SUPPLY FAN Fan:OnOff 0.25 160.07 0.31 197.58 640.27 1.00 General
L003_P03 SUPPLY FAN Fan:OnOff 0.25 160.07 0.23 149.59 640.27 1.00 General
L003_P04 SUPPLY FAN Fan:OnOff 0.25 160.07 0.48 304.69 640.27 1.00 General
L003_P05 SUPPLY FAN Fan:OnOff 0.25 160.07 0.39 247.50 640.27 1.00 General
L003_P06 SUPPLY FAN Fan:OnOff 0.25 160.07 0.32 203.15 640.27 1.00 General
L003_P07 SUPPLY FAN Fan:OnOff 0.25 160.07 0.33 212.44 640.27 1.00 General
L003_P08 SUPPLY FAN Fan:OnOff 0.25 160.07 0.30 190.79 640.27 1.00 General
L003_P09 SUPPLY FAN Fan:OnOff 0.25 160.07 0.30 190.47 640.27 1.00 General
L003_P10 SUPPLY FAN Fan:OnOff 0.25 160.07 0.31 201.40 640.27 1.00 General
L003_P11 SUPPLY FAN Fan:OnOff 0.25 160.07 0.36 231.94 640.27 1.00 General
L003_P12 SUPPLY FAN Fan:OnOff 0.25 160.07 0.28 179.36 640.27 1.00 General
L003_P13 SUPPLY FAN Fan:OnOff 0.25 160.07 2.09 1338.15 640.27 1.00 General
L003_P14 SUPPLY FAN Fan:OnOff 0.25 160.07 0.26 167.97 640.27 1.00 General
L003_P15 SUPPLY FAN Fan:OnOff 0.25 160.07 0.46 295.78 640.27 1.00 General
DOAS SUPPLY FAN Fan:VariableVolume 0.50 1748.57 3.17 11070.53 3497.14 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
HOT WATER LOOP HW SUPPLY PUMP Pump:VariableSpeed Continuous 300000.00 0.005993 2560.95 427350.43 0.90
CHILLED WATER LOOP CHW SUPPLY PUMP Pump:VariableSpeed Continuous 300000.00 0.021890 9354.81 427350.43 0.90
CHILLED WATER LOOP CNDW SUPPLY PUMP Pump:VariableSpeed Continuous 100000.00 0.023555 3355.43 142450.14 0.90


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
None            



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2017-11-30 14:32:12

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
L001_P01 1622.13 1622.13 36.87 0.113 0.113 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 09:00:00 24.00 24.77 0.01098 27.68 0.01656 0.035 0.00
L001_P02 3688.13 3688.13 43.91 0.251 0.251 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 09:00:00 24.00 25.01 0.01027 27.68 0.01656 0.067 0.00
L001_P03 2701.99 2701.99 37.05 0.197 0.197 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 10:00:00 24.00 24.21 0.00930 29.11 0.01656 0.058 0.00
L001_P04 6767.91 6767.91 72.72 0.450 0.450 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 09:00:00 24.00 25.26 0.00911 27.68 0.01656 0.074 0.00
L001_P05 5893.26 5893.26 101.10 0.386 0.386 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 09:00:00 24.00 25.45 0.00839 27.68 0.01656 0.047 0.00
L001_P06 4584.79 4584.79 95.52 0.301 0.301 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 09:00:00 24.00 25.42 0.00838 27.68 0.01656 0.038 0.00
L001_P07 4365.45 4365.45 80.84 0.317 0.317 3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 9) 9/21 10:00:00 24.00 24.25 0.00857 25.81 0.01428 0.043 0.00
L001_P08 3970.48 3970.48 73.53 0.295 0.295 3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 9) 9/21 13:00:00 24.00 24.00 0.00844 28.58 0.01428 0.043 0.00
L001_P09 4011.71 4011.71 72.28 0.298 0.298 3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 9) 9/21 13:00:00 24.00 24.00 0.00843 28.58 0.01428 0.044 0.00
L001_P10 4193.21 4193.21 67.09 0.311 0.311 3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 9) 9/21 13:00:00 24.00 24.00 0.00846 28.58 0.01428 0.050 0.00
L001_P11 4845.68 4845.68 106.50 0.360 0.360 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 18:00:00 24.00 23.99 0.00832 30.28 0.01656 0.036 0.00
L001_P12 3788.30 3788.30 106.71 0.281 0.281 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 18:00:00 24.00 23.99 0.00831 30.28 0.01656 0.028 0.00
L001_P13 3519.88 3519.88 103.53 0.261 0.261 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 18:00:00 24.00 23.99 0.00830 30.28 0.01656 0.027 0.00
L001_P14 28490.07 28490.07 55.24 1.920 1.920 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 09:00:00 24.00 25.11 0.00978 27.68 0.01656 0.413 0.00
L001_P15 6148.63 6148.63 99.17 0.457 0.457 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 18:00:00 24.00 23.99 0.00837 30.28 0.01656 0.050 0.00
L002_P01 1942.87 1942.87 44.16 0.133 0.133 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 09:00:00 24.00 24.91 0.01030 27.68 0.01656 0.035 0.00
L002_P02 4103.76 4103.76 48.85 0.279 0.279 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 09:00:00 24.00 25.02 0.01004 27.68 0.01656 0.067 0.00
L002_P03 3145.19 3145.19 43.13 0.228 0.228 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 10:00:00 24.00 24.25 0.00903 29.11 0.01656 0.058 0.00
L002_P04 6757.02 6757.02 72.60 0.482 0.482 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 10:00:00 24.00 24.45 0.00836 29.11 0.01656 0.074 0.00
L002_P05 5603.95 5603.95 96.13 0.370 0.370 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 09:00:00 24.00 25.38 0.00855 27.68 0.01656 0.047 0.00
L002_P06 4446.66 4446.66 92.64 0.293 0.293 3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 6) 6/21 09:00:00 24.00 25.37 0.00841 24.38 0.01428 0.038 0.00
L002_P07 4465.84 4465.84 82.70 0.331 0.331 3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 9) 9/21 13:00:00 24.00 24.02 0.00842 28.58 0.01428 0.043 0.00
L002_P08 3958.19 3958.19 73.30 0.294 0.294 3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 9) 9/21 13:00:00 24.00 24.00 0.00845 28.58 0.01428 0.043 0.00
L002_P09 4030.72 4030.72 72.63 0.299 0.299 3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 9) 9/21 13:00:00 24.00 24.01 0.00844 28.58 0.01428 0.044 0.00
L002_P10 4212.74 4212.74 67.40 0.312 0.312 3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 9) 9/21 13:00:00 24.00 24.00 0.00847 28.58 0.01428 0.050 0.00
L002_P11 4563.68 4563.68 100.30 0.339 0.339 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 18:00:00 24.00 23.99 0.00836 30.28 0.01656 0.036 0.00
L002_P12 3597.18 3597.18 101.33 0.267 0.267 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 18:00:00 24.00 23.99 0.00835 30.28 0.01656 0.028 0.00
L002_P13 29969.54 29969.54 58.11 2.019 2.019 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 09:00:00 24.00 25.11 0.00932 27.68 0.01656 0.413 0.00
L002_P14 3367.47 3367.47 99.04 0.250 0.250 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 18:00:00 24.00 23.99 0.00834 30.28 0.01656 0.027 0.00
L002_P15 5854.28 5854.28 94.42 0.435 0.435 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 18:00:00 24.00 23.99 0.00841 30.28 0.01656 0.050 0.00
L003_P01 1945.09 1945.09 44.21 0.133 0.133 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 09:00:00 24.00 24.91 0.00994 27.68 0.01656 0.035 0.00
L003_P02 4559.31 4559.31 54.28 0.309 0.309 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 09:00:00 24.00 25.06 0.00964 27.68 0.01656 0.067 0.00
L003_P03 3426.59 3426.59 46.98 0.234 0.234 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 09:00:00 24.00 24.97 0.01022 27.68 0.01656 0.058 0.00
L003_P04 6665.08 6665.08 71.61 0.476 0.476 3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 7) 7/21 10:00:00 24.00 24.43 0.00837 25.81 0.01428 0.074 0.00
L003_P05 5876.55 5876.55 100.81 0.387 0.387 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 09:00:00 24.00 25.41 0.00846 27.68 0.01656 0.047 0.00
L003_P06 4816.46 4816.46 100.34 0.317 0.317 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 09:00:00 24.00 25.39 0.00848 27.68 0.01656 0.038 0.00
L003_P07 4476.69 4476.69 82.90 0.332 0.332 3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 9) 9/21 13:00:00 24.00 24.01 0.00842 28.58 0.01428 0.043 0.00
L003_P08 4014.99 4014.99 74.35 0.298 0.298 3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 9) 9/21 14:00:00 24.00 24.00 0.00842 29.00 0.01428 0.043 0.00
L003_P09 4010.46 4010.46 72.26 0.297 0.297 3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 9) 9/21 13:00:00 24.00 24.00 0.00845 28.58 0.01428 0.044 0.00
L003_P10 4238.24 4238.24 67.81 0.315 0.315 3600175 ANN CLG .4% CONDNS DB=>MWB (MONTH 9) 9/21 14:00:00 24.00 24.00 0.00845 29.00 0.01428 0.050 0.00
L003_P11 4879.00 4879.00 107.23 0.362 0.362 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 18:00:00 24.00 23.99 0.00833 30.28 0.01656 0.036 0.00
L003_P12 3773.08 3773.08 106.28 0.280 0.280 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 18:00:00 24.00 23.99 0.00833 30.28 0.01656 0.028 0.00
L003_P13 31068.38 31068.38 60.24 2.090 2.090 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 09:00:00 24.00 25.13 0.00914 27.68 0.01656 0.413 0.00
L003_P14 3533.48 3533.48 103.93 0.262 0.262 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 18:00:00 24.00 23.99 0.00832 30.28 0.01656 0.027 0.00
L003_P15 6221.56 6221.56 100.35 0.462 0.462 3600175 ANN CLG .4% CONDNS ENTH=>MDB 7/21 18:00:00 24.00 23.99 0.00838 30.28 0.01656 0.050 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
L001_P01 1784.20 1784.20 40.55 0.093 0.093 3600175 ANN HTG 99.6% CONDNS DB 1/21 09:00:00 21.00 19.26 0.00659 -0.90 0.00295 0.035 0.00
L001_P02 3452.66 3452.66 41.10 0.135 0.135 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 14.07 0.00488 -0.90 0.00295 0.067 0.00
L001_P03 3202.20 3202.20 43.91 0.122 0.122 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 13.58 0.00470 -0.90 0.00295 0.058 0.00
L001_P04 4946.29 4946.29 53.15 0.242 0.242 3600175 ANN HTG 99.6% CONDNS DB 1/21 09:00:00 21.00 18.31 0.00594 -0.90 0.00295 0.074 0.00
L001_P05 3189.92 3189.92 54.72 0.118 0.118 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 12.87 0.00427 -0.90 0.00295 0.047 0.00
L001_P06 2671.31 2671.31 55.65 0.099 0.099 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 12.95 0.00422 -0.90 0.00295 0.038 0.00
L001_P07 3215.96 3215.96 59.55 0.114 0.114 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 12.00 0.00390 -0.90 0.00295 0.043 0.00
L001_P08 2863.76 2863.76 53.03 0.107 0.107 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 13.17 0.00424 -0.90 0.00295 0.043 0.00
L001_P09 2712.03 2712.03 48.87 0.103 0.103 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 13.56 0.00444 -0.90 0.00295 0.044 0.00
L001_P10 3032.23 3032.23 48.52 0.115 0.115 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 13.50 0.00448 -0.90 0.00295 0.050 0.00
L001_P11 2908.70 2908.70 63.93 0.104 0.104 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 12.14 0.00400 -0.90 0.00295 0.036 0.00
L001_P12 2324.72 2324.72 65.49 0.083 0.083 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 12.26 0.00394 -0.90 0.00295 0.028 0.00
L001_P13 2061.73 2061.73 60.64 0.076 0.076 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 12.74 0.00417 -0.90 0.00295 0.027 0.00
L001_P14 24618.82 24618.82 47.74 0.920 0.920 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 13.15 0.00458 -0.90 0.00295 0.413 0.00
L001_P15 4002.96 4002.96 64.56 0.142 0.142 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 12.00 0.00367 -0.90 0.00295 0.050 0.00
L002_P01 1378.46 1378.46 31.33 0.060 0.060 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 16.24 0.00534 -0.90 0.00295 0.035 0.00
L002_P02 2521.68 2521.68 30.02 0.109 0.109 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 16.19 0.00470 -0.90 0.00295 0.067 0.00
L002_P03 2547.23 2547.23 34.93 0.106 0.106 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 15.43 0.00453 -0.90 0.00295 0.058 0.00
L002_P04 5131.62 5131.62 55.14 0.192 0.192 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 13.13 0.00356 -0.90 0.00295 0.074 0.00
L002_P05 2626.58 2626.58 45.06 0.105 0.105 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 14.62 0.00412 -0.90 0.00295 0.047 0.00
L002_P06 2201.02 2201.02 45.85 0.088 0.088 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 14.68 0.00407 -0.90 0.00295 0.038 0.00
L002_P07 3059.73 3059.73 56.66 0.116 0.116 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 13.40 0.00366 -0.90 0.00295 0.043 0.00
L002_P08 2330.50 2330.50 43.16 0.095 0.095 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 14.91 0.00409 -0.90 0.00295 0.043 0.00
L002_P09 2145.98 2145.98 38.67 0.089 0.089 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 15.39 0.00428 -0.90 0.00295 0.044 0.00
L002_P10 2398.54 2398.54 38.38 0.100 0.100 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 15.34 0.00431 -0.90 0.00295 0.050 0.00
L002_P11 2477.00 2477.00 54.44 0.095 0.095 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 13.80 0.00386 -0.90 0.00295 0.036 0.00
L002_P12 1985.67 1985.67 55.93 0.077 0.077 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 13.87 0.00381 -0.90 0.00295 0.028 0.00
L002_P13 19525.66 19525.66 37.86 0.800 0.800 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 15.07 0.00441 -0.90 0.00295 0.413 0.00
L002_P14 1726.50 1726.50 50.78 0.068 0.068 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 14.40 0.00402 -0.90 0.00295 0.027 0.00
L002_P15 3586.80 3586.80 57.85 0.136 0.136 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 13.48 0.00350 -0.90 0.00295 0.050 0.00
L003_P01 2106.84 2106.84 47.88 0.109 0.109 3600175 ANN HTG 99.6% CONDNS DB 1/21 09:00:00 21.00 19.16 0.00663 -0.90 0.00295 0.035 0.00
L003_P02 3629.50 3629.50 43.21 0.138 0.138 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 13.58 0.00475 -0.90 0.00295 0.067 0.00
L003_P03 3418.31 3418.31 46.87 0.172 0.172 3600175 ANN HTG 99.6% CONDNS DB 1/21 09:00:00 21.00 18.82 0.00614 -0.90 0.00295 0.058 0.00
L003_P04 5691.44 5691.44 61.15 0.278 0.278 3600175 ANN HTG 99.6% CONDNS DB 1/21 09:00:00 21.00 18.26 0.00616 -0.90 0.00295 0.074 0.00
L003_P05 3372.99 3372.99 57.86 0.122 0.122 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 12.42 0.00413 -0.90 0.00295 0.047 0.00
L003_P06 2816.39 2816.39 58.67 0.102 0.102 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 12.54 0.00408 -0.90 0.00295 0.038 0.00
L003_P07 3602.03 3602.03 66.70 0.176 0.176 3600175 ANN HTG 99.6% CONDNS DB 1/21 09:00:00 21.00 18.29 0.00613 -0.90 0.00295 0.043 0.00
L003_P08 3020.30 3020.30 55.93 0.111 0.111 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 12.75 0.00410 -0.90 0.00295 0.043 0.00
L003_P09 2861.36 2861.36 51.56 0.107 0.107 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 13.12 0.00430 -0.90 0.00295 0.044 0.00
L003_P10 3200.30 3200.30 51.20 0.119 0.119 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 13.05 0.00434 -0.90 0.00295 0.050 0.00
L003_P11 3039.45 3039.45 66.80 0.149 0.149 3600175 ANN HTG 99.6% CONDNS DB 1/21 09:00:00 21.00 18.34 0.00610 -0.90 0.00295 0.036 0.00
L003_P12 2462.89 2462.89 69.38 0.121 0.121 3600175 ANN HTG 99.6% CONDNS DB 1/21 09:00:00 21.00 18.35 0.00608 -0.90 0.00295 0.028 0.00
L003_P13 26111.79 26111.79 50.63 0.954 0.954 3600175 ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 12.67 0.00444 -0.90 0.00295 0.413 0.00
L003_P14 2283.95 2283.95 67.17 0.112 0.112 3600175 ANN HTG 99.6% CONDNS DB 1/21 09:00:00 21.00 18.41 0.00615 -0.90 0.00295 0.027 0.00
L003_P15 4093.64 4093.64 66.03 0.200 0.200 3600175 ANN HTG 99.6% CONDNS DB 1/21 09:00:00 21.00 18.32 0.00603 -0.90 0.00295 0.050 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
DOAS 19.08 3.17 7.78 3.17


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2017-11-30 14:32:12

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
L001_P01 3.00 4.40 154.00 0.352 0.030 0.000 0.000
L001_P02 5.72 8.40 294.00 0.352 0.042 0.000 0.000
L001_P03 4.97 7.29 255.26 0.352 0.048 0.000 0.000
L001_P04 6.34 9.31 325.74 0.352 0.095 0.000 0.000
L001_P05 3.97 5.83 204.03 0.352 0.062 0.000 0.000
L001_P06 3.27 4.80 168.00 0.352 0.064 0.000 0.000
L001_P07 3.68 5.40 189.00 0.352 0.087 0.000 0.000
L001_P08 3.68 5.40 189.00 0.352 0.063 0.000 0.000
L001_P09 3.78 5.55 194.25 0.352 0.055 0.000 0.000
L001_P10 4.26 6.25 218.75 0.352 0.054 0.000 0.000
L001_P11 3.10 4.55 159.25 0.352 0.075 0.000 0.000
L001_P12 2.42 3.55 124.25 0.352 0.078 0.000 0.000
L001_P13 2.32 3.40 119.00 0.352 0.067 0.000 0.000
L001_P14 35.12 51.57 1804.97 0.352 0.052 0.000 0.000
L001_P15 4.22 6.20 217.00 0.352 0.099 0.000 0.000
L002_P01 3.00 4.40 154.00 0.352 0.032 0.000 0.000
L002_P02 5.72 8.40 294.00 0.352 0.046 0.000 0.000
L002_P03 4.97 7.29 255.26 0.352 0.052 0.000 0.000
L002_P04 6.34 9.31 325.74 0.352 0.103 0.000 0.000
L002_P05 3.97 5.83 204.03 0.352 0.068 0.000 0.000
L002_P06 3.27 4.80 168.00 0.352 0.070 0.000 0.000
L002_P07 3.68 5.40 189.00 0.352 0.095 0.000 0.000
L002_P08 3.68 5.40 189.00 0.352 0.068 0.000 0.000
L002_P09 3.78 5.55 194.25 0.352 0.060 0.000 0.000
L002_P10 4.26 6.25 218.75 0.352 0.059 0.000 0.000
L002_P11 3.10 4.55 159.25 0.352 0.081 0.000 0.000
L002_P12 2.42 3.55 124.25 0.352 0.085 0.000 0.000
L002_P13 35.12 51.57 1804.97 0.352 0.056 0.000 0.000
L002_P14 2.32 3.40 119.00 0.352 0.073 0.000 0.000
L002_P15 4.22 6.20 217.00 0.352 0.108 0.000 0.000
L003_P01 3.00 4.40 154.00 0.352 0.033 0.000 0.000
L003_P02 5.72 8.40 294.00 0.352 0.048 0.000 0.000
L003_P03 4.97 7.29 255.26 0.352 0.054 0.000 0.000
L003_P04 6.34 9.31 325.74 0.352 0.107 0.000 0.000
L003_P05 3.97 5.83 204.03 0.352 0.070 0.000 0.000
L003_P06 3.27 4.80 168.00 0.352 0.072 0.000 0.000
L003_P07 3.68 5.40 189.00 0.352 0.098 0.000 0.000
L003_P08 3.68 5.40 189.00 0.352 0.071 0.000 0.000
L003_P09 3.78 5.55 194.25 0.352 0.063 0.000 0.000
L003_P10 4.26 6.25 218.75 0.352 0.062 0.000 0.000
L003_P11 3.10 4.55 159.25 0.352 0.085 0.000 0.000
L003_P12 2.42 3.55 124.25 0.352 0.088 0.000 0.000
L003_P13 35.12 51.57 1804.97 0.352 0.059 0.000 0.000
L003_P14 2.32 3.40 119.00 0.352 0.076 0.000 0.000
L003_P15 4.22 6.20 217.00 0.352 0.112 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
L001_P01 3.00 4.40 154.00 0.000 0.024 0.000 0.000
L001_P02 5.72 8.40 294.00 0.000 0.034 0.000 0.000
L001_P03 4.97 7.29 255.26 0.000 0.038 0.000 0.000
L001_P04 6.34 9.31 325.74 0.000 0.076 0.000 0.000
L001_P05 3.97 5.83 204.03 0.000 0.050 0.000 0.000
L001_P06 3.27 4.80 168.00 0.000 0.052 0.000 0.000
L001_P07 3.68 5.40 189.00 0.000 0.069 0.000 0.000
L001_P08 3.68 5.40 189.00 0.000 0.051 0.000 0.000
L001_P09 3.78 5.55 194.25 0.000 0.045 0.000 0.000
L001_P10 4.26 6.25 218.75 0.000 0.044 0.000 0.000
L001_P11 3.10 4.55 159.25 0.000 0.060 0.000 0.000
L001_P12 2.42 3.55 124.25 0.000 0.063 0.000 0.000
L001_P13 2.32 3.40 119.00 0.000 0.054 0.000 0.000
L001_P14 35.12 51.57 1804.97 0.000 0.041 0.000 0.000
L001_P15 4.22 6.20 217.00 0.000 0.080 0.000 0.000
L002_P01 3.00 4.40 154.00 0.000 0.025 0.000 0.000
L002_P02 5.72 8.40 294.00 0.000 0.036 0.000 0.000
L002_P03 4.97 7.29 255.26 0.000 0.041 0.000 0.000
L002_P04 6.34 9.31 325.74 0.000 0.082 0.000 0.000
L002_P05 3.97 5.83 204.03 0.000 0.054 0.000 0.000
L002_P06 3.27 4.80 168.00 0.000 0.055 0.000 0.000
L002_P07 3.68 5.40 189.00 0.000 0.075 0.000 0.000
L002_P08 3.68 5.40 189.00 0.000 0.054 0.000 0.000
L002_P09 3.78 5.55 194.25 0.000 0.048 0.000 0.000
L002_P10 4.26 6.25 218.75 0.000 0.047 0.000 0.000
L002_P11 3.10 4.55 159.25 0.000 0.065 0.000 0.000
L002_P12 2.42 3.55 124.25 0.000 0.068 0.000 0.000
L002_P13 35.12 51.57 1804.97 0.000 0.045 0.000 0.000
L002_P14 2.32 3.40 119.00 0.000 0.058 0.000 0.000
L002_P15 4.22 6.20 217.00 0.000 0.087 0.000 0.000
L003_P01 3.00 4.40 154.00 0.000 0.026 0.000 0.000
L003_P02 5.72 8.40 294.00 0.000 0.038 0.000 0.000
L003_P03 4.97 7.29 255.26 0.000 0.043 0.000 0.000
L003_P04 6.34 9.31 325.74 0.000 0.085 0.000 0.000
L003_P05 3.97 5.83 204.03 0.000 0.056 0.000 0.000
L003_P06 3.27 4.80 168.00 0.000 0.057 0.000 0.000
L003_P07 3.68 5.40 189.00 0.000 0.078 0.000 0.000
L003_P08 3.68 5.40 189.00 0.000 0.056 0.000 0.000
L003_P09 3.78 5.55 194.25 0.000 0.050 0.000 0.000
L003_P10 4.26 6.25 218.75 0.000 0.049 0.000 0.000
L003_P11 3.10 4.55 159.25 0.000 0.068 0.000 0.000
L003_P12 2.42 3.55 124.25 0.000 0.070 0.000 0.000
L003_P13 35.12 51.57 1804.97 0.000 0.047 0.000 0.000
L003_P14 2.32 3.40 119.00 0.000 0.061 0.000 0.000
L003_P15 4.22 6.20 217.00 0.000 0.090 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2017-11-30 14:32:12

AirTerminal:SingleDuct:VAV:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
L001_P01 DOAS AIR TERMINAL 0.035200
L001_P02 DOAS AIR TERMINAL 0.067200
L001_P03 DOAS AIR TERMINAL 0.058344
L001_P04 DOAS AIR TERMINAL 0.074456
L001_P05 DOAS AIR TERMINAL 0.046635
L001_P06 DOAS AIR TERMINAL 0.038400
L001_P07 DOAS AIR TERMINAL 0.043200
L001_P08 DOAS AIR TERMINAL 0.043200
L001_P09 DOAS AIR TERMINAL 0.044400
L001_P10 DOAS AIR TERMINAL 0.050000
L001_P11 DOAS AIR TERMINAL 0.036400
L001_P12 DOAS AIR TERMINAL 0.028400
L001_P13 DOAS AIR TERMINAL 0.027200
L001_P14 DOAS AIR TERMINAL 0.412565
L001_P15 DOAS AIR TERMINAL 0.049600
L002_P01 DOAS AIR TERMINAL 0.035200
L002_P02 DOAS AIR TERMINAL 0.067200
L002_P03 DOAS AIR TERMINAL 0.058344
L002_P04 DOAS AIR TERMINAL 0.074456
L002_P05 DOAS AIR TERMINAL 0.046635
L002_P06 DOAS AIR TERMINAL 0.038400
L002_P07 DOAS AIR TERMINAL 0.043200
L002_P08 DOAS AIR TERMINAL 0.043200
L002_P09 DOAS AIR TERMINAL 0.044400
L002_P10 DOAS AIR TERMINAL 0.050000
L002_P11 DOAS AIR TERMINAL 0.036400
L002_P12 DOAS AIR TERMINAL 0.028400
L002_P13 DOAS AIR TERMINAL 0.412565
L002_P14 DOAS AIR TERMINAL 0.027200
L002_P15 DOAS AIR TERMINAL 0.049600
L003_P01 DOAS AIR TERMINAL 0.035200
L003_P02 DOAS AIR TERMINAL 0.067200
L003_P03 DOAS AIR TERMINAL 0.058344
L003_P04 DOAS AIR TERMINAL 0.074456
L003_P05 DOAS AIR TERMINAL 0.046635
L003_P06 DOAS AIR TERMINAL 0.038400
L003_P07 DOAS AIR TERMINAL 0.043200
L003_P08 DOAS AIR TERMINAL 0.043200
L003_P09 DOAS AIR TERMINAL 0.044400
L003_P10 DOAS AIR TERMINAL 0.050000
L003_P11 DOAS AIR TERMINAL 0.036400
L003_P12 DOAS AIR TERMINAL 0.028400
L003_P13 DOAS AIR TERMINAL 0.412565
L003_P14 DOAS AIR TERMINAL 0.027200
L003_P15 DOAS AIR TERMINAL 0.049600
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
L001_P01 FAN COIL 0.112524 0.000043 0.000126
L001_P02 FAN COIL 0.250589 0.000084 0.000259
L001_P03 FAN COIL 0.196674 0.000078 0.000166
L001_P04 FAN COIL 0.450424 0.000120 0.000396
L001_P05 FAN COIL 0.386429 0.000078 0.000303
L001_P06 FAN COIL 0.301199 0.000065 0.000235
L001_P07 FAN COIL 0.316609 0.000078 0.000234
L001_P08 FAN COIL 0.294614 0.000070 0.000208
L001_P09 FAN COIL 0.297639 0.000066 0.000210
L001_P10 FAN COIL 0.311138 0.000074 0.000221
L001_P11 FAN COIL 0.359788 0.000071 0.000248
L001_P12 FAN COIL 0.281267 0.000056 0.000193
L001_P13 FAN COIL 0.261331 0.000050 0.000179
L001_P14 FAN COIL 1.92 0.000598 0.001856
L001_P15 FAN COIL 0.456554 0.000097 0.000318
L002_P01 FAN COIL 0.133189 0.000034 0.000137
L002_P02 FAN COIL 0.278711 0.000061 0.000278
L002_P03 FAN COIL 0.228247 0.000062 0.000184
L002_P04 FAN COIL 0.481821 0.000125 0.000347
L002_P05 FAN COIL 0.369543 0.000064 0.000297
L002_P06 FAN COIL 0.293481 0.000053 0.000229
L002_P07 FAN COIL 0.330915 0.000074 0.000233
L002_P08 FAN COIL 0.293585 0.000057 0.000208
L002_P09 FAN COIL 0.298931 0.000052 0.000211
L002_P10 FAN COIL 0.312463 0.000058 0.000222
L002_P11 FAN COIL 0.338843 0.000060 0.000235
L002_P12 FAN COIL 0.267075 0.000048 0.000185
L002_P13 FAN COIL 2.02 0.000475 0.001817
L002_P14 FAN COIL 0.250015 0.000042 0.000173
L002_P15 FAN COIL 0.434691 0.000087 0.000305
L003_P01 FAN COIL 0.133313 0.000051 0.000130
L003_P02 FAN COIL 0.308587 0.000088 0.000291
L003_P03 FAN COIL 0.233637 0.000083 0.000239
L003_P04 FAN COIL 0.475873 0.000138 0.000344
L003_P05 FAN COIL 0.386551 0.000082 0.000306
L003_P06 FAN COIL 0.317288 0.000068 0.000252
L003_P07 FAN COIL 0.331794 0.000088 0.000234
L003_P08 FAN COIL 0.297985 0.000073 0.000209
L003_P09 FAN COIL 0.297481 0.000070 0.000211
L003_P10 FAN COIL 0.314561 0.000078 0.000222
L003_P11 FAN COIL 0.362253 0.000074 0.000250
L003_P12 FAN COIL 0.280135 0.000060 0.000193
L003_P13 FAN COIL 2.09 0.000635 0.001827
L003_P14 FAN COIL 0.262341 0.000056 0.000181
L003_P15 FAN COIL 0.461963 0.000099 0.000322
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
L001_P01 SUPPLY FAN 0.112524
L001_P02 SUPPLY FAN 0.250589
L001_P03 SUPPLY FAN 0.196674
L001_P04 SUPPLY FAN 0.450424
L001_P05 SUPPLY FAN 0.386429
L001_P06 SUPPLY FAN 0.301199
L001_P07 SUPPLY FAN 0.316609
L001_P08 SUPPLY FAN 0.294614
L001_P09 SUPPLY FAN 0.297639
L001_P10 SUPPLY FAN 0.311138
L001_P11 SUPPLY FAN 0.359788
L001_P12 SUPPLY FAN 0.281267
L001_P13 SUPPLY FAN 0.261331
L001_P14 SUPPLY FAN 1.92
L001_P15 SUPPLY FAN 0.456554
L002_P01 SUPPLY FAN 0.133189
L002_P02 SUPPLY FAN 0.278711
L002_P03 SUPPLY FAN 0.228247
L002_P04 SUPPLY FAN 0.481821
L002_P05 SUPPLY FAN 0.369543
L002_P06 SUPPLY FAN 0.293481
L002_P07 SUPPLY FAN 0.330915
L002_P08 SUPPLY FAN 0.293585
L002_P09 SUPPLY FAN 0.298931
L002_P10 SUPPLY FAN 0.312463
L002_P11 SUPPLY FAN 0.338843
L002_P12 SUPPLY FAN 0.267075
L002_P13 SUPPLY FAN 2.02
L002_P14 SUPPLY FAN 0.250015
L002_P15 SUPPLY FAN 0.434691
L003_P01 SUPPLY FAN 0.133313
L003_P02 SUPPLY FAN 0.308587
L003_P03 SUPPLY FAN 0.233637
L003_P04 SUPPLY FAN 0.475873
L003_P05 SUPPLY FAN 0.386551
L003_P06 SUPPLY FAN 0.317288
L003_P07 SUPPLY FAN 0.331794
L003_P08 SUPPLY FAN 0.297985
L003_P09 SUPPLY FAN 0.297481
L003_P10 SUPPLY FAN 0.314561
L003_P11 SUPPLY FAN 0.362253
L003_P12 SUPPLY FAN 0.280135
L003_P13 SUPPLY FAN 2.09
L003_P14 SUPPLY FAN 0.262341
L003_P15 SUPPLY FAN 0.461963
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] User-Specified Design Air Flow Rate [m3/s] Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio Design Size Design Coil Load [W]
L001_P01 COOLING COIL 0.000126 0.112524 0.112524 24.77 7.00 0.010978 13.00 0.008000  
L001_P02 COOLING COIL 0.000259 0.250589 0.250589 25.01 7.00 0.010271 13.00 0.008000  
L001_P03 COOLING COIL 0.000166 0.196674 0.196674 24.21 7.00 0.009299 13.00 0.008000  
L001_P04 COOLING COIL 0.000396 0.450424 0.450424 25.26 7.00 0.009115 13.00 0.008000  
L001_P05 COOLING COIL 0.000303 0.386429 0.386429 25.45 7.00 0.008389 13.00 0.008000  
L001_P06 COOLING COIL 0.000235 0.301199 0.301199 25.42 7.00 0.008379 13.00 0.008000  
L001_P07 COOLING COIL 0.000234 0.316609 0.316609 24.25 7.00 0.008570 13.00 0.008000  
L001_P08 COOLING COIL 0.000208 0.294614 0.294614 24.00 7.00 0.008438 13.00 0.008000  
L001_P09 COOLING COIL 0.000210 0.297639 0.297639 24.00 7.00 0.008430 13.00 0.008000  
L001_P10 COOLING COIL 0.000221 0.311138 0.311138 24.00 7.00 0.008464 13.00 0.008000  
L001_P11 COOLING COIL 0.000248 0.359788 0.359788 23.99 7.00 0.008319 13.00 0.008000  
L001_P12 COOLING COIL 0.000193 0.281267 0.281267 23.99 7.00 0.008313 13.00 0.008000  
L001_P13 COOLING COIL 0.000179 0.261331 0.261331 23.99 7.00 0.008303 13.00 0.008000  
L001_P14 COOLING COIL 0.001856 1.92 1.92 25.11 7.00 0.009781 13.00 0.008000  
L001_P15 COOLING COIL 0.000318 0.456554 0.456554 23.99 7.00 0.008375 13.00 0.008000  
L002_P01 COOLING COIL 0.000137 0.133189 0.133189 24.91 7.00 0.010304 13.00 0.008000  
L002_P02 COOLING COIL 0.000278 0.278711 0.278711 25.02 7.00 0.010036 13.00 0.008000  
L002_P03 COOLING COIL 0.000184 0.228247 0.228247 24.25 7.00 0.009033 13.00 0.008000  
L002_P04 COOLING COIL 0.000347 0.481821 0.481821 24.45 7.00 0.008359 13.00 0.008000  
L002_P05 COOLING COIL 0.000297 0.369543 0.369543 25.38 7.00 0.008548 13.00 0.008000  
L002_P06 COOLING COIL 0.000229 0.293481 0.293481 25.37 7.00 0.008411 13.00 0.008000  
L002_P07 COOLING COIL 0.000233 0.330915 0.330915 24.02 7.00 0.008417 13.00 0.008000  
L002_P08 COOLING COIL 0.000208 0.293585 0.293585 24.00 7.00 0.008452 13.00 0.008000  
L002_P09 COOLING COIL 0.000211 0.298931 0.298931 24.01 7.00 0.008440 13.00 0.008000  
L002_P10 COOLING COIL 0.000222 0.312463 0.312463 24.00 7.00 0.008474 13.00 0.008000  
L002_P11 COOLING COIL 0.000235 0.338843 0.338843 23.99 7.00 0.008356 13.00 0.008000  
L002_P12 COOLING COIL 0.000185 0.267075 0.267075 23.99 7.00 0.008347 13.00 0.008000  
L002_P13 COOLING COIL 0.001817 2.02 2.02 25.11 7.00 0.009320 13.00 0.008000  
L002_P14 COOLING COIL 0.000173 0.250015 0.250015 23.99 7.00 0.008336 13.00 0.008000  
L002_P15 COOLING COIL 0.000305 0.434691 0.434691 23.99 7.00 0.008408 13.00 0.008000  
L003_P01 COOLING COIL 0.000130 0.133313 0.133313 24.91 7.00 0.009944 13.00 0.008000  
L003_P02 COOLING COIL 0.000291 0.308587 0.308587 25.06 7.00 0.009640 13.00 0.008000  
L003_P03 COOLING COIL 0.000239 0.233637 0.233637 24.97 7.00 0.010220 13.00 0.008000  
L003_P04 COOLING COIL 0.000344 0.475873 0.475873 24.43 7.00 0.008374 13.00 0.008000  
L003_P05 COOLING COIL 0.000306 0.386551 0.386551 25.41 7.00 0.008458 13.00 0.008000  
L003_P06 COOLING COIL 0.000252 0.317288 0.317288 25.39 7.00 0.008477 13.00 0.008000  
L003_P07 COOLING COIL 0.000234 0.331794 0.331794 24.01 7.00 0.008420 13.00 0.008000  
L003_P08 COOLING COIL 0.000209 0.297985 0.297985 24.00 7.00 0.008417 13.00 0.008000  
L003_P09 COOLING COIL 0.000211 0.297481 0.297481 24.00 7.00 0.008449 13.00 0.008000  
L003_P10 COOLING COIL 0.000222 0.314561 0.314561 24.00 7.00 0.008446 13.00 0.008000  
L003_P11 COOLING COIL 0.000250 0.362253 0.362253 23.99 7.00 0.008328 13.00 0.008000  
L003_P12 COOLING COIL 0.000193 0.280135 0.280135 23.99 7.00 0.008334 13.00 0.008000  
L003_P13 COOLING COIL 0.001827 2.09 2.09 25.13 7.00 0.009137 13.00 0.008000  
L003_P14 COOLING COIL 0.000181 0.262341 0.262341 23.99 7.00 0.008324 13.00 0.008000  
L003_P15 COOLING COIL 0.000322 0.461963 0.461963 23.99 7.00 0.008378 13.00 0.008000  
DOAS COOLING COIL 0.006467 3.17   28.34 7.00 0.016027 13.00 0.008407 135737.72
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Water

Design Size Design Coil Load [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
L001_P01 HEATING COIL 1814.50 0.000043 39.67
L001_P02 HEATING COIL 3511.29 0.000084 72.67
L001_P03 HEATING COIL 3256.58 0.000078 67.07
L001_P04 HEATING COIL 5030.29 0.000120 108.82
L001_P05 HEATING COIL 3244.10 0.000078 66.36
L001_P06 HEATING COIL 2716.68 0.000065 55.62
L001_P07 HEATING COIL 3270.58 0.000078 66.36
L001_P08 HEATING COIL 2912.40 0.000070 59.75
L001_P09 HEATING COIL 2758.09 0.000066 56.80
L001_P10 HEATING COIL 3083.72 0.000074 63.47
L001_P11 HEATING COIL 2958.10 0.000071 60.09
L001_P12 HEATING COIL 2364.20 0.000056 48.09
L001_P13 HEATING COIL 2096.75 0.000050 42.84
L001_P14 HEATING COIL 25036.93 0.000598 513.54
L001_P15 HEATING COIL 4070.94 0.000097 82.61
L002_P01 HEATING COIL 1401.87 0.000034 29.66
L002_P02 HEATING COIL 2564.51 0.000061 54.24
L002_P03 HEATING COIL 2590.49 0.000062 54.36
L002_P04 HEATING COIL 5218.77 0.000125 107.07
L002_P05 HEATING COIL 2671.19 0.000064 55.60
L002_P06 HEATING COIL 2238.40 0.000053 46.62
L002_P07 HEATING COIL 3111.69 0.000074 64.00
L002_P08 HEATING COIL 2370.08 0.000057 49.48
L002_P09 HEATING COIL 2182.43 0.000052 45.78
L002_P10 HEATING COIL 2439.27 0.000058 51.14
L002_P11 HEATING COIL 2519.07 0.000060 52.02
L002_P12 HEATING COIL 2019.39 0.000048 41.73
L002_P13 HEATING COIL 19857.27 0.000475 415.19
L002_P14 HEATING COIL 1755.82 0.000042 36.47
L002_P15 HEATING COIL 3647.72 0.000087 75.09
L003_P01 HEATING COIL 2142.63 0.000051 46.79
L003_P02 HEATING COIL 3691.14 0.000088 76.02
L003_P03 HEATING COIL 3476.36 0.000083 75.63
L003_P04 HEATING COIL 5788.10 0.000138 125.13
L003_P05 HEATING COIL 3430.28 0.000082 69.87
L003_P06 HEATING COIL 2864.23 0.000068 58.41
L003_P07 HEATING COIL 3663.20 0.000088 79.23
L003_P08 HEATING COIL 3071.60 0.000073 62.77
L003_P09 HEATING COIL 2909.96 0.000070 59.67
L003_P10 HEATING COIL 3254.65 0.000078 66.70
L003_P11 HEATING COIL 3091.07 0.000074 66.89
L003_P12 HEATING COIL 2504.72 0.000060 54.21
L003_P13 HEATING COIL 26555.25 0.000635 542.13
L003_P14 HEATING COIL 2322.74 0.000056 50.30
L003_P15 HEATING COIL 4163.17 0.000099 90.07
DOAS HEATING COIL 53123.12 0.001269 799.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Branch

Maximum Flow Rate [m3/s]
DOAS MAIN BRANCH 3.17
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
DOAS 3.17
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
DOAS OA CONTROLLER 3.17 3.17
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
DOAS HEAT RECOVERY 3.17
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W]
DOAS HUMIDIFIER 0.000023 5.00 0.129638E+11
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
DOAS SUPPLY FAN 3.17
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
DOAS COOLING COIL CONTROLLER 0.006467 0.000074
DOAS HEATING COIL CONTROLLER 0.001269 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HOT WATER LOOP HOT WATER LOOP 0.005993 26.97
CHILLED WATER LOOP CHILLED WATER LOOP 0.021890 98.51
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
HOT WATER LOOP HW SUPPLY PUMP 0.005993 2560.95
CHILLED WATER LOOP CHW SUPPLY PUMP 0.021890 9354.81
CHILLED WATER LOOP CNDW SUPPLY PUMP 0.023555 3355.43
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
B-1 251700.10 0.005993
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
CH-1 0.021890 459421.76 0.023555
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
CHILLED WATER LOOP CONDENSER WATER LOOP 0.023555 106.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Water Flow Rate [m3/s] Fan Power at Design Air Flow Rate [W] Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
CT-1 0.023555 5788.71 15.27 587111.42 3.05 73388.93
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Zone Component Load Summary

For: L001_P01

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 262.97 13.72   257.81 534.50 30.48
Lights 190.08 34.16 0.00   224.24 12.79
Equipment 396.00 21.26   0.00 417.26 23.80
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 4.71     24.15 28.85 1.65
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   78.15     78.15 4.46
Other Roof   0.00     0.00 0.00
Exterior Wall   37.11     37.11 2.12
Interzone Wall   341.29     341.29 19.46
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   0.00     0.00 0.00
Ground Contact Floor   -6.0     -6.0 -0.3
Other Floor   0.00     0.00 0.00
Fenestration Conduction 9.05       9.05 0.52
Fenestration Solar   88.99     88.99 5.08
Opaque Door   0.00     0.00 0.00
Grand Total 862.80 608.72 0.00 281.95 1753.47  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 09:00:00
Outside Dry Bulb Temperature [C] 27.68
Outside Wet Bulb Temperature [C] 23.51
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 24.77
Zone Relative Humdity [%] 56.23
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.01098
Peak Design Sensible Load [W] 1622.13
Estimated Instant + Delayed Sensible Load [W] 1471.52
Difference [W] 150.61


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -57.7     -30.9 -88.6 7.07
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   -168.2     -168.2 13.43
Other Roof   0.00     0.00 -0.00
Exterior Wall   -86.5     -86.5 6.91
Interzone Wall   -628.6     -628.6 50.20
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   0.00     0.00 -0.00
Ground Contact Floor   -193.6     -193.6 15.46
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -86.6       -86.6 6.92
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -144.3 -1076.9 0.00 -30.9 -1252.1  


Heating Peak Conditions

Value
Time of Peak Load 1/21 09:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 19.26
Zone Relative Humdity [%] 47.59
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00659
Peak Design Sensible Load [W] -1784.2
Estimated Instant + Delayed Sensible Load [W] -1221.2
Difference [W] -563.0



Table of Contents

Report: Zone Component Load Summary

For: L001_P02

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 492.75 27.71   502.50 1022.96 26.67
Lights 362.88 68.30 0.00   431.18 11.24
Equipment 756.00 44.22   0.00 800.22 20.86
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 12.44     69.97 82.41 2.15
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -86.2     -86.2 -2.2
Other Roof   0.00     0.00 0.00
Exterior Wall   4.14     4.14 0.11
Interzone Wall   199.20     199.20 5.19
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   0.00     0.00 0.00
Ground Contact Floor   306.48     306.48 7.99
Other Floor   0.00     0.00 0.00
Fenestration Conduction 155.20       155.20 4.05
Fenestration Solar   920.24     920.24 23.99
Opaque Door   0.00     0.00 0.00
Grand Total 1779.26 1484.12 0.00 572.47 3835.86  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 09:00:00
Outside Dry Bulb Temperature [C] 27.68
Outside Wet Bulb Temperature [C] 23.51
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 25.01
Zone Relative Humdity [%] 51.90
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.01027
Peak Design Sensible Load [W] 3688.13
Estimated Instant + Delayed Sensible Load [W] 3263.38
Difference [W] 424.75


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -131.7     -53.5 -185.2 91.58
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   229.89     229.89 -113.7
Other Roof   0.00     0.00 -0.00
Exterior Wall   -0.3     -0.3 0.15
Interzone Wall   54.03     54.03 -26.7
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   0.00     0.00 -0.00
Ground Contact Floor   -98.8     -98.8 48.85
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -201.9       -201.9 99.84
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -333.5 184.84 0.00 -53.5 -202.2  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 14.07
Zone Relative Humdity [%] 49.13
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00488
Peak Design Sensible Load [W] -3452.7
Estimated Instant + Delayed Sensible Load [W] -148.7
Difference [W] -3304.0



Table of Contents

Report: Zone Component Load Summary

For: L001_P03

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 453.67 72.14   407.54 933.35 29.97
Lights 315.06 112.32 0.00   427.37 13.72
Equipment 656.37 109.35   0.00 765.72 24.59
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 19.48     75.19 94.67 3.04
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   220.24     220.24 7.07
Other Roof   0.00     0.00 0.00
Exterior Wall   87.05     87.05 2.80
Interzone Wall   408.68     408.68 13.12
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   0.00     0.00 0.00
Ground Contact Floor   -157.5     -157.5 -5.1
Other Floor   0.00     0.00 0.00
Fenestration Conduction 67.86       67.86 2.18
Fenestration Solar   267.03     267.03 8.57
Opaque Door   0.00     0.00 0.00
Grand Total 1512.44 1119.26 0.00 482.74 3114.44  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 10:00:00
Outside Dry Bulb Temperature [C] 29.11
Outside Wet Bulb Temperature [C] 23.89
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 24.21
Zone Relative Humdity [%] 49.36
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00930
Peak Design Sensible Load [W] 2701.99
Estimated Instant + Delayed Sensible Load [W] 2631.70
Difference [W] 70.28


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -125.8     -50.5 -176.4 93.66
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   214.73     214.73 -114.0
Other Roof   0.00     0.00 -0.00
Exterior Wall   14.53     14.53 -7.7
Interzone Wall   8.04     8.04 -4.3
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   0.00     0.00 -0.00
Ground Contact Floor   -77.3     -77.3 41.06
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -171.9       -171.9 91.30
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -297.8 159.98 0.00 -50.5 -188.3  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 13.58
Zone Relative Humdity [%] 48.81
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00470
Peak Design Sensible Load [W] -3202.2
Estimated Instant + Delayed Sensible Load [W] -137.8
Difference [W] -3064.4



Table of Contents

Report: Zone Component Load Summary

For: L001_P04

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 535.35 33.95   568.54 1137.84 16.99
Lights 402.06 79.04 0.00   481.10 7.19
Equipment 837.63 56.83   0.00 894.46 13.36
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 28.89     182.38 211.27 3.16
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -259.2     -259.2 -3.9
Other Roof   0.00     0.00 0.00
Exterior Wall   -155.3     -155.3 -2.3
Interzone Wall   -11.3     -11.3 -0.2
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   0.00     0.00 0.00
Ground Contact Floor   474.37     474.37 7.09
Other Floor   0.00     0.00 0.00
Fenestration Conduction 424.37       424.37 6.34
Fenestration Solar   3497.53     3497.53 52.24
Opaque Door   0.00     0.00 0.00
Grand Total 2228.30 3715.96 0.00 750.92 6695.18  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 09:00:00
Outside Dry Bulb Temperature [C] 27.68
Outside Wet Bulb Temperature [C] 23.51
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 25.26
Zone Relative Humdity [%] 45.46
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00911
Peak Design Sensible Load [W] 6767.91
Estimated Instant + Delayed Sensible Load [W] 5944.26
Difference [W] 823.65


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -379.5     -200.4 -580.0 16.80
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   -655.5     -655.5 18.99
Other Roof   0.00     0.00 -0.00
Exterior Wall   -713.0     -713.0 20.66
Interzone Wall   -259.9     -259.9 7.53
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   0.00     0.00 -0.00
Ground Contact Floor   -497.9     -497.9 14.43
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -745.1       -745.1 21.59
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -1124.6 -2126.3 0.00 -200.4 -3451.4  


Heating Peak Conditions

Value
Time of Peak Load 1/21 09:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 18.31
Zone Relative Humdity [%] 45.50
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00594
Peak Design Sensible Load [W] -4946.3
Estimated Instant + Delayed Sensible Load [W] -3250.9
Difference [W] -1695.3



Table of Contents

Report: Zone Component Load Summary

For: L001_P05

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 330.42 21.37   361.54 713.33 12.85
Lights 251.83 52.65 0.00   304.48 5.49
Equipment 524.64 35.52   0.00 560.16 10.09
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 11.32     75.70 87.02 1.57
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -320.6     -320.6 -5.8
Other Roof   0.00     0.00 0.00
Exterior Wall   -128.4     -128.4 -2.3
Interzone Wall   176.43     176.43 3.18
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   0.00     0.00 0.00
Ground Contact Floor   245.75     245.75 4.43
Other Floor   0.00     0.00 0.00
Fenestration Conduction 464.90       464.90 8.38
Fenestration Solar   3446.78     3446.78 62.10
Opaque Door   0.00     0.00 0.00
Grand Total 1583.11 3529.58 0.00 437.24 5549.93  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 09:00:00
Outside Dry Bulb Temperature [C] 27.68
Outside Wet Bulb Temperature [C] 23.51
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 25.45
Zone Relative Humdity [%] 41.43
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00839
Peak Design Sensible Load [W] 5893.26
Estimated Instant + Delayed Sensible Load [W] 5112.69
Difference [W] 780.58


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -127.3     -51.0 -178.3 93.29
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   179.60     179.60 -94.0
Other Roof   0.00     0.00 -0.00
Exterior Wall   25.91     25.91 -13.6
Interzone Wall   73.47     73.47 -38.4
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   0.00     0.00 -0.00
Ground Contact Floor   -54.1     -54.1 28.28
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -237.7       -237.7 124.39
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -365.0 224.92 0.00 -51.0 -191.1  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 12.87
Zone Relative Humdity [%] 46.55
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00427
Peak Design Sensible Load [W] -3189.9
Estimated Instant + Delayed Sensible Load [W] -140.1
Difference [W] -3049.8



Table of Contents

Report: Zone Component Load Summary

For: L001_P06

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 272.59 17.35   297.13 587.06 13.66
Lights 207.36 42.75 0.00   250.11 5.82
Equipment 432.00 28.75   0.00 460.75 10.72
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 9.71     64.08 73.80 1.72
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -252.2     -252.2 -5.9
Other Roof   0.00     0.00 0.00
Exterior Wall   -111.3     -111.3 -2.6
Interzone Wall   128.17     128.17 2.98
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   0.00     0.00 0.00
Ground Contact Floor   306.02     306.02 7.12
Other Floor   0.00     0.00 0.00
Fenestration Conduction 353.16       353.16 8.22
Fenestration Solar   2500.97     2500.97 58.21
Opaque Door   0.00     0.00 0.00
Grand Total 1274.82 2660.43 0.00 361.21 4296.46  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 09:00:00
Outside Dry Bulb Temperature [C] 27.68
Outside Wet Bulb Temperature [C] 23.51
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 25.42
Zone Relative Humdity [%] 41.44
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00838
Peak Design Sensible Load [W] 4584.79
Estimated Instant + Delayed Sensible Load [W] 3935.25
Difference [W] 649.54


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -108.3     -43.2 -151.5 93.63
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   147.21     147.21 -91.0
Other Roof   0.00     0.00 -0.00
Exterior Wall   20.75     20.75 -12.8
Interzone Wall   67.25     67.25 -41.6
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   0.00     0.00 -0.00
Ground Contact Floor   -45.4     -45.4 28.04
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -200.1       -200.1 123.70
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -308.4 189.84 0.00 -43.2 -161.8  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 12.95
Zone Relative Humdity [%] 45.75
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00422
Peak Design Sensible Load [W] -2671.3
Estimated Instant + Delayed Sensible Load [W] -118.6
Difference [W] -2552.7



Table of Contents

Report: Zone Component Load Summary

For: L001_P07

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 334.96 54.92   302.82 692.70 14.90
Lights 233.28 85.32 0.00   318.60 6.85
Equipment 486.00 82.38   0.00 568.38 12.23
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 8.50     74.17 82.67 1.78
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -114.0     -114.0 -2.5
Other Roof   0.00     0.00 0.00
Exterior Wall   -69.2     -69.2 -1.5
Interzone Wall   91.87     91.87 1.98
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   0.00     0.00 0.00
Ground Contact Floor   -70.3     -70.3 -1.5
Other Floor   0.00     0.00 0.00
Fenestration Conduction 216.05       216.05 4.65
Fenestration Solar   2931.44     2931.44 63.07
Opaque Door   0.00     0.00 0.00
Grand Total 1278.79 2992.42 0.00 377.00 4648.21  


Cooling Peak Conditions

Value
Time of Peak Load 9/21 10:00:00
Outside Dry Bulb Temperature [C] 25.81
Outside Wet Bulb Temperature [C] 21.45
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01428
Zone Dry Bulb Temperature [C] 24.25
Zone Relative Humdity [%] 45.44
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00857
Peak Design Sensible Load [W] 4365.45
Estimated Instant + Delayed Sensible Load [W] 4271.22
Difference [W] 94.23


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -158.0     -62.2 -220.3 82.60
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   171.43     171.43 -64.3
Other Roof   0.00     0.00 -0.00
Exterior Wall   46.79     46.79 -17.5
Interzone Wall   49.49     49.49 -18.6
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   0.00     0.00 -0.00
Ground Contact Floor   -45.9     -45.9 17.20
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -268.2       -268.2 100.59
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -426.2 221.83 0.00 -62.2 -266.6  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 12.00
Zone Relative Humdity [%] 45.04
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00390
Peak Design Sensible Load [W] -3216.0
Estimated Instant + Delayed Sensible Load [W] -204.4
Difference [W] -3011.6



Table of Contents

Report: Zone Component Load Summary

For: L001_P08

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 340.92 79.31   296.20 716.43 16.28
Lights 233.28 114.97 0.00   348.25 7.91
Equipment 486.00 113.81   0.00 599.81 13.63
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 18.15     57.60 75.75 1.72
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -67.0     -67.0 -1.5
Other Roof   0.00     0.00 0.00
Exterior Wall   -118.0     -118.0 -2.7
Interzone Wall   -31.9     -31.9 -0.7
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   0.00     0.00 0.00
Ground Contact Floor   -214.8     -214.8 -4.9
Other Floor   0.00     0.00 0.00
Fenestration Conduction 351.78       351.78 7.99
Fenestration Solar   2739.91     2739.91 62.27
Opaque Door   0.00     0.00 0.00
Grand Total 1430.13 2616.35 0.00 353.80 4400.28  


Cooling Peak Conditions

Value
Time of Peak Load 9/21 13:00:00
Outside Dry Bulb Temperature [C] 28.58
Outside Wet Bulb Temperature [C] 22.25
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01428
Zone Dry Bulb Temperature [C] 24.00
Zone Relative Humdity [%] 45.43
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00844
Peak Design Sensible Load [W] 3970.48
Estimated Instant + Delayed Sensible Load [W] 4046.48
Difference [W] -76.0


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -120.8     -47.6 -168.4 96.23
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   160.88     160.88 -91.9
Other Roof   0.00     0.00 -0.00
Exterior Wall   15.85     15.85 -9.1
Interzone Wall   68.79     68.79 -39.3
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   0.00     0.00 -0.00
Ground Contact Floor   -53.7     -53.7 30.67
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -198.4       -198.4 113.39
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -319.2 191.84 0.00 -47.6 -175.0  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 13.17
Zone Relative Humdity [%] 45.32
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00424
Peak Design Sensible Load [W] -2863.8
Estimated Instant + Delayed Sensible Load [W] -127.4
Difference [W] -2736.4



Table of Contents

Report: Zone Component Load Summary

For: L001_P09

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 350.36 64.91   304.46 719.73 16.30
Lights 239.76 104.73 0.00   344.49 7.80
Equipment 499.50 93.13   0.00 592.63 13.42
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 16.42     52.13 68.55 1.55
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -57.9     -57.9 -1.3
Other Roof   0.00     0.00 0.00
Exterior Wall   -80.8     -80.8 -1.8
Interzone Wall   -43.9     -43.9 -1.0
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   0.00     0.00 0.00
Ground Contact Floor   -279.0     -279.0 -6.3
Other Floor   0.00     0.00 0.00
Fenestration Conduction 359.18       359.18 8.13
Fenestration Solar   2793.35     2793.35 63.25
Opaque Door   0.00     0.00 0.00
Grand Total 1465.22 2594.47 0.00 356.59 4416.29  


Cooling Peak Conditions

Value
Time of Peak Load 9/21 13:00:00
Outside Dry Bulb Temperature [C] 28.58
Outside Wet Bulb Temperature [C] 22.25
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01428
Zone Dry Bulb Temperature [C] 24.00
Zone Relative Humdity [%] 45.39
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00843
Peak Design Sensible Load [W] 4011.71
Estimated Instant + Delayed Sensible Load [W] 4059.69
Difference [W] -48.0


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -111.2     -44.1 -155.3 94.88
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   159.62     159.62 -97.5
Other Roof   0.00     0.00 -0.00
Exterior Wall   7.22     7.22 -4.4
Interzone Wall   63.00     63.00 -38.5
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   0.00     0.00 -0.00
Ground Contact Floor   -59.5     -59.5 36.37
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -178.7       -178.7 109.16
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -289.9 170.31 0.00 -44.1 -163.7  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 13.56
Zone Relative Humdity [%] 46.23
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00444
Peak Design Sensible Load [W] -2712.0
Estimated Instant + Delayed Sensible Load [W] -119.6
Difference [W] -2592.4



Table of Contents

Report: Zone Component Load Summary

For: L001_P10

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 394.58 95.14   342.83 832.55 17.77
Lights 270.00 136.19 0.00   406.19 8.67
Equipment 562.50 136.58   0.00 699.08 14.92
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 18.15     57.31 75.46 1.61
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -57.5     -57.5 -1.2
Other Roof   0.00     0.00 0.00
Exterior Wall   -118.4     -118.4 -2.5
Interzone Wall   -19.3     -19.3 -0.4
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   0.00     0.00 0.00
Ground Contact Floor   -235.2     -235.2 -5.0
Other Floor   0.00     0.00 0.00
Fenestration Conduction 356.02       356.02 7.60
Fenestration Solar   2746.57     2746.57 58.62
Opaque Door   0.00     0.00 0.00
Grand Total 1601.26 2684.06 0.00 400.13 4685.45  


Cooling Peak Conditions

Value
Time of Peak Load 9/21 13:00:00
Outside Dry Bulb Temperature [C] 28.58
Outside Wet Bulb Temperature [C] 22.25
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01428
Zone Dry Bulb Temperature [C] 24.00
Zone Relative Humdity [%] 45.57
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00846
Peak Design Sensible Load [W] 4193.21
Estimated Instant + Delayed Sensible Load [W] 4285.31
Difference [W] -92.1


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -122.6     -48.8 -171.4 94.58
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   180.11     180.11 -99.4
Other Roof   0.00     0.00 -0.00
Exterior Wall   9.17     9.17 -5.1
Interzone Wall   70.96     70.96 -39.2
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   0.00     0.00 -0.00
Ground Contact Floor   -66.2     -66.2 36.55
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -203.8       -203.8 112.49
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -326.4 194.00 0.00 -48.8 -181.2  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 13.50
Zone Relative Humdity [%] 46.79
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00448
Peak Design Sensible Load [W] -3032.2
Estimated Instant + Delayed Sensible Load [W] -132.4
Difference [W] -2899.8



Table of Contents

Report: Zone Component Load Summary

For: L001_P11

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 287.40 74.75   249.42 611.57 11.65
Lights 196.56 106.07 0.00   302.63 5.77
Equipment 409.50 106.78   0.00 516.28 9.84
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 24.76     80.34 105.10 2.00
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -177.8     -177.8 -3.4
Other Roof   0.00     0.00 0.00
Exterior Wall   -193.6     -193.6 -3.7
Interzone Wall   -80.6     -80.6 -1.5
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   0.00     0.00 0.00
Ground Contact Floor   259.08     259.08 4.94
Other Floor   0.00     0.00 0.00
Fenestration Conduction 525.69       525.69 10.02
Fenestration Solar   3380.47     3380.47 64.40
Opaque Door   0.00     0.00 0.00
Grand Total 1443.91 3475.18 0.00 329.76 5248.85  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 18:00:00
Outside Dry Bulb Temperature [C] 30.28
Outside Wet Bulb Temperature [C] 24.21
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 23.99
Zone Relative Humdity [%] 44.82
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00832
Peak Design Sensible Load [W] 4845.68
Estimated Instant + Delayed Sensible Load [W] 4919.09
Difference [W] -73.4


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -115.3     -46.7 -162.0 91.65
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   151.39     151.39 -85.6
Other Roof   0.00     0.00 -0.00
Exterior Wall   35.29     35.29 -20.0
Interzone Wall   68.81     68.81 -38.9
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   0.00     0.00 -0.00
Ground Contact Floor   -35.1     -35.1 19.86
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -235.1       -235.1 133.02
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -350.4 220.39 0.00 -46.7 -176.8  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 12.14
Zone Relative Humdity [%] 45.78
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00400
Peak Design Sensible Load [W] -2908.7
Estimated Instant + Delayed Sensible Load [W] -130.0
Difference [W] -2778.7



Table of Contents

Report: Zone Component Load Summary

For: L001_P12

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 224.23 55.80   194.61 474.64 11.57
Lights 153.36 80.72 0.00   234.08 5.71
Equipment 319.50 79.70   0.00 399.20 9.73
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 20.04     65.02 85.06 2.07
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -125.3     -125.3 -3.1
Other Roof   0.00     0.00 0.00
Exterior Wall   -143.9     -143.9 -3.5
Interzone Wall   -66.0     -66.0 -1.6
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   0.00     0.00 0.00
Ground Contact Floor   175.93     175.93 4.29
Other Floor   0.00     0.00 0.00
Fenestration Conduction 416.46       416.46 10.15
Fenestration Solar   2652.05     2652.05 64.65
Opaque Door   0.00     0.00 0.00
Grand Total 1133.59 2708.96 0.00 259.63 4102.18  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 18:00:00
Outside Dry Bulb Temperature [C] 30.28
Outside Wet Bulb Temperature [C] 24.21
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 23.99
Zone Relative Humdity [%] 44.78
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00831
Peak Design Sensible Load [W] 3788.30
Estimated Instant + Delayed Sensible Load [W] 3842.55
Difference [W] -54.3


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -93.8     -38.0 -131.8 92.01
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   117.51     117.51 -82.0
Other Roof   0.00     0.00 -0.00
Exterior Wall   27.27     27.27 -19.0
Interzone Wall   61.09     61.09 -42.6
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   0.00     0.00 -0.00
Ground Contact Floor   -28.3     -28.3 19.73
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -189.1       -189.1 131.99
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -282.9 177.61 0.00 -38.0 -143.2  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 12.26
Zone Relative Humdity [%] 44.74
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00394
Peak Design Sensible Load [W] -2324.7
Estimated Instant + Delayed Sensible Load [W] -105.3
Difference [W] -2219.4



Table of Contents

Report: Zone Component Load Summary

For: L001_P13

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 214.75 41.38   186.39 442.52 11.67
Lights 146.88 67.31 0.00   214.19 5.65
Equipment 306.00 59.08   0.00 365.08 9.63
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 16.51     53.56 70.06 1.85
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -121.7     -121.7 -3.2
Other Roof   0.00     0.00 0.00
Exterior Wall   -99.4     -99.4 -2.6
Interzone Wall   -71.9     -71.9 -1.9
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   0.00     0.00 0.00
Ground Contact Floor   134.18     134.18 3.54
Other Floor   0.00     0.00 0.00
Fenestration Conduction 390.55       390.55 10.30
Fenestration Solar   2468.51     2468.51 65.10
Opaque Door   0.00     0.00 0.00
Grand Total 1074.69 2477.51 0.00 239.95 3792.15  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 18:00:00
Outside Dry Bulb Temperature [C] 30.28
Outside Wet Bulb Temperature [C] 24.21
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 23.99
Zone Relative Humdity [%] 44.73
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00830
Peak Design Sensible Load [W] 3519.88
Estimated Instant + Delayed Sensible Load [W] 3552.20
Difference [W] -32.3


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -79.0     -32.2 -111.2 89.16
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   108.80     108.80 -87.3
Other Roof   0.00     0.00 -0.00
Exterior Wall   16.71     16.71 -13.4
Interzone Wall   61.15     61.15 -49.1
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   0.00     0.00 -0.00
Ground Contact Floor   -30.4     -30.4 24.35
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -169.8       -169.8 136.21
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -248.8 156.30 0.00 -32.2 -124.7  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 12.74
Zone Relative Humdity [%] 45.81
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00417
Peak Design Sensible Load [W] -2061.7
Estimated Instant + Delayed Sensible Load [W] -92.5
Difference [W] -1969.2



Table of Contents

Report: Zone Component Load Summary

For: L001_P14

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 3002.50 254.99   3110.22 6367.71 21.98
Lights 2227.85 526.91 0.00   2754.76 9.51
Equipment 4641.36 441.38   0.00 5082.74 17.54
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 90.66     539.76 630.42 2.18
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -896.8     -896.8 -3.1
Other Roof   0.00     0.00 0.00
Exterior Wall   -75.8     -75.8 -0.3
Interzone Wall   1180.25     1180.25 4.07
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   0.00     0.00 0.00
Ground Contact Floor   1970.38     1970.38 6.80
Other Floor   0.00     0.00 0.00
Fenestration Conduction 1471.46       1471.46 5.08
Fenestration Solar   10485.66     10485.66 36.19
Opaque Door   0.00     0.00 0.00
Grand Total 11433.82 13887.02 0.00 3649.99 28970.83  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 09:00:00
Outside Dry Bulb Temperature [C] 27.68
Outside Wet Bulb Temperature [C] 23.51
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 25.11
Zone Relative Humdity [%] 49.17
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00978
Peak Design Sensible Load [W] 28490.07
Estimated Instant + Delayed Sensible Load [W] 25320.85
Difference [W] 3169.22


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -946.3     -382.2 -1328.5 93.04
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   1525.56     1525.56 -106.8
Other Roof   0.00     0.00 -0.00
Exterior Wall   131.36     131.36 -9.2
Interzone Wall   448.26     448.26 -31.4
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   0.00     0.00 -0.00
Ground Contact Floor   -511.0     -511.0 35.79
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -1693.6       -1693.6 118.61
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -2639.9 1594.17 0.00 -382.2 -1427.9  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 13.15
Zone Relative Humdity [%] 48.93
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00458
Peak Design Sensible Load [W] -24618.8
Estimated Instant + Delayed Sensible Load [W] -1045.7
Difference [W] -23573.1



Table of Contents

Report: Zone Component Load Summary

For: L001_P15

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 391.63 99.73   339.85 831.22 12.34
Lights 267.84 141.60 0.00   409.44 6.08
Equipment 558.00 142.49   0.00 700.49 10.40
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 44.81     144.54 189.35 2.81
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -182.2     -182.2 -2.7
Other Roof   0.00     0.00 0.00
Exterior Wall   -318.2     -318.2 -4.7
Interzone Wall   -394.4     -394.4 -5.9
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   0.00     0.00 0.00
Ground Contact Floor   334.86     334.86 4.97
Other Floor   0.00     0.00 0.00
Fenestration Conduction 683.20       683.20 10.14
Fenestration Solar   4484.53     4484.53 66.55
Opaque Door   0.00     0.00 0.00
Grand Total 1945.49 4308.48 0.00 484.39 6738.37  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 18:00:00
Outside Dry Bulb Temperature [C] 30.28
Outside Wet Bulb Temperature [C] 24.21
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 23.99
Zone Relative Humdity [%] 45.12
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00837
Peak Design Sensible Load [W] 6148.63
Estimated Instant + Delayed Sensible Load [W] 6253.98
Difference [W] -105.3


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -207.2     -80.5 -287.7 96.84
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   187.18     187.18 -63.0
Other Roof   0.00     0.00 -0.00
Exterior Wall   48.47     48.47 -16.3
Interzone Wall   184.17     184.17 -62.0
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   0.00     0.00 -0.00
Ground Contact Floor   -51.5     -51.5 17.33
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -377.7       -377.7 127.16
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -584.9 368.34 0.00 -80.5 -297.0  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 12.00
Zone Relative Humdity [%] 42.38
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00367
Peak Design Sensible Load [W] -4003.0
Estimated Instant + Delayed Sensible Load [W] -216.6
Difference [W] -3786.4



Table of Contents

Report: Zone Component Load Summary

For: L002_P01

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 260.22 12.02   260.87 533.10 26.56
Lights 190.08 30.05 0.00   220.13 10.97
Equipment 396.00 18.94   0.00 414.94 20.67
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 4.90     26.86 31.75 1.58
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   93.51     93.51 4.66
Other Roof   0.00     0.00 0.00
Exterior Wall   40.68     40.68 2.03
Interzone Wall   403.61     403.61 20.11
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   173.62     173.62 8.65
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 8.01       8.01 0.40
Fenestration Solar   87.65     87.65 4.37
Opaque Door   0.00     0.00 0.00
Grand Total 859.20 860.08 0.00 287.73 2007.00  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 09:00:00
Outside Dry Bulb Temperature [C] 27.68
Outside Wet Bulb Temperature [C] 23.51
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 24.91
Zone Relative Humdity [%] 52.39
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.01030
Peak Design Sensible Load [W] 1942.87
Estimated Instant + Delayed Sensible Load [W] 1719.28
Difference [W] 223.59


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -55.8     -22.7 -78.5 87.74
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   93.19     93.19 -104.1
Other Roof   0.00     0.00 -0.00
Exterior Wall   -18.0     -18.0 20.12
Interzone Wall   -110.3     -110.3 123.31
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   92.94     92.94 -103.9
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -68.8       -68.8 76.82
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -124.5 57.78 0.00 -22.7 -89.5  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 16.24
Zone Relative Humdity [%] 46.70
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00534
Peak Design Sensible Load [W] -1378.5
Estimated Instant + Delayed Sensible Load [W] -66.8
Difference [W] -1311.7



Table of Contents

Report: Zone Component Load Summary

For: L002_P02

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 492.55 23.68   502.72 1018.95 24.06
Lights 362.88 57.76 0.00   420.64 9.93
Equipment 756.00 38.15   0.00 794.15 18.75
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 13.14     75.88 89.02 2.10
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   39.40     39.40 0.93
Other Roof   0.00     0.00 0.00
Exterior Wall   47.54     47.54 1.12
Interzone Wall   333.60     333.60 7.88
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   421.43     421.43 9.95
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 165.05       165.05 3.90
Fenestration Solar   905.63     905.63 21.38
Opaque Door   0.00     0.00 0.00
Grand Total 1789.63 1867.20 0.00 578.60 4235.42  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 09:00:00
Outside Dry Bulb Temperature [C] 27.68
Outside Wet Bulb Temperature [C] 23.51
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 25.02
Zone Relative Humdity [%] 50.71
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.01004
Peak Design Sensible Load [W] 4103.76
Estimated Instant + Delayed Sensible Load [W] 3656.82
Difference [W] 446.94


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -153.2     -54.9 -208.0 127.39
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   144.68     144.68 -88.6
Other Roof   0.00     0.00 -0.00
Exterior Wall   -61.2     -61.2 37.49
Interzone Wall   53.72     53.72 -32.9
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   143.84     143.84 -88.1
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -236.3       -236.3 144.70
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -389.5 281.03 0.00 -54.9 -163.3  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 16.19
Zone Relative Humdity [%] 41.29
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00470
Peak Design Sensible Load [W] -2521.7
Estimated Instant + Delayed Sensible Load [W] -108.5
Difference [W] -2413.2



Table of Contents

Report: Zone Component Load Summary

For: L002_P03

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 452.60 61.24   408.74 922.57 26.17
Lights 315.06 95.48 0.00   410.54 11.65
Equipment 656.37 93.68   0.00 750.05 21.28
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 20.56     81.00 101.56 2.88
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   242.28     242.28 6.87
Other Roof   0.00     0.00 0.00
Exterior Wall   103.48     103.48 2.94
Interzone Wall   391.16     391.16 11.10
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   222.47     222.47 6.31
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 66.77       66.77 1.89
Fenestration Solar   313.97     313.97 8.91
Opaque Door   0.00     0.00 0.00
Grand Total 1511.36 1523.76 0.00 489.74 3524.85  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 10:00:00
Outside Dry Bulb Temperature [C] 29.11
Outside Wet Bulb Temperature [C] 23.89
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 24.25
Zone Relative Humdity [%] 47.87
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00903
Peak Design Sensible Load [W] 3145.19
Estimated Instant + Delayed Sensible Load [W] 3035.12
Difference [W] 110.08


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -145.3     -52.6 -197.9 116.70
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   155.18     155.18 -91.5
Other Roof   0.00     0.00 -0.00
Exterior Wall   -37.2     -37.2 21.95
Interzone Wall   -45.2     -45.2 26.65
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   154.18     154.18 -90.9
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -198.7       -198.7 117.17
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -343.9 226.97 0.00 -52.6 -169.5  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 15.43
Zone Relative Humdity [%] 41.78
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00453
Peak Design Sensible Load [W] -2547.2
Estimated Instant + Delayed Sensible Load [W] -117.0
Difference [W] -2430.3



Table of Contents

Report: Zone Component Load Summary

For: L002_P04

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 569.45 89.54   530.65 1189.64 16.54
Lights 402.06 133.90 0.00   535.97 7.45
Equipment 837.63 139.94   0.00 977.57 13.59
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 50.79     206.88 257.67 3.58
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   182.50     182.50 2.54
Other Roof   0.00     0.00 0.00
Exterior Wall   106.53     106.53 1.48
Interzone Wall   -6.3     -6.3 -0.1
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   341.19     341.19 4.74
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 402.03       402.03 5.59
Fenestration Solar   3207.21     3207.21 44.58
Opaque Door   0.00     0.00 0.00
Grand Total 2261.96 4194.52 0.00 737.53 7194.01  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 10:00:00
Outside Dry Bulb Temperature [C] 29.11
Outside Wet Bulb Temperature [C] 23.89
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 24.45
Zone Relative Humdity [%] 43.82
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00836
Peak Design Sensible Load [W] 6757.02
Estimated Instant + Delayed Sensible Load [W] 6456.48
Difference [W] 300.54


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -335.7     -119.1 -454.8 126.37
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   237.85     237.85 -66.1
Other Roof   0.00     0.00 -0.00
Exterior Wall   -2.7     -2.7 0.75
Interzone Wall   135.17     135.17 -37.6
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   235.18     235.18 -65.3
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -510.6       -510.6 141.88
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -846.3 605.51 0.00 -119.1 -359.9  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 13.13
Zone Relative Humdity [%] 38.12
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00356
Peak Design Sensible Load [W] -5131.6
Estimated Instant + Delayed Sensible Load [W] -240.8
Difference [W] -4890.8



Table of Contents

Report: Zone Component Load Summary

For: L002_P05

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 332.29 18.69   359.46 710.44 13.31
Lights 251.83 45.06 0.00   296.89 5.56
Equipment 524.64 31.24   0.00 555.88 10.42
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 12.22     81.04 93.26 1.75
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -161.3     -161.3 -3.0
Other Roof   0.00     0.00 0.00
Exterior Wall   -61.1     -61.1 -1.1
Interzone Wall   261.06     261.06 4.89
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   236.18     236.18 4.43
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 465.85       465.85 8.73
Fenestration Solar   2940.07     2940.07 55.09
Opaque Door   0.00     0.00 0.00
Grand Total 1586.83 3309.87 0.00 440.49 5337.20  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 09:00:00
Outside Dry Bulb Temperature [C] 27.68
Outside Wet Bulb Temperature [C] 23.51
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 25.38
Zone Relative Humdity [%] 42.38
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00855
Peak Design Sensible Load [W] 5603.95
Estimated Instant + Delayed Sensible Load [W] 4896.71
Difference [W] 707.24


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -146.9     -53.4 -200.4 115.85
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   134.36     134.36 -77.7
Other Roof   0.00     0.00 -0.00
Exterior Wall   -20.7     -20.7 11.95
Interzone Wall   55.91     55.91 -32.3
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   133.37     133.37 -77.1
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -275.5       -275.5 159.32
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -422.5 302.97 0.00 -53.4 -173.0  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 14.62
Zone Relative Humdity [%] 40.05
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00412
Peak Design Sensible Load [W] -2626.6
Estimated Instant + Delayed Sensible Load [W] -119.5
Difference [W] -2507.1



Table of Contents

Report: Zone Component Load Summary

For: L002_P06

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 273.85 15.20   295.72 584.77 13.94
Lights 207.36 36.70 0.00   244.06 5.82
Equipment 432.00 25.24   0.00 457.24 10.90
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration -0.6     52.40 51.80 1.23
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -140.7     -140.7 -3.4
Other Roof   0.00     0.00 0.00
Exterior Wall   -87.8     -87.8 -2.1
Interzone Wall   203.66     203.66 4.85
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   261.44     261.44 6.23
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 308.98       308.98 7.36
Fenestration Solar   2312.17     2312.17 55.11
Opaque Door   0.00     0.00 0.00
Grand Total 1221.59 2625.90 0.00 348.12 4195.61  


Cooling Peak Conditions

Value
Time of Peak Load 6/21 09:00:00
Outside Dry Bulb Temperature [C] 24.38
Outside Wet Bulb Temperature [C] 21.03
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01428
Zone Dry Bulb Temperature [C] 25.37
Zone Relative Humdity [%] 41.73
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00841
Peak Design Sensible Load [W] 4446.66
Estimated Instant + Delayed Sensible Load [W] 3847.49
Difference [W] 599.17


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -124.7     -45.3 -170.0 116.12
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   110.47     110.47 -75.5
Other Roof   0.00     0.00 -0.00
Exterior Wall   -17.9     -17.9 12.20
Interzone Wall   51.31     51.31 -35.0
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   109.66     109.66 -74.9
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -230.0       -230.0 157.09
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -354.7 253.59 0.00 -45.3 -146.4  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 14.68
Zone Relative Humdity [%] 39.44
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00407
Peak Design Sensible Load [W] -2201.0
Estimated Instant + Delayed Sensible Load [W] -101.1
Difference [W] -2099.9



Table of Contents

Report: Zone Component Load Summary

For: L002_P07

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 340.57 80.50   296.59 717.66 14.59
Lights 233.28 113.33 0.00   346.61 7.05
Equipment 486.00 116.78   0.00 602.78 12.25
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 26.91     86.33 113.24 2.30
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   76.24     76.24 1.55
Other Roof   0.00     0.00 0.00
Exterior Wall   -91.7     -91.7 -1.9
Interzone Wall   6.62     6.62 0.13
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   -152.0     -152.0 -3.1
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 334.36       334.36 6.80
Fenestration Solar   2965.02     2965.02 60.28
Opaque Door   0.00     0.00 0.00
Grand Total 1421.12 3114.72 0.00 382.92 4918.77  


Cooling Peak Conditions

Value
Time of Peak Load 9/21 13:00:00
Outside Dry Bulb Temperature [C] 28.58
Outside Wet Bulb Temperature [C] 22.25
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01428
Zone Dry Bulb Temperature [C] 24.02
Zone Relative Humdity [%] 45.28
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00842
Peak Design Sensible Load [W] 4465.84
Estimated Instant + Delayed Sensible Load [W] 4535.84
Difference [W] -70.0


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -180.6     -65.9 -246.5 116.58
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   144.07     144.07 -68.1
Other Roof   0.00     0.00 -0.00
Exterior Wall   0.93     0.93 -0.4
Interzone Wall   49.84     49.84 -23.6
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   142.72     142.72 -67.5
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -302.5       -302.5 143.07
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -483.1 337.55 0.00 -65.9 -211.4  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 13.40
Zone Relative Humdity [%] 38.56
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00366
Peak Design Sensible Load [W] -3059.7
Estimated Instant + Delayed Sensible Load [W] -145.5
Difference [W] -2914.2



Table of Contents

Report: Zone Component Load Summary

For: L002_P08

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 340.82 75.31   296.31 712.45 16.25
Lights 233.28 109.52 0.00   342.80 7.82
Equipment 486.00 108.81   0.00 594.81 13.57
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 19.51     62.19 81.71 1.86
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   1.03     1.03 0.02
Other Roof   0.00     0.00 0.00
Exterior Wall   -82.8     -82.8 -1.9
Interzone Wall   -10.1     -10.1 -0.2
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   -23.5     -23.5 -0.5
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 350.54       350.54 8.00
Fenestration Solar   2417.46     2417.46 55.14
Opaque Door   0.00     0.00 0.00
Grand Total 1430.15 2595.76 0.00 358.51 4384.41  


Cooling Peak Conditions

Value
Time of Peak Load 9/21 13:00:00
Outside Dry Bulb Temperature [C] 28.58
Outside Wet Bulb Temperature [C] 22.25
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01428
Zone Dry Bulb Temperature [C] 24.00
Zone Relative Humdity [%] 45.49
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00845
Peak Design Sensible Load [W] 3958.19
Estimated Instant + Delayed Sensible Load [W] 4025.91
Difference [W] -67.7


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -139.2     -49.6 -188.8 120.42
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   118.98     118.98 -75.9
Other Roof   0.00     0.00 -0.00
Exterior Wall   -29.5     -29.5 18.83
Interzone Wall   51.71     51.71 -33.0
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   118.13     118.13 -75.3
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -227.3       -227.3 144.97
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -366.5 259.30 0.00 -49.6 -156.8  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 14.91
Zone Relative Humdity [%] 39.01
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00409
Peak Design Sensible Load [W] -2330.5
Estimated Instant + Delayed Sensible Load [W] -107.2
Difference [W] -2223.3



Table of Contents

Report: Zone Component Load Summary

For: L002_P09

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 350.25 61.76   304.58 716.59 16.16
Lights 239.76 99.74 0.00   339.50 7.66
Equipment 499.50 89.19   0.00 588.69 13.28
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 17.65     56.32 73.97 1.67
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   0.70     0.70 0.02
Other Roof   0.00     0.00 0.00
Exterior Wall   -53.8     -53.8 -1.2
Interzone Wall   -24.0     -24.0 -0.5
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   -64.9     -64.9 -1.5
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 356.68       356.68 8.04
Fenestration Solar   2500.12     2500.12 56.39
Opaque Door   0.00     0.00 0.00
Grand Total 1463.84 2608.81 0.00 360.90 4433.55  


Cooling Peak Conditions

Value
Time of Peak Load 9/21 13:00:00
Outside Dry Bulb Temperature [C] 28.58
Outside Wet Bulb Temperature [C] 22.25
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01428
Zone Dry Bulb Temperature [C] 24.01
Zone Relative Humdity [%] 45.43
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00844
Peak Design Sensible Load [W] 4030.72
Estimated Instant + Delayed Sensible Load [W] 4072.65
Difference [W] -41.9


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -128.3     -45.7 -174.0 121.71
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   113.66     113.66 -79.5
Other Roof   0.00     0.00 -0.00
Exterior Wall   -36.6     -36.6 25.61
Interzone Wall   45.87     45.87 -32.1
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   112.92     112.92 -79.0
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -204.8       -204.8 143.30
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -333.1 235.85 0.00 -45.7 -142.9  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 15.39
Zone Relative Humdity [%] 39.59
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00428
Peak Design Sensible Load [W] -2146.0
Estimated Instant + Delayed Sensible Load [W] -97.3
Difference [W] -2048.7



Table of Contents

Report: Zone Component Load Summary

For: L002_P10

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 394.46 90.18   342.96 827.60 17.61
Lights 270.00 129.49 0.00   399.49 8.50
Equipment 562.50 130.38   0.00 692.88 14.74
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 19.51     61.92 81.43 1.73
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   16.47     16.47 0.35
Other Roof   0.00     0.00 0.00
Exterior Wall   -85.3     -85.3 -1.8
Interzone Wall   0.41     0.41 0.01
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   -12.0     -12.0 -0.3
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 354.66       354.66 7.55
Fenestration Solar   2423.95     2423.95 51.58
Opaque Door   0.00     0.00 0.00
Grand Total 1601.13 2693.63 0.00 404.88 4699.64  


Cooling Peak Conditions

Value
Time of Peak Load 9/21 13:00:00
Outside Dry Bulb Temperature [C] 28.58
Outside Wet Bulb Temperature [C] 22.25
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01428
Zone Dry Bulb Temperature [C] 24.00
Zone Relative Humdity [%] 45.61
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00847
Peak Design Sensible Load [W] 4212.74
Estimated Instant + Delayed Sensible Load [W] 4294.76
Difference [W] -82.0


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -141.5     -50.6 -192.1 121.33
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   128.26     128.26 -81.0
Other Roof   0.00     0.00 -0.00
Exterior Wall   -38.9     -38.9 24.54
Interzone Wall   51.06     51.06 -32.2
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   127.41     127.41 -80.5
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -234.1       -234.1 147.84
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -375.6 267.87 0.00 -50.6 -158.3  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 15.34
Zone Relative Humdity [%] 40.02
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00431
Peak Design Sensible Load [W] -2398.5
Estimated Instant + Delayed Sensible Load [W] -107.8
Difference [W] -2290.8



Table of Contents

Report: Zone Component Load Summary

For: L002_P11

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 287.39 74.50   249.42 611.32 12.30
Lights 196.56 106.19 0.00   302.75 6.09
Equipment 409.50 106.54   0.00 516.04 10.39
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 26.20     85.05 111.25 2.24
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -110.8     -110.8 -2.2
Other Roof   0.00     0.00 0.00
Exterior Wall   -156.5     -156.5 -3.2
Interzone Wall   -50.1     -50.1 -1.0
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   227.67     227.67 4.58
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 529.62       529.62 10.66
Fenestration Solar   2987.70     2987.70 60.13
Opaque Door   0.00     0.00 0.00
Grand Total 1449.27 3185.11 0.00 334.48 4968.86  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 18:00:00
Outside Dry Bulb Temperature [C] 30.28
Outside Wet Bulb Temperature [C] 24.21
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 23.99
Zone Relative Humdity [%] 45.02
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00836
Peak Design Sensible Load [W] 4563.68
Estimated Instant + Delayed Sensible Load [W] 4634.39
Difference [W] -70.7


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -133.0     -49.5 -182.5 110.56
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   118.73     118.73 -71.9
Other Roof   0.00     0.00 -0.00
Exterior Wall   -3.6     -3.6 2.20
Interzone Wall   54.92     54.92 -33.3
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   117.76     117.76 -71.3
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -270.3       -270.3 163.77
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -403.4 287.78 0.00 -49.5 -165.1  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 13.80
Zone Relative Humdity [%] 39.63
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00386
Peak Design Sensible Load [W] -2477.0
Estimated Instant + Delayed Sensible Load [W] -115.6
Difference [W] -2361.4



Table of Contents

Report: Zone Component Load Summary

For: L002_P12

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 224.22 55.63   194.61 474.47 12.12
Lights 153.36 80.84 0.00   234.20 5.98
Equipment 319.50 79.55   0.00 399.05 10.20
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 21.21     68.85 90.06 2.30
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -80.5     -80.5 -2.1
Other Roof   0.00     0.00 0.00
Exterior Wall   -118.5     -118.5 -3.0
Interzone Wall   -42.2     -42.2 -1.1
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   169.57     169.57 4.33
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 416.45       416.45 10.64
Fenestration Solar   2370.44     2370.44 60.58
Opaque Door   0.00     0.00 0.00
Grand Total 1134.74 2514.96 0.00 263.47 3913.17  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 18:00:00
Outside Dry Bulb Temperature [C] 30.28
Outside Wet Bulb Temperature [C] 24.21
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 23.99
Zone Relative Humdity [%] 44.97
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00835
Peak Design Sensible Load [W] 3597.18
Estimated Instant + Delayed Sensible Load [W] 3649.70
Difference [W] -52.5


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -108.0     -40.2 -148.2 110.62
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   92.67     92.67 -69.2
Other Roof   0.00     0.00 -0.00
Exterior Wall   -3.5     -3.5 2.61
Interzone Wall   49.01     49.01 -36.6
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   91.92     91.92 -68.6
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -215.9       -215.9 161.18
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -323.9 230.10 0.00 -40.2 -133.9  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 13.87
Zone Relative Humdity [%] 38.89
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00381
Peak Design Sensible Load [W] -1985.7
Estimated Instant + Delayed Sensible Load [W] -93.7
Difference [W] -1891.9



Table of Contents

Report: Zone Component Load Summary

For: L002_P13

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 3001.64 225.28   3111.17 6338.10 20.83
Lights 2227.85 454.95 0.00   2682.80 8.82
Equipment 4641.36 397.73   0.00 5039.08 16.56
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 95.91     579.67 675.58 2.22
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   335.94     335.94 1.10
Other Roof   0.00     0.00 0.00
Exterior Wall   353.46     353.46 1.16
Interzone Wall   1696.12     1696.12 5.57
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   2612.88     2612.88 8.59
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 1485.35       1485.35 4.88
Fenestration Solar   9214.00     9214.00 30.28
Opaque Door   0.00     0.00 0.00
Grand Total 11452.10 15290.35 0.00 3690.85 30433.29  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 09:00:00
Outside Dry Bulb Temperature [C] 27.68
Outside Wet Bulb Temperature [C] 23.51
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 25.11
Zone Relative Humdity [%] 46.88
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00932
Peak Design Sensible Load [W] 29969.54
Estimated Instant + Delayed Sensible Load [W] 26742.45
Difference [W] 3227.09


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -1097.6     -398.1 -1495.7 119.57
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   1081.32     1081.32 -86.4
Other Roof   0.00     0.00 -0.00
Exterior Wall   -252.9     -252.9 20.21
Interzone Wall   323.15     323.15 -25.8
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   1073.71     1073.71 -85.8
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -1980.5       -1980.5 158.32
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -3078.2 2225.31 0.00 -398.1 -1250.9  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 15.07
Zone Relative Humdity [%] 41.65
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00441
Peak Design Sensible Load [W] -19525.7
Estimated Instant + Delayed Sensible Load [W] -852.9
Difference [W] -18672.8



Table of Contents

Report: Zone Component Load Summary

For: L002_P14

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 214.75 41.33   186.39 442.47 12.15
Lights 146.88 67.53 0.00   214.41 5.89
Equipment 306.00 59.08   0.00 365.08 10.02
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 17.46     56.74 74.20 2.04
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -81.8     -81.8 -2.2
Other Roof   0.00     0.00 0.00
Exterior Wall   -80.3     -80.3 -2.2
Interzone Wall   -47.4     -47.4 -1.3
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   136.14     136.14 3.74
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 389.03       389.03 10.68
Fenestration Solar   2230.04     2230.04 61.23
Opaque Door   0.00     0.00 0.00
Grand Total 1074.12 2324.65 0.00 243.13 3641.90  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 18:00:00
Outside Dry Bulb Temperature [C] 30.28
Outside Wet Bulb Temperature [C] 24.21
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 23.99
Zone Relative Humdity [%] 44.90
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00834
Peak Design Sensible Load [W] 3367.47
Estimated Instant + Delayed Sensible Load [W] 3398.77
Difference [W] -31.3


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -90.9     -33.9 -124.8 109.38
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   83.36     83.36 -73.1
Other Roof   0.00     0.00 -0.00
Exterior Wall   -9.2     -9.2 8.06
Interzone Wall   47.63     47.63 -41.8
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   82.76     82.76 -72.6
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -193.9       -193.9 169.97
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -284.8 204.56 0.00 -33.9 -114.1  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 14.40
Zone Relative Humdity [%] 39.66
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00402
Peak Design Sensible Load [W] -1726.5
Estimated Instant + Delayed Sensible Load [W] -80.2
Difference [W] -1646.3



Table of Contents

Report: Zone Component Load Summary

For: L002_P15

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 391.63 98.89   339.86 830.38 12.88
Lights 267.84 141.08 0.00   408.92 6.34
Equipment 558.00 141.47   0.00 699.47 10.85
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 47.41     152.99 200.40 3.11
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   0.00     0.00 0.00
Interzone Ceiling   -96.3     -96.3 -1.5
Other Roof   0.00     0.00 0.00
Exterior Wall   -251.1     -251.1 -3.9
Interzone Wall   -332.7     -332.7 -5.2
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   329.65     329.65 5.11
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 691.53       691.53 10.72
Fenestration Solar   3968.26     3968.26 61.54
Opaque Door   0.00     0.00 0.00
Grand Total 1956.41 3999.26 0.00 492.85 6448.51  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 18:00:00
Outside Dry Bulb Temperature [C] 30.28
Outside Wet Bulb Temperature [C] 24.21
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 23.99
Zone Relative Humdity [%] 45.29
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00841
Peak Design Sensible Load [W] 5854.28
Estimated Instant + Delayed Sensible Load [W] 5955.66
Difference [W] -101.4


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -237.5     -84.9 -322.3 127.71
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   0.00     0.00 -0.00
Interzone Ceiling   151.55     151.55 -60.0
Other Roof   0.00     0.00 -0.00
Exterior Wall   -14.5     -14.5 5.73
Interzone Wall   210.03     210.03 -83.2
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   149.82     149.82 -59.4
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -427.0       -427.0 169.18
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -664.5 496.93 0.00 -84.9 -252.4  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 13.48
Zone Relative Humdity [%] 36.65
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00350
Peak Design Sensible Load [W] -3586.8
Estimated Instant + Delayed Sensible Load [W] -167.5
Difference [W] -3419.3



Table of Contents

Report: Zone Component Load Summary

For: L003_P01

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 260.17 11.92   260.93 533.01 26.53
Lights 190.08 30.42 0.00   220.50 10.97
Equipment 396.00 18.83   0.00 414.83 20.65
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 5.03     28.08 33.11 1.65
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   65.13     65.13 3.24
Interzone Ceiling   0.00     0.00 0.00
Other Roof   0.00     0.00 0.00
Exterior Wall   45.63     45.63 2.27
Interzone Wall   407.65     407.65 20.29
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   186.29     186.29 9.27
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 8.34       8.34 0.42
Fenestration Solar   94.74     94.74 4.72
Opaque Door   0.00     0.00 0.00
Grand Total 859.62 860.61 0.00 289.00 2009.23  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 09:00:00
Outside Dry Bulb Temperature [C] 27.68
Outside Wet Bulb Temperature [C] 23.51
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 24.91
Zone Relative Humdity [%] 50.58
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00994
Peak Design Sensible Load [W] 1945.09
Estimated Instant + Delayed Sensible Load [W] 1720.23
Difference [W] 224.86


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -63.1     -34.4 -97.5 6.40
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   -487.3     -487.3 31.99
Interzone Ceiling   0.00     0.00 -0.00
Other Roof   0.00     0.00 -0.00
Exterior Wall   -91.1     -91.1 5.98
Interzone Wall   -697.4     -697.4 45.78
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   -63.5     -63.5 4.17
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -86.5       -86.5 5.68
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -149.6 -1339.3 0.00 -34.4 -1523.3  


Heating Peak Conditions

Value
Time of Peak Load 1/21 09:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 19.16
Zone Relative Humdity [%] 48.12
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00663
Peak Design Sensible Load [W] -2106.8
Estimated Instant + Delayed Sensible Load [W] -1488.9
Difference [W] -617.9



Table of Contents

Report: Zone Component Load Summary

For: L003_P02

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 490.99 23.93   504.46 1019.37 21.95
Lights 362.88 59.91 0.00   422.79 9.10
Equipment 756.00 38.79   0.00 794.79 17.11
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 13.36     79.71 93.07 2.00
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   82.37     82.37 1.77
Interzone Ceiling   0.00     0.00 0.00
Other Roof   0.00     0.00 0.00
Exterior Wall   54.26     54.26 1.17
Interzone Wall   339.99     339.99 7.32
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   324.09     324.09 6.98
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 204.48       204.48 4.40
Fenestration Solar   1309.41     1309.41 28.19
Opaque Door   0.00     0.00 0.00
Grand Total 1827.71 2232.74 0.00 584.17 4644.62  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 09:00:00
Outside Dry Bulb Temperature [C] 27.68
Outside Wet Bulb Temperature [C] 23.51
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 25.06
Zone Relative Humdity [%] 48.62
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00964
Peak Design Sensible Load [W] 4559.31
Estimated Instant + Delayed Sensible Load [W] 4060.45
Difference [W] 498.86


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -143.2     -57.7 -200.9 90.49
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   -155.6     -155.6 70.09
Interzone Ceiling   0.00     0.00 -0.00
Other Roof   0.00     0.00 -0.00
Exterior Wall   15.40     15.40 -6.9
Interzone Wall   65.19     65.19 -29.4
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   251.11     251.11 -113.1
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -197.2       -197.2 88.80
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -340.4 176.06 0.00 -57.7 -222.0  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 13.58
Zone Relative Humdity [%] 49.41
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00475
Peak Design Sensible Load [W] -3629.5
Estimated Instant + Delayed Sensible Load [W] -164.4
Difference [W] -3465.1



Table of Contents

Report: Zone Component Load Summary

For: L003_P03

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 429.19 22.54   434.74 886.48 24.71
Lights 315.06 52.99 0.00   368.05 10.26
Equipment 656.37 37.36   0.00 693.73 19.34
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 13.32     75.62 88.94 2.48
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   94.55     94.55 2.64
Interzone Ceiling   0.00     0.00 0.00
Other Roof   0.00     0.00 0.00
Exterior Wall   78.40     78.40 2.19
Interzone Wall   507.84     507.84 14.16
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   307.54     307.54 8.57
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 68.59       68.59 1.91
Fenestration Solar   493.28     493.28 13.75
Opaque Door   0.00     0.00 0.00
Grand Total 1482.53 1594.51 0.00 510.36 3587.40  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 09:00:00
Outside Dry Bulb Temperature [C] 27.68
Outside Wet Bulb Temperature [C] 23.51
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 24.97
Zone Relative Humdity [%] 51.77
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.01022
Peak Design Sensible Load [W] 3426.59
Estimated Instant + Delayed Sensible Load [W] 3077.03
Difference [W] 349.56


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -167.5     -88.6 -256.1 10.37
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   -882.4     -882.4 35.72
Interzone Ceiling   0.00     0.00 -0.00
Other Roof   0.00     0.00 -0.00
Exterior Wall   -254.9     -254.9 10.32
Interzone Wall   -655.4     -655.4 26.53
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   -160.2     -160.2 6.49
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -261.1       -261.1 10.57
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -428.6 -1952.8 0.00 -88.6 -2470.0  


Heating Peak Conditions

Value
Time of Peak Load 1/21 09:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 18.82
Zone Relative Humdity [%] 45.56
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00614
Peak Design Sensible Load [W] -3418.3
Estimated Instant + Delayed Sensible Load [W] -2381.4
Difference [W] -1036.9



Table of Contents

Report: Zone Component Load Summary

For: L003_P04

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 570.05 93.28   529.98 1193.32 16.92
Lights 402.06 142.40 0.00   544.46 7.72
Equipment 837.63 145.36   0.00 982.99 13.94
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 16.91     153.88 170.79 2.42
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   188.28     188.28 2.67
Interzone Ceiling   0.00     0.00 0.00
Other Roof   0.00     0.00 0.00
Exterior Wall   -48.4     -48.4 -0.7
Interzone Wall   -33.1     -33.1 -0.5
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   134.91     134.91 1.91
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 297.61       297.61 4.22
Fenestration Solar   3622.84     3622.84 51.36
Opaque Door   0.00     0.00 0.00
Grand Total 2124.26 4245.52 0.00 683.87 7053.65  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 10:00:00
Outside Dry Bulb Temperature [C] 25.81
Outside Wet Bulb Temperature [C] 21.45
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01428
Zone Dry Bulb Temperature [C] 24.43
Zone Relative Humdity [%] 43.94
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00837
Peak Design Sensible Load [W] 6665.08
Estimated Instant + Delayed Sensible Load [W] 6369.78
Difference [W] 295.29


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -415.8     -223.9 -639.7 15.53
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   -1304.9     -1304.9 31.69
Interzone Ceiling   0.00     0.00 -0.00
Other Roof   0.00     0.00 -0.00
Exterior Wall   -769.6     -769.6 18.69
Interzone Wall   -315.6     -315.6 7.66
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   -343.0     -343.0 8.33
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -745.5       -745.5 18.10
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -1161.3 -2733.2 0.00 -223.9 -4118.5  


Heating Peak Conditions

Value
Time of Peak Load 1/21 09:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 18.26
Zone Relative Humdity [%] 47.33
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00616
Peak Design Sensible Load [W] -5691.4
Estimated Instant + Delayed Sensible Load [W] -3894.5
Difference [W] -1796.9



Table of Contents

Report: Zone Component Load Summary

For: L003_P05

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 331.46 18.71   360.38 710.55 12.74
Lights 251.83 46.02 0.00   297.85 5.34
Equipment 524.64 31.42   0.00 556.07 9.97
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 12.46     83.88 96.34 1.73
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   -18.3     -18.3 -0.3
Interzone Ceiling   0.00     0.00 0.00
Other Roof   0.00     0.00 0.00
Exterior Wall   -66.8     -66.8 -1.2
Interzone Wall   261.27     261.27 4.68
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   95.14     95.14 1.71
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 455.01       455.01 8.16
Fenestration Solar   3192.28     3192.28 57.22
Opaque Door   0.00     0.00 0.00
Grand Total 1575.42 3559.74 0.00 444.26 5579.41  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 09:00:00
Outside Dry Bulb Temperature [C] 27.68
Outside Wet Bulb Temperature [C] 23.51
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 25.41
Zone Relative Humdity [%] 41.86
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00846
Peak Design Sensible Load [W] 5876.55
Estimated Instant + Delayed Sensible Load [W] 5135.15
Difference [W] 741.40


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -139.0     -55.5 -194.5 92.08
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   -90.3     -90.3 42.73
Interzone Ceiling   0.00     0.00 -0.00
Other Roof   0.00     0.00 -0.00
Exterior Wall   37.55     37.55 -17.8
Interzone Wall   79.65     79.65 -37.7
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   191.80     191.80 -90.8
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -235.5       -235.5 111.47
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -374.5 218.74 0.00 -55.5 -211.2  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 12.42
Zone Relative Humdity [%] 46.41
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00413
Peak Design Sensible Load [W] -3373.0
Estimated Instant + Delayed Sensible Load [W] -155.8
Difference [W] -3217.2



Table of Contents

Report: Zone Component Load Summary

For: L003_P06

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 273.34 15.31   296.29 584.94 12.82
Lights 207.36 37.76 0.00   245.12 5.37
Equipment 432.00 25.63   0.00 457.63 10.03
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 10.63     71.11 81.74 1.79
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   -16.0     -16.0 -0.3
Interzone Ceiling   0.00     0.00 0.00
Other Roof   0.00     0.00 0.00
Exterior Wall   -52.7     -52.7 -1.2
Interzone Wall   234.27     234.27 5.14
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   97.77     97.77 2.14
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 368.02       368.02 8.07
Fenestration Solar   2561.27     2561.27 56.14
Opaque Door   0.00     0.00 0.00
Grand Total 1291.34 2903.38 0.00 367.40 4562.12  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 09:00:00
Outside Dry Bulb Temperature [C] 27.68
Outside Wet Bulb Temperature [C] 23.51
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 25.39
Zone Relative Humdity [%] 42.00
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00848
Peak Design Sensible Load [W] 4816.46
Estimated Instant + Delayed Sensible Load [W] 4194.72
Difference [W] 621.74


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -118.4     -47.0 -165.4 92.66
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   -75.7     -75.7 42.43
Interzone Ceiling   0.00     0.00 -0.00
Other Roof   0.00     0.00 -0.00
Exterior Wall   30.98     30.98 -17.4
Interzone Wall   72.74     72.74 -40.7
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   156.92     156.92 -87.9
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -198.0       -198.0 110.92
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -316.4 184.90 0.00 -47.0 -178.5  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 12.54
Zone Relative Humdity [%] 45.50
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00408
Peak Design Sensible Load [W] -2816.4
Estimated Instant + Delayed Sensible Load [W] -131.5
Difference [W] -2684.9



Table of Contents

Report: Zone Component Load Summary

For: L003_P07

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 340.62 85.55   296.53 722.70 14.63
Lights 233.28 120.63 0.00   353.91 7.16
Equipment 486.00 123.64   0.00 609.64 12.34
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 27.89     89.83 117.72 2.38
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   19.05     19.05 0.39
Interzone Ceiling   0.00     0.00 0.00
Other Roof   0.00     0.00 0.00
Exterior Wall   -107.5     -107.5 -2.2
Interzone Wall   2.58     2.58 0.05
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   -265.7     -265.7 -5.4
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 338.17       338.17 6.85
Fenestration Solar   3149.08     3149.08 63.75
Opaque Door   0.00     0.00 0.00
Grand Total 1425.96 3127.34 0.00 386.36 4939.66  


Cooling Peak Conditions

Value
Time of Peak Load 9/21 13:00:00
Outside Dry Bulb Temperature [C] 28.58
Outside Wet Bulb Temperature [C] 22.25
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01428
Zone Dry Bulb Temperature [C] 24.01
Zone Relative Humdity [%] 45.30
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00842
Peak Design Sensible Load [W] 4476.69
Estimated Instant + Delayed Sensible Load [W] 4553.30
Difference [W] -76.6


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -221.5     -121.1 -342.6 13.50
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   -739.3     -739.3 29.14
Interzone Ceiling   0.00     0.00 -0.00
Other Roof   0.00     0.00 -0.00
Exterior Wall   -369.8     -369.8 14.58
Interzone Wall   -476.6     -476.6 18.78
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   -172.5     -172.5 6.80
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -436.3       -436.3 17.20
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -657.8 -1758.2 0.00 -121.1 -2537.1  


Heating Peak Conditions

Value
Time of Peak Load 1/21 09:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 18.29
Zone Relative Humdity [%] 47.00
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00613
Peak Design Sensible Load [W] -3602.0
Estimated Instant + Delayed Sensible Load [W] -2416.0
Difference [W] -1186.0



Table of Contents

Report: Zone Component Load Summary

For: L003_P08

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 340.98 84.97   296.14 722.08 16.20
Lights 233.28 122.80 0.00   356.08 7.99
Equipment 486.00 121.94   0.00 607.94 13.64
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 22.34     65.75 88.09 1.98
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   -13.9     -13.9 -0.3
Interzone Ceiling   0.00     0.00 0.00
Other Roof   0.00     0.00 0.00
Exterior Wall   -112.0     -112.0 -2.5
Interzone Wall   -34.2     -34.2 -0.8
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   -237.1     -237.1 -5.3
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 344.00       344.00 7.72
Fenestration Solar   2736.18     2736.18 61.39
Opaque Door   0.00     0.00 0.00
Grand Total 1426.60 2668.76 0.00 361.89 4457.24  


Cooling Peak Conditions

Value
Time of Peak Load 9/21 14:00:00
Outside Dry Bulb Temperature [C] 29.00
Outside Wet Bulb Temperature [C] 22.37
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01428
Zone Dry Bulb Temperature [C] 24.00
Zone Relative Humdity [%] 45.33
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00842
Peak Design Sensible Load [W] 4014.99
Estimated Instant + Delayed Sensible Load [W] 4095.35
Difference [W] -80.4


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -132.0     -51.8 -183.8 95.19
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   -89.2     -89.2 46.19
Interzone Ceiling   0.00     0.00 -0.00
Other Roof   0.00     0.00 -0.00
Exterior Wall   27.92     27.92 -14.5
Interzone Wall   74.52     74.52 -38.6
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   171.79     171.79 -89.0
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -194.3       -194.3 100.65
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -326.4 185.04 0.00 -51.8 -193.1  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 12.75
Zone Relative Humdity [%] 45.09
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00410
Peak Design Sensible Load [W] -3020.3
Estimated Instant + Delayed Sensible Load [W] -141.3
Difference [W] -2879.0



Table of Contents

Report: Zone Component Load Summary

For: L003_P09

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 350.30 65.66   304.53 720.49 16.30
Lights 239.76 106.53 0.00   346.29 7.83
Equipment 499.50 94.52   0.00 594.02 13.44
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 18.29     58.60 76.89 1.74
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   -40.7     -40.7 -0.9
Interzone Ceiling   0.00     0.00 0.00
Other Roof   0.00     0.00 0.00
Exterior Wall   -63.0     -63.0 -1.4
Interzone Wall   -26.8     -26.8 -0.6
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   -188.1     -188.1 -4.3
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 355.89       355.89 8.05
Fenestration Solar   2644.80     2644.80 59.84
Opaque Door   0.00     0.00 0.00
Grand Total 1463.74 2592.93 0.00 363.13 4419.80  


Cooling Peak Conditions

Value
Time of Peak Load 9/21 13:00:00
Outside Dry Bulb Temperature [C] 28.58
Outside Wet Bulb Temperature [C] 22.25
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01428
Zone Dry Bulb Temperature [C] 24.00
Zone Relative Humdity [%] 45.48
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00845
Peak Design Sensible Load [W] 4010.46
Estimated Instant + Delayed Sensible Load [W] 4056.67
Difference [W] -46.2


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -121.4     -47.8 -169.2 93.69
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   -96.9     -96.9 53.66
Interzone Ceiling   0.00     0.00 -0.00
Other Roof   0.00     0.00 -0.00
Exterior Wall   19.08     19.08 -10.6
Interzone Wall   68.68     68.68 -38.0
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   171.67     171.67 -95.1
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -173.9       -173.9 96.34
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -295.3 162.54 0.00 -47.8 -180.6  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 13.12
Zone Relative Humdity [%] 46.13
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00430
Peak Design Sensible Load [W] -2861.4
Estimated Instant + Delayed Sensible Load [W] -132.8
Difference [W] -2728.6



Table of Contents

Report: Zone Component Load Summary

For: L003_P10

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 394.66 102.20   342.74 839.60 17.70
Lights 270.00 145.70 0.00   415.70 8.76
Equipment 562.50 146.70   0.00 709.20 14.95
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 22.34     65.44 87.78 1.85
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   -14.3     -14.3 -0.3
Interzone Ceiling   0.00     0.00 0.00
Other Roof   0.00     0.00 0.00
Exterior Wall   -117.6     -117.6 -2.5
Interzone Wall   -27.7     -27.7 -0.6
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   -232.2     -232.2 -4.9
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 348.22       348.22 7.34
Fenestration Solar   2735.36     2735.36 57.66
Opaque Door   0.00     0.00 0.00
Grand Total 1597.72 2738.11 0.00 408.18 4744.01  


Cooling Peak Conditions

Value
Time of Peak Load 9/21 14:00:00
Outside Dry Bulb Temperature [C] 29.00
Outside Wet Bulb Temperature [C] 22.37
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01428
Zone Dry Bulb Temperature [C] 24.00
Zone Relative Humdity [%] 45.48
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00845
Peak Design Sensible Load [W] 4238.24
Estimated Instant + Delayed Sensible Load [W] 4335.83
Difference [W] -97.6


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -133.8     -52.9 -186.6 93.30
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   -108.2     -108.2 54.09
Interzone Ceiling   0.00     0.00 -0.00
Other Roof   0.00     0.00 -0.00
Exterior Wall   22.16     22.16 -11.1
Interzone Wall   77.35     77.35 -38.7
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   193.88     193.88 -96.9
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -198.6       -198.6 99.27
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -332.3 185.19 0.00 -52.9 -200.0  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 13.05
Zone Relative Humdity [%] 46.70
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00434
Peak Design Sensible Load [W] -3200.3
Estimated Instant + Delayed Sensible Load [W] -147.2
Difference [W] -3053.1



Table of Contents

Report: Zone Component Load Summary

For: L003_P11

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 287.39 75.18   249.43 612.00 11.58
Lights 196.56 107.98 0.00   304.54 5.76
Equipment 409.50 107.40   0.00 516.90 9.78
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 26.94     87.96 114.90 2.17
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   80.28     80.28 1.52
Interzone Ceiling   0.00     0.00 0.00
Other Roof   0.00     0.00 0.00
Exterior Wall   -177.2     -177.2 -3.4
Interzone Wall   -58.1     -58.1 -1.1
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   61.00     61.00 1.15
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 530.53       530.53 10.03
Fenestration Solar   3302.11     3302.11 62.46
Opaque Door   0.00     0.00 0.00
Grand Total 1450.92 3498.63 0.00 337.39 5286.94  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 18:00:00
Outside Dry Bulb Temperature [C] 30.28
Outside Wet Bulb Temperature [C] 24.21
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 23.99
Zone Relative Humdity [%] 44.87
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00833
Peak Design Sensible Load [W] 4879.00
Estimated Instant + Delayed Sensible Load [W] 4949.55
Difference [W] -70.5


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -160.7     -88.3 -249.0 11.83
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   -607.9     -607.9 28.89
Interzone Ceiling   0.00     0.00 -0.00
Other Roof   0.00     0.00 -0.00
Exterior Wall   -231.7     -231.7 11.01
Interzone Wall   -509.1     -509.1 24.19
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   -128.8     -128.8 6.12
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -377.8       -377.8 17.95
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -538.6 -1477.5 0.00 -88.3 -2104.3  


Heating Peak Conditions

Value
Time of Peak Load 1/21 09:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 18.34
Zone Relative Humdity [%] 46.64
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00610
Peak Design Sensible Load [W] -3039.5
Estimated Instant + Delayed Sensible Load [W] -2016.0
Difference [W] -1023.4



Table of Contents

Report: Zone Component Load Summary

For: L003_P12

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 224.22 56.07   194.61 474.91 11.61
Lights 153.36 82.12 0.00   235.48 5.76
Equipment 319.50 80.10   0.00 399.60 9.77
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 21.81     71.16 92.96 2.27
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   65.68     65.68 1.61
Interzone Ceiling   0.00     0.00 0.00
Other Roof   0.00     0.00 0.00
Exterior Wall   -129.9     -129.9 -3.2
Interzone Wall   -45.2     -45.2 -1.1
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   40.93     40.93 1.00
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 410.20       410.20 10.03
Fenestration Solar   2546.55     2546.55 62.24
Opaque Door   0.00     0.00 0.00
Grand Total 1129.09 2696.38 0.00 265.77 4091.24  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 18:00:00
Outside Dry Bulb Temperature [C] 30.28
Outside Wet Bulb Temperature [C] 24.21
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 23.99
Zone Relative Humdity [%] 44.90
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00833
Peak Design Sensible Load [W] 3773.08
Estimated Instant + Delayed Sensible Load [W] 3825.47
Difference [W] -52.4


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -130.2     -71.9 -202.1 11.92
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   -465.3     -465.3 27.45
Interzone Ceiling   0.00     0.00 -0.00
Other Roof   0.00     0.00 -0.00
Exterior Wall   -185.9     -185.9 10.97
Interzone Wall   -444.0     -444.0 26.19
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   -97.5     -97.5 5.75
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -300.3       -300.3 17.71
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -430.5 -1192.7 0.00 -71.9 -1695.1  


Heating Peak Conditions

Value
Time of Peak Load 1/21 09:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 18.35
Zone Relative Humdity [%] 46.50
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00608
Peak Design Sensible Load [W] -2462.9
Estimated Instant + Delayed Sensible Load [W] -1623.2
Difference [W] -839.7



Table of Contents

Report: Zone Component Load Summary

For: L003_P13

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 2997.08 228.88   3116.24 6342.20 20.19
Lights 2227.85 466.86 0.00   2694.71 8.58
Equipment 4641.36 406.04   0.00 5047.40 16.07
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 98.19     601.94 700.13 2.23
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   567.13     567.13 1.81
Interzone Ceiling   0.00     0.00 0.00
Other Roof   0.00     0.00 0.00
Exterior Wall   323.65     323.65 1.03
Interzone Wall   1711.48     1711.48 5.45
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   2139.38     2139.38 6.81
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 1483.94       1483.94 4.72
Fenestration Solar   10398.41     10398.41 33.11
Opaque Door   0.00     0.00 0.00
Grand Total 11448.42 16241.82 0.00 3718.18 31408.43  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 09:00:00
Outside Dry Bulb Temperature [C] 27.68
Outside Wet Bulb Temperature [C] 23.51
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 25.13
Zone Relative Humdity [%] 45.92
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00914
Peak Design Sensible Load [W] 31068.38
Estimated Instant + Delayed Sensible Load [W] 27690.24
Difference [W] 3378.14


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -1031.2     -414.4 -1445.6 91.18
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   -837.8     -837.8 52.85
Interzone Ceiling   0.00     0.00 -0.00
Other Roof   0.00     0.00 -0.00
Exterior Wall   225.73     225.73 -14.2
Interzone Wall   492.21     492.21 -31.0
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   1651.11     1651.11 -104.1
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -1671.0       -1671.0 105.40
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -2702.2 1531.22 0.00 -414.4 -1585.4  


Heating Peak Conditions

Value
Time of Peak Load 1/21 08:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 12.67
Zone Relative Humdity [%] 49.02
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00444
Peak Design Sensible Load [W] -26111.8
Estimated Instant + Delayed Sensible Load [W] -1171.0
Difference [W] -24940.8



Table of Contents

Report: Zone Component Load Summary

For: L003_P14

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 214.75 41.95   186.39 443.09 11.63
Lights 146.88 69.20 0.00   216.08 5.67
Equipment 306.00 59.91   0.00 365.91 9.60
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 17.96     58.64 76.59 2.01
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   58.59     58.59 1.54
Interzone Ceiling   0.00     0.00 0.00
Other Roof   0.00     0.00 0.00
Exterior Wall   -90.4     -90.4 -2.4
Interzone Wall   -32.1     -32.1 -0.8
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   2.73     2.73 0.07
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 381.94       381.94 10.02
Fenestration Solar   2387.48     2387.48 62.66
Opaque Door   0.00     0.00 0.00
Grand Total 1067.52 2497.37 0.00 245.03 3809.93  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 18:00:00
Outside Dry Bulb Temperature [C] 30.28
Outside Wet Bulb Temperature [C] 24.21
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 23.99
Zone Relative Humdity [%] 44.84
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00832
Peak Design Sensible Load [W] 3533.48
Estimated Instant + Delayed Sensible Load [W] 3564.90
Difference [W] -31.4


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -107.5     -59.4 -166.9 10.68
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   -438.3     -438.3 28.04
Interzone Ceiling   0.00     0.00 -0.00
Other Roof   0.00     0.00 -0.00
Exterior Wall   -146.0     -146.0 9.34
Interzone Wall   -463.8     -463.8 29.67
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   -88.3     -88.3 5.65
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -260.0       -260.0 16.63
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -367.5 -1136.4 0.00 -59.4 -1563.2  


Heating Peak Conditions

Value
Time of Peak Load 1/21 09:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 18.41
Zone Relative Humdity [%] 46.84
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00615
Peak Design Sensible Load [W] -2283.9
Estimated Instant + Delayed Sensible Load [W] -1503.8
Difference [W] -780.1



Table of Contents

Report: Zone Component Load Summary

For: L003_P15

Timestamp: 2017-11-30 14:32:12

Estimated Cooling Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 391.63 99.65   339.86 831.14 12.18
Lights 267.84 143.22 0.00   411.06 6.03
Equipment 558.00 142.40   0.00 700.40 10.27
Refrigeration 0.00   0.00 0.00 0.00 0.00
Water Use Equipment 0.00     0.00 0.00 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00
Power Generation Equipment 0.00 0.00     0.00 0.00
DOAS Direct to Zone 0.00     0.00 0.00 0.00
Infiltration 48.75     158.25 207.00 3.03
Zone Ventilation 0.00     0.00 0.00 0.00
Interzone Mixing 0.00     0.00 0.00 0.00
Roof   138.12     138.12 2.02
Interzone Ceiling   0.00     0.00 0.00
Other Roof   0.00     0.00 0.00
Exterior Wall   -289.4     -289.4 -4.2
Interzone Wall   -363.6     -363.6 -5.3
Ground Contact Wall   0.00     0.00 0.00
Other Wall   0.00     0.00 0.00
Exterior Floor   0.00     0.00 0.00
Interzone Floor   121.58     121.58 1.78
Ground Contact Floor   0.00     0.00 0.00
Other Floor   0.00     0.00 0.00
Fenestration Conduction 700.47       700.47 10.27
Fenestration Solar   4364.31     4364.31 63.98
Opaque Door   0.00     0.00 0.00
Grand Total 1966.68 4356.31 0.00 498.10 6821.10  


Cooling Peak Conditions

Value
Time of Peak Load 7/21 18:00:00
Outside Dry Bulb Temperature [C] 30.28
Outside Wet Bulb Temperature [C] 24.21
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.01656
Zone Dry Bulb Temperature [C] 23.99
Zone Relative Humdity [%] 45.13
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00838
Peak Design Sensible Load [W] 6221.56
Estimated Instant + Delayed Sensible Load [W] 6322.99
Difference [W] -101.4


Estimated Heating Peak Load Components

Sensible - Instant [W] Sensible - Delayed [W] Sensible - Return Air [W] Latent [W] Total [W] %Grand Total
People 0.00 0.00   0.00 0.00 -0.00
Lights 0.00 0.00 0.00   0.00 -0.00
Equipment 0.00 0.00   0.00 0.00 -0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00
Water Use Equipment 0.00     0.00 0.00 -0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00
Power Generation Equipment 0.00 0.00     0.00 -0.00
DOAS 0.00     0.00 0.00 -0.00
Infiltration -290.5     -158.6 -449.1 15.38
Zone Ventilation 0.00     0.00 0.00 -0.00
Interzone Mixing 0.00     0.00 0.00 -0.00
Roof   -846.5     -846.5 28.99
Interzone Ceiling   0.00     0.00 -0.00
Other Roof   0.00     0.00 -0.00
Exterior Wall   -477.8     -477.8 16.37
Interzone Wall   -334.1     -334.1 11.44
Ground Contact Wall   0.00     0.00 -0.00
Other Wall   0.00     0.00 -0.00
Exterior Floor   0.00     0.00 -0.00
Interzone Floor   -205.8     -205.8 7.05
Ground Contact Floor   0.00     0.00 -0.00
Other Floor   0.00     0.00 -0.00
Fenestration Conduction -606.2       -606.2 20.77
Fenestration Solar   0.00     0.00 -0.00
Opaque Door   0.00     0.00 -0.00
Grand Total -896.8 -1864.2 0.00 -158.6 -2919.5  


Heating Peak Conditions

Value
Time of Peak Load 1/21 09:00:00
Outside Dry Bulb Temperature [C] -0.9
Outside Wet Bulb Temperature [C] -1.7
Outside Humidity Ratio at Peak [kgWater/kgAir] 0.00295
Zone Dry Bulb Temperature [C] 18.32
Zone Relative Humdity [%] 46.22
Zone Humidity Ratio at Peak [kgWater/kgAir] 0.00603
Peak Design Sensible Load [W] -4093.6
Estimated Instant + Delayed Sensible Load [W] -2760.9
Difference [W] -1332.7



Table of Contents

Report: Economics Results Summary Report

For: Entire Facility

Timestamp: 2017-11-30 14:32:12

Annual Cost

Electric Gas Other Total
Cost [£] 0.00 0.00 0.00 0.00
Cost per Total Building Area [£/m2] 0.00 0.00 0.00 0.00
Cost per Net Conditioned Building Area [£/m2] 0.00 0.00 0.00 0.00


Tariff Summary

Selected Qualified Meter Buy or Sell Group Annual Cost (£)
ELECTRICSERVICETARIFF Yes Yes ELECTRICITY:FACILITY Buy COMM ELECT 0.00
GASSERVICETARIFF Yes Yes GAS:FACILITY Buy COMM GAS 0.00



Table of Contents

Report: Tariff Report

For: ELECTRICSERVICETARIFF

Timestamp: 2017-11-30 14:32:12

General

Parameter
Meter ELECTRICITY:FACILITY
Selected Yes
Group COMM ELECT
Qualified Yes
Disqualifier n/a
Computation automatic
Units kWh


Categories

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
EnergyCharges (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DemandCharges (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ServiceCharges (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Basis (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Adjustment (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Surcharge (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Subtotal (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Taxes (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Charges

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max Category
ELECTRICSERVICECHARGE (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 EnergyCharges


Corresponding Sources for Charges

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
TotalEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Ratchets

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max


Qualifies

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max


Native Variables

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
TotalEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TotalDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
OffPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
OffPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MidPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MidPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsOffPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
OffPeakExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsMidPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MidPeakExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsShoulder 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsWinter 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotWinter 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsSpring 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotSpring 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsSummer 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotSummer 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsAutumn 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotAutumn 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
PeakAndShoulderEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakAndShoulderDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakAndMidPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakAndMidPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderAndOffPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderAndOffPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakAndOffPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakAndOffPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RealTimePriceCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AboveCustomerBaseCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BelowCustomerBaseCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AboveCustomerBaseEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BelowCustomerBaseEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Other Variables

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
NotIncluded 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Computation - Automatic

ELECTRICSERVICECHARGE FROM TotalEnergy
EnergyCharges SUM ELECTRICSERVICECHARGE
Basis SUM EnergyCharges DemandCharges ServiceCharges
Subtotal SUM Basis Adjustment Surcharge
Total SUM Subtotal Taxes

Table of Contents

Report: Tariff Report

For: GASSERVICETARIFF

Timestamp: 2017-11-30 14:32:12

General

Parameter
Meter GAS:FACILITY
Selected Yes
Group COMM GAS
Qualified Yes
Disqualifier n/a
Computation automatic
Units kWh


Categories

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
EnergyCharges (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DemandCharges (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ServiceCharges (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Basis (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Adjustment (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Surcharge (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Subtotal (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Taxes (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Charges

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max Category
GASSERVICECHARGE (£) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 EnergyCharges


Corresponding Sources for Charges

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
TotalEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Ratchets

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max


Qualifies

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max


Native Variables

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
TotalEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TotalDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
OffPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
OffPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MidPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MidPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsOffPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
OffPeakExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsMidPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MidPeakExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsShoulder 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsWinter 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotWinter 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsSpring 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotSpring 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsSummer 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotSummer 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsAutumn 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotAutumn 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
PeakAndShoulderEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakAndShoulderDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakAndMidPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakAndMidPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderAndOffPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderAndOffPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakAndOffPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakAndOffPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RealTimePriceCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AboveCustomerBaseCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BelowCustomerBaseCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AboveCustomerBaseEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BelowCustomerBaseEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Other Variables

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
NotIncluded 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Computation - Automatic

GASSERVICECHARGE FROM TotalEnergy
EnergyCharges SUM GASSERVICECHARGE
Basis SUM EnergyCharges DemandCharges ServiceCharges
Subtotal SUM Basis Adjustment Surcharge
Total SUM Subtotal Taxes